Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.5 LAccepted-Finance | ₹36.5 L | L1 | Accepted-Finance Being L1 |
| 2 | L2₹43.1 L+₹6.6 L (18.0%)Rejected-Finance | ₹43.1 L+₹6.6 L (18.0%) | L2 | Rejected-Finance Being not L1 |
| 3 | L3₹43.1 L+₹6.6 L (18.0%)Rejected-Finance | ₹43.1 L+₹6.6 L (18.0%) | L3 | Rejected-Finance Being not L1 |
| 4 | L4₹44.9 L+₹8.4 L (23.0%)Rejected-Finance DOOR NO 2 31 23 SECTOR 7 SBI COLONY MVP VISAKHAPATNAM 530 017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | ₹44.9 L+₹8.4 L (23.0%) | L4 | Rejected-Finance Being not L1 |
Tender Value
₹46.8 L
EMD Value
₹93,500
Closing Date
8 Oct 2024, 6:00 pmClosed
GE (I) DM, Visakhapatnam
GE (I) DM, Visakhapatnam
REPAIR REPLACEMENT OF OLD UNSV LT PANEL AND ALLIED WORKS AT DAS AND TELEPHONE EXCHANGE UNDER NAVAL DOCKYARD, VISAKHAPATNAM UNDER GE (I) DM VISAKHAPATNAM.
2024_MES_655354_2
8048/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naval Dockyard Visakhapatnam
As per tender documents
8 documents required · 8 mandatory
₹500
GE (I) DM, Visakhapatnam
₹93,500
Yes
22 Jan 2025
17 Sept 2024
10 Oct 2024
17 Sept 2024
8 Oct 2024
24 Sept 2024
Amount
Servicing, repair, maintinance of Air Circuit Breaker 800 Amps to 2000 Amps capacity by drawing out movable unit, forced air cleaning of movable and fixed unit, decarbonize breaker contracts and checking for any defects due to any flush/loose contact, cleaning of all fixed and moving contact point, terminal connection points with CTC, replacement of defective parts and re-fixing ACB, cables completes all as specified and directed. Note: (a) required male/female ACB contacts, trip coils, closing coils, electronic protection unit will be measured as supply only. (b) all cleaning agents are included in the quoted rate.
Supply only fixed contract of ACB 800A to 2000A all as specified and directed.
Supply only Moving contact of ACB 800A to 2000A all as specified and directed.
Supply only Electronic protection unit of ACB 800A to 2000A all as specified and directed.
Supply only shunt trip coil of ACB 800A to 2000A all as specified and directed.
Supply only closing coil ACB 800A to 2000A all as specified and directed.
Supply only LED Pilot lamps red, yellow and blue in colours of 22.5 mm dia to monitor on LT panel board suitable for 230 V AC supply all as specified and directed. Cat Part No:-1SFA619402R5231/32/33 Make:-Siemens/ C&S/ schneider/ ABB/ L&T/ Selzer
Supply only metering current transformer of 1000/5 Amps, Class-1, 15VA, all as specified and directed. Make:- Rishabh, Cat No- TW-06 or equivelent of Kappa/ AE
Supply only metering current transformer of 600/5 Amps, Class-1, 10VA, all as specified and directed. Make:-Rishabh, Cat No- TW-06 or equivelent of Kappa/ AE
Supply and fix LT 2000 Amps, 4 pole 50 KA breaking capacity, 415 V, 50 Hz, manual drawn out type and manually charged with micro processor ET6G trip unit, release protection system against over current, earth fault and short circuit with 2 NO + 2 NC auxiliary switch, main CTs, safety shutter, cradle guard, operating handles conforming to IEC 60947-2 & 3 all as specified and directed.
M&L for painting of outer surface of complete LT Panel board of size upto 2 m x 2 m comprising ACBs/MCCBs/SDFs, busbar chamber, swich gear chamber, metering chamber cable termination/tray using one coat of synthetic enamel spray painting after preparation of surface, providing protection cover to all metering equipment, switchgears, cleaning of all non-metalic surface after completion of painting with paint remover all as specified and directed.
S/F of LT heat shrink straight through cable joint suitable for cable size LT 1100 volts grade, 4 core, 150-185 sqmm all as specified and directed. Make :- 3M, cat No MHS/Ox1.1KV (HSLA-1/4C) or equivelent of Denson/M Seal/MS Seal/RPG all as specified and directed.
All as per item No. 15.00 above, but for cable sizes 240 to 300 sqmm. Make :- 3M, cat No MHS/Ox1.1KV (HSLA-5/4C) or equivelent of Denson/M Seal/MS Seal/RPG
Supply and fix rubber insulating mat in front of LT panel board of size 2 mm thick, 1m width upto 3.3 KV suitable for electrical shock safety of sizes 2m x 1m all as specified and directed. Make- RPG or equivelent as approved by GE
M&L earthing with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 m deep below ground level with top edge of the plate not less than 1.5 m below normal ground level connected to GI strip32x6 mm by means of nuts, bolts check nuts, washers of galvanised iron or steel connected to earth test point including excavation work in any strata Precasted PCC chamber with precasted PCC cover slab with GI protection pipe 40 mm dia light gde upto 7.5 mtr/20 mm dia tunnel pipe med grade but all as specified and directed.
M&L Earth continuity conductor or main earth lead fixed to wall of batten or recess or chases or buried in ground or drawn in conduct/pipe or any other indicated situation for loop earthy etc of 32x6 mm all as specified and directed.
S&F MCCB metal box enclosure suitable for 32A, 4P incl dismantling taking down unsv one all as specified and directed.
S&F MCCB metal box enclosure suitable for 63A, 4P incl dismantling taking down unsv one all as specified and directed.
S&F MCCB metal box enclosure suitable for 100A, 4P incl dismentling taking down unsv one all as specified and directed.
S&F 32A MCCB 3 pole 415V fixed type with 16 KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
S&F 63A MCCB 3 pole 415V fixed type with 16 KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
S&F 100A MCCB 3 pole 415V fixed type with 16KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
M&L for Dismantling old LT panel carefully and supply, installation, testing and commissioning of floor mounted cubical/trunk type indoor type made out of 2 mm thick CRCA steel sheet traded and powder coated, prewired, factory made and of 50x50x6mm angle and 75x40mm base with provision for one incoming and multiple outgoing as mentioned below, with suitable CT's, individual comparment dust and vermin proof, weather proof electrical panel and with Godrej type lock, cable glands etc. and consisting of the following all as specified and as directed :- (i) ETP Copper Bus bar of capacity 800 Amps for phases and neutral. (ii) MCCB 400 Amps 4 pole 36KA as incommer-01 Nos. (iii) MCCB 200 Amps 3 pole 36kA- 01 Nos (iv) MCCB 125Amps 3 pole 36kA-01 Nos
(v) MCCB 100 Amps 3 pole 36 kA -01 Nos out going (vi) MCCB 63 Amps three pole breaking capacity 16 kA -03 Nos as out going (vii) Digital Ammeter 0-2000 Amps-02 Nos . (viii) Digital voltmeter 0-500 Volts-02 Nos . (ix) Indication lamps RYB -03 sets. Note: (i) Drawing for LT panel showing layout of incoming and outgoing switch gear with capacity before errection shall be approved by Engr-in-Charge. (ii) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC foundation to fix the LT Panel enclosure.(iii) Thequoted rates are exclusive of ETP copper bus bar and switchgear (MCCB/MCB) will be measured and paid separately.
M&L for Dismantling old LT panel carefully and supply, installation, testing and commissioning of floor mounted cubical/trunk type indoor made out of 2 mm thick CRCA steel sheet traded and powder coated, prewired, factory made , with provision for one incoming and multiple outgoing as mentioned below, with suitable CT's, individual comparment dust and vermin proof, weather proof electrical panel and with Godrej type lock, cable glands etc. and consisting of the following all as specified and as directed :- (i) ETP Copper Bus bar of capacity 500 Amps for phases and neutral. (ii) MCCB 250 Amps 4 pole 36KA as incommer-01 Nos. (iii) MCCB 125 Amps 3 pole 16 kA -01 Nos out going (iv) MCCB 100 Amp 3 pole 16 kA-01 Nos (iv)MCCB 63 Amps three pole breaking capacity 16 kA -03 Nos as out going
(v) Digital Ammeter 0-2000 Amps-02 Nos . (vi) Digital voltmeter 0-500 Volts-02 Nos . (vii) Indication lamps RYB -03 sets. Note: (i) Drawing for LT panel showing layout of incoming and outgoing switch gear with capacity before errection shall be approved by Engr-in-Charge. (ii) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC foundation to fix the LT Panel enclosure.(iii) Thequoted rates are exclusive of ETP copper bus bar and switchgear (MCCB/MCB) will be measured and paid separately.
M&L for Dismantling old LT panel carefully and supply, installation, testing and commissioning of floor mounted cubical/trunk type outdoor type made out of 2 mm thick CRCA steel sheet traded and powder coated, prewired, factory made , with provision for one incoming and multiple outgoing as mentioned below, with suitable CT's, individual comparment dust and vermin proof, weather proof electrical panel and with Godrej type lock, cable glands etc. and consisting of the following all as specified and as directed :- (i) ETP Copper Bus bar of capacity 500 Amps for phases and neutral. (ii) MCCB 250 Amps 4 pole 36KA as incommer-01 Nos. (iii) MCCB 125 Amps 3 pole 16 kA -01 Nos out going (iv) MCCB 100 Amp 3 pole 16 kA-02 Nos
(v) Digital Ammeter 0-2000 Amps-02 Nos . (vi) Digital voltmeter 0-500 Volts-02 Nos . (vii) Indication lamps RYB -03 sets. Note: (i) Drawing for LT panel showing layout of incoming and outgoing switch gear with capacity before errection shall be approved by Engr-in-Charge. (ii) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC foundation to fix the LT Panel enclosure.(iii) Thequoted rates are exclusive of ETP copper bus bar and switchgear (MCCB/MCB) will be measured and paid separately.
M&L for Dismantling old LT panel carefully and supply, installation, testing and commissioning of floor mounted cubical/trunk type outdoor made out of 2 mm thick CRCA steel sheet traded and powder coated, prewired, factory made , with provision for one incoming and multiple outgoing as mentioned below, with suitable CT's, individual comparment dust and vermin proof, weather proof electrical panel and with Godrej type lock, cable glands etc. and consisting of the following all as specified and as directed :- (i) ETP Copper Bus bar of capacity 400 Amps for phases and neutral. (ii) MCCB 200 Amps 4 pole 36KA as incommer-01 Nos. (iv) MCCB 63 Amp 3 pole 16 kA-05 Nos
(v) Digital Ammeter 0-2000 Amps-02 Nos . (vi) Digital voltmeter 0-500 Volts-02 Nos . (vii) Indication lamps RYB -03 sets. Note: (i) Drawing for LT panel showing layout of incoming and outgoing switch gear with capacity before errection shall be approved by Engr-in-Charge. (ii) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC foundation to fix the LT Panel enclosure.(iii) Thequoted rates are exclusive of ETP copper bus bar and switchgear (MCCB/MCB) will be measured and paid separately.
M&L for Dismantling old LT panel carefully and supply, installation, testing and commissioning of floor mounted cubical/trunk type indoor made out of 2 mm thick CRCA steel sheet traded and powder coated, prewired, factory made , with provision for one incoming and multiple outgoing as mentioned below, with suitable CT's, individual comparment dust and vermin proof, weather proof electrical panel and with Godrej type lock, cable glands etc. and consisting of the following all as specified and as directed :- (i) ETP Copper Bus bar of capacity 500 Amps for phases and neutral. (ii) MCCB 250 Amps 4 pole 36KA as incommer-01 Nos. (iii) MCCB 125 Amps 3 pole 16 kA -01 Nos out going (iv) MCCB 100 Amp 3 pole 16 kA-02 Nos
(v) Digital Ammeter 0-2000 Amps-02 Nos . (vi) Digital voltmeter 0-500 Volts-02 Nos . (vii) Indication lamps RYB -03 sets. Note: (i) Drawing for LT panel showing layout of incoming and outgoing switch gear with capacity before errection shall be approved by Engr-in-Charge. (ii) Unit rate quoted include for necessary grouting / chipping of concrete and Anchor fastners and providing necessary PCC foundation to fix the LT Panel enclosure.(iii) Thequoted rates are exclusive of ETP copper bus bar and switchgear (MCCB/MCB) will be measured and paid separately.
Supply only 400A MCCB 4 pole 415V fixed type with 36KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
Supply only 250A MCCB 4 pole 415V fixed type with 36KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
Supply only 200A MCCB 3 pole 415V fixed type with 36KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
Supply only 125A MCCB 3 pole 415V fixed type with 16KA breaking capacity incl dismentling taking down unsv one all as specified and directed.
Supply only busbar ETP copper off sizes including drilling holes for fixing with other bus / cable connections complete all as specified and directed
Supply and fixing PVC XLPE insulated, armoured heavy duty cable with aluminium conductor, 1100 volts grade cross section area 35 sqmm 4 core incl dismantling taking down unsv one from wall, cable tray, trench complete all as specified and as directed
Supply and fixing PVC XLPE insulated, armoured heavy duty cable with aluminium conductor, 1100 volts grade cross section area 70 sqmm 3.5 core incl dismantling taking down unsv one from wall, cable tray, trench complete all as specified and as directed
Supply and fixing PVC XLPE insulated, armoured heavy duty cable with aluminium conductor, 1100 volts grade cross section area 240 sqmm 3.5 core incl dismantling taking down unsv one from wall, cable tray, trench complete all as specified and as directed
Supply and fixing PVC XLPE insulated, armoured heavy duty cable with aluminium conductor, 1100 volts grade cross section area 400 sqmm 3.5 core incl dismantling taking down unsv one from wall, cable tray, trench complete all as specified and as directed
S&F LT heat shrink cable end termination for cable sizes 35 to 120 sqmm 3.5 core, 1100 volts grade by cutting out damaged portion of xlpe insulated cable ends for the following sizes including disconnection cable ends from ACB/MCCB/Busbar and reconnection with existing new stainless steel bolts of size not less than 16 mm dia and 40 mm long complete all as specified and directed.
S&F LT heat shrink cable end termination for cable sizes 240 to 400 sqmm 3.5 core, 1100 volts grade by cutting out damaged portion of xlpe insulated cable ends for the following sizes including disconnection cable ends from ACB/MCCB/Busbar and reconnection with existing new stainless steel bolts of size not less than 16 mm dia and 40 mm long complete all as specified and directed.
M&L for dismantling and taking out all cable connection from all switchgear and earthing connection of the indoor panel board, removing carefully the complete panel board of size not less than 2 m x 2 m using sufficient man power from base of panel and keeping aside, re-construction of damaged panel foundation in same place or other specified location with brick-work, plaster, foundation bolt, white wash to new plastered surface, reinstallation of complete panel and necessary cable end connection to respective switchgears, earthing complete all as specified and directed. Note- (i) Relaying of cables due to change of foundation of panel shall be measured and paid separately (ii) required additional length of cables shall be measured and paid separately, (iii) cable joints if require will be measured and paid separately, (iv) required aluminium cable lugs, nuts, bolts and washers, foundation bolts, white wash will be inclusive of quoted rate (v) Brick work/plaster work will be measured and paid separately.
M&L for dismatling and relaying of cable off sizes after opening loop, on cable tray/wall/floor with proper clamp complete all as specified and directed.
S & F Hot dip Galvanised wire mesh cable trays 105 x 300 complete with tray, coupler, cover and cover clip to support clamps, securing properly to support strcture complete including dismanling from building wall more than 3 mtr hieght form FL comlete all as specified and directed. Make-Legrand
M&L for brick work with subclass `B' bricks, straight or curved on plan exc 6m mean radius, built in 1:6 cement morter for panel foundation incl dismantling taking out unsv one complete all as specified and directed.
M&L for rendering 10mm thick plaster on fair faces of brick work or concrete surfaces incl dismantling taking out unsv plaster complete all as specified and directed.
M/s SAI GANESH ENGINEERING ENTERPRISES (BID ID -3114585)
R AND A ASSOCIATES ENGINEERS CONTRACTORS (BID ID -3124273)
M/s SS Engineering Enterprises (BID ID -3124165)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .