Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.9 LAccepted-AOC 231 TRIBHUVAN COMPLEX MATHURA ROAD ISHWAR NAGAR SOUTH DELHI DELHI 110065 | SOUTH EAST DELHI | DELHI | 110065 | L1 | Accepted-AOC PO issued | |
| 2 | L2₹58.9 L+₹10.7 L (22.2%)Rejected-Finance | L2 | Rejected-Finance Higher rates | |
| 3 | L3₹63.8 L+₹15.6 L (32.4%)Rejected-Finance | L3 | Rejected-Finance Higher rates | |
| 4 | L4₹65.4 L+₹17.2 L (35.8%)Rejected-Finance 24 TOP FLOOR ADCHINI NEW DELHI 110017 | NEW DELHI | SOUTH DELHI | DELHI | 110017 | L4 | Rejected-Finance Higher rates |
| Sl No | Description | Qty | Unit | Dynamic Edge Solution L2 | AZURE MULTITRADE AND VANIJYA PVT LTD L1 | Exsol Energy Systems Pvt Ltd L3 | Naresh Poly Plastic L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply of Battery Bank for 2x130 KVA UPS system
Type : VRLA
Each cell voltage= 2V
Ampere rating of each cell = 850 AH
Total Battery Bank Voltage= 408 V
Ampere rating of Battery Bank: 850 AH
Minimum Number of cells per Bank: 204
Voltage limit of Inverter operation: 320V (Min voltage), 490V (Max voltage)
Absolute maximum voltage: 490 V
Float voltage per cell: 2.25V
Boost voltage per cell: 2.35V
Over all float voltage of Battery Bank = 459 V
Over all Boost voltage of Battery Bank: 480 V
DC Voltage stability: ±1V
Minimum DC Voltage per cell (ECV) = 1.75 V
Others details :-
1) The 408V, 830AH battery banks installed with 2x130 KVA Emerson make UPS system.
I) The bidder / supplier shall supply type tested battery as per IS:15549: 2004/IEC60896-21 & 22:2004 and IEC61427-2005. Over the range of at least 01 capacity per design and should have met requirement of service life test as per above stated IEC standards within last 7 yrs.
(Other detailed specifications/ technical data sheet /Standards as per Annexure I&II) | 2 | Nos | 36,78,854.4 ₹73,57,708.8 | 33,30,555.63 ₹66,61,111.26 Lowest | 39,36,377.6 ₹78,72,755.2 | 42,52,861.44 ₹85,05,722.88 |
| 2.00 | Buyback of old battery bank already installed at DCRTPP, Yamuna nagar. | 2 | Nos | 8,51,267.34 ₹17,02,534.68 | 8,69,601 ₹17,39,202 | 7,88,210.5 ₹15,76,421 Lowest | 10,83,240 ₹21,66,480 |
| 3.00 | Erection, Testing and Commissioning of New Battery Bank after dismantling of existing battery bank free of cost. Transportation of old dismantled battery bank either to store or out of DCRTPP shall be in the scope of firm.
Test shall be conducted in accordance with IEC60896-21&22: 2004. Other detail as per annexure attached.(Annexure-I&II)
Current Drain: 360 mA | 2 | Nos | 1,15,415.04 ₹2,30,830.08 | 70,800 ₹1,41,600 | 1,23,494.4 ₹2,46,988.8 | 21,240 ₹42,480 Lowest |
Tender Value
Refer Docs
EMD Value
₹1.3 L
Closing Date
1 Apr 2025, 1:00 pmClosed
SE MM STORE YAMUNA NAGAR
DCRTPP YAMUNA NAGAR
SUPPLY OF BATTERY BANK ERECTION TESTING AND COMMISSIONING AND BUYBACK OF OLD BATTERY BANK INSTALLED AT DCRTPP YAMUNA NAGAR
2025_HBC_429854_1
POM-14032-SUPPLY OF BATTERY BANK
Open Tender
Electrical Work/ Equipment
Supply
DCRTPP YAMUNA NAGAR
AS PER NIT DOC
2 documents required · 2 mandatory
₹1,180
Yes
₹1.3 L
Yes
25 Sept 2025
20 Feb 2025
4 Apr 2025
20 Feb 2025
1 Apr 2025
20 Feb 2025
Supply of Battery Bank for 2x130 KVA UPS system Type : VRLA Each cell voltage= 2V Ampere rating of each cell = 850 AH Total Battery Bank Voltage= 408 V Ampere rating of Battery Bank: 850 AH Minimum Number of cells per Bank: 204 Voltage limit of Inverter operation: 320V (Min voltage), 490V (Max voltage) Absolute maximum voltage: 490 V Float voltage per cell: 2.25V Boost voltage per cell: 2.35V Over all float voltage of Battery Bank = 459 V Over all Boost voltage of Battery Bank: 480 V DC Voltage stability: ±1V Minimum DC Voltage per cell (ECV) = 1.75 V Others details :- 1) The 408V, 830AH battery banks installed with 2x130 KVA Emerson make UPS system. I) The bidder / supplier shall supply type tested battery as per IS:15549: 2004/IEC60896-21 & 22:2004 and IEC61427-2005. Over the range of at least 01 capacity per design and should have met requirement of service life test as per above stated IEC standards within last 7 yrs. (Other detailed specifications/ technical data sheet /Standards as per Annexure I&II)
Buyback of old battery bank already installed at DCRTPP, Yamuna nagar.
Erection, Testing and Commissioning of New Battery Bank after dismantling of existing battery bank free of cost. Transportation of old dismantled battery bank either to store or out of DCRTPP shall be in the scope of firm. Test shall be conducted in accordance with IEC60896-21&22: 2004. Other detail as per annexure attached.(Annexure-I&II) Current Drain: 360 mA
Dynamic Edge Solution (BID ID -1226549)
Exsol Energy Systems Pvt Ltd (BID ID -1233769)
Naresh Poly Plastic (BID ID -1232388)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .