DY INSPECTOR GENERAL(ADM), ITBP ACADEMY, MUSSOORIE
ITB POLICE, ACADEMY MUSSOORIE(UKD)
ARM OF 11 KVA SUB STATION AT ADM WING ITB POLICE ACADEMY, MUSSOORIE(UKD) FOR THE YEAR 2021-22
2021_ITBP_646488_1
ITBP/ACDMY/ENGR/21-10030
Open Tender
Electrical Works
Item Rate
180 days
ITBP ACADEMY, ADM WING, MUSSOORIE(UKD)
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
Exempted
17 Sept 2021
3 Sept 2021
14 Sept 2021
3 Sept 2021
13 Sept 2021
4 Sept 2021
Amount
Electrical works
Overhauling and Maintenance of OCB (disconnect the trolly from panel and dismantling of mechanism and other necessary part, cleaning of it by Kerosene, carbonate and reassemble of all gear set for the smooth operation and reassemble of trolly and insert in panel connected all wiring parts as per requirement and check the operation shell be smooth and proper)
Replacement of complete Tripping assembling of VCB
Providing and Replacement of Panel Spout complete GEC make OCB.
Overhauling and Maintenance of ACB (disconnect the trolly from panel and dismantling of mechanism and other necessary part, cleaning of it by Kerosene, carbonate and reassemble of all gear set for the smooth operation and reassemble of trolly and insert in panel connected all wiring parts as per requirement and check the operation shell be smooth and proper)
Re-insulation of 11KV old and used CTs by using insulation Paint HT Tape etc.
Opening cleaning of 11KV bus bar spout CTs by CTC thinner and insulation by using paint non moisturized complete 11KV bus bar spout, 3 Nos panel complete.
Providing, Replacement of 11KV CT 50/25/5 Amp double ratio protection & Metering GEC make
Complete testing of Transformer including minor repair like repairing of Transformer leakage of oil including replacement of oil seal, gasket, HT/LT bushing, Nut bolts packing of top cover sheet, Inspection sheet, and conservator tank complete.
Supply and replacement of silica gel breather
Dehydration of 11 KVA Transformer and OCB
Providing and fixing panel light different colour
Top up of Transformer oil in Transformer 1&2 complete as per direction of Engineer in-charge
Providing and Fixing of LT HRC fuse with base
RAM CHANDER GUPTA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .