Electrical General work in connection with Commercial work "Comprehensive Improvement of dilapidated TTE Rest Rooms at NJP, MLDT, SGUJ, DJ, RDP, BLGT, HDB & KNE".
26_2026
26_2026
Open
6 Months
Unknown (Unspecified Location)
₹0
₹1.2 L
25 May 2026
25 May 2026
2 Jun 2026
Improvement of dilapidated TTE Rest Rooms at NJP, MLDT, SGUJ, DJ, RDP, BLGT, HDB & KNE".
Item- 1 Please see item breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
1 1 Supply, installation, testing & commissioning of Numbers 69.00 1193.00 82317.00
modular power unit complete with 32 Amp mini
MCB DP "C" series 3kA , 25 amps starter, 25 Amp
Socket and 25 Amp plug to be mounted on 6
module GI box, 6 module combined plate
concealed on wall and wiring by 6 sq mm, Single
Core FR-LSH PVC Insulated Industrial Grade
Copper Conductor (Unsheathed) Flexible Cables,
1100 Volts with earth coninuity wire by 1 sq mm
copper cable Conforming to IS: 694 to be drawn
through Rigid PVC conduit pipe not less than 20
mm dia as per instruction of Engineer incharge at
KATIHAR DIVISION-ELECTRICAL/N F RLY
2 2 Supply, installation, testing & commissioning of Numbers 69.00 54091.00 3732279.00
Inverter Split Air Conditioners 1.5 Ton, (BEE star
raying-5 star, Coil material-Copper, Echo-friendly
refrigerant, Nominal cooling capacity in Ton /
(kcal/hr)-1.5 Ton / 4500 kcal/hr) with all
accessories as per OEM suitable for operation on
230V AC ,single phase, 50 Hz as per instruction of
Engineer incharge at site. Re-mending work
should be done after installation of RAC. (with 1
pair outdoor wall stand)
3 3 Supply & wiring by 4 sq mm, Single Core FR-LSH Metre 5750.00 63.00 362250.00
PVC Insulated Industrial Grade Copper Conductor
(Unsheathed) Flexible Cables, 1100 Volts
Conforming to IS: 694 to be drawn through
double locked PVC casing capping of not less than
19 mm wide & 0.85 mm thick along with 1 sq mm
single core FR PVC insulated and unsheathed
copper wire for earth continuity as per instruction
of Engineer Incharge at Site.
4 4 Supply & wiring by 6 sq mm, Single Core FR-LSH Metre 1200.00 76.00 91200.00
PVC Insulated Industrial Grade Copper Conductor
(Unsheathed) Flexible Cables, 1100 Volts
Conforming to IS: 694 to be drawn through
double locked PVC casing capping of not less than
19 mm wide & 0.85 mm thick along with 1 sq mm
single core FR PVC insulated and unsheathed
copper wire for earth continuity as per instruction
of Engineer Incharge at Site.
5 5 Supply, fixing and commissioning of DLP-S-U-PVC Metre 150.00 805.00 120750.00
trunking of size 100 x 50 mm including
acessories like bends, elbows, junction box etc.
similar to M/s LEGRAND cat No. 638038 as per
instruction of Engineer Incharge at site.
6 6 Horizontal machine boring of 300 mm dia hole Metre 90.00 2538.00 228420.00
across track/Road/High drain etc. at a depth of
1.0 mtr below of ground level with suitable boring
instruments & neessary arrangement and as per
technical procedure.
7 7 Supply, laying, commissioning & testing of GI pipe Metre 270.00 850.00 229500.00
100 mm medium guage with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt etc. (For protection of
cable) as per instruction of Engineer incharge at
8 8 Supply, laying, commissioning & testing of HDPE Metre 256.00 70.00 17920.00
pipe 50 mm dia, PN-6 grade to be laid partly
along the p o l e / w a l l with suitable fixing
arrangement by MS clamp made of MS flat of size
50x6 mm and suitable size nut , bolt, washer etc
as per instruction of Engineer Incharge at site.
9 9 Supply, fixing, testing & commissioning of IP Numbers 18.00 10035.00 180630.00
66/67 thermoplastic cable junction box / loop box
of size (300 x 450 x 170) mm with knockouts &
04 nos terminals as per instruction of Engineer
Incharge at Site.
10 10 Supply, installation, testing & commissioning of Numbers 23.00 1190.00 27370.00
poly carbonate/Thermoplastic cable cable
junction box of size (155 x 210 x 92) mm with IP
67 grade protection with metric knock out with
terminals as per instruction of Engineer incharge
KATIHAR DIVISION-ELECTRICAL/N F RLY
11 11 Supply & erection of Earthing electrode complete Numbers 27.00 1856.00 50112.00
by 50 mm dia GI Pipe, medium gauge 3 mt long
including construction of earth pit and RCC pit
cover, earth continuity wire by 6 SWG GI earth
wire with salt, charcoal, soldered end terminal, GI
nut & bolt etc including connection to Platform
Electric metal pole as per Drg. No.-
PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as
per instruction of Engineer Incharge at site.
12 12 (A) Supply, installation, testing & commissioning Set 8.00 12330.00 98640.00
of 4 way VTPN MCCB DB (MCCB+12 modules)
with IP 43 grade protection, metal door with wire
sets, busbar, earth bar, blanking plates, cable ties
etc with supply and fixing of following MCCB/MCB
as per instruction of Engineer incharge at site.
Conforms to IS/IEC 60898 - 1:2002
15 15 (A) Supply, fixing & Commissioning of 6 way SPN Set 11.00 1212.00 13332.00
Distribution Board, Flush/Surface mounting, IP 43
grade protection with copper bus bar, fully
shrouded neutral bar, earth bar, cable ties, metal
double door as per IS 8623 - III as per instruction
of Engineer Incharge at Site.
Conforms to IS/IEC 60898 - 1:2002
Conforms to IS/IEC 60898 - 1:2002
18 18 (A) Supply, fabrication, erection, testing, Set 2.00 32916.00 65832.00
commissioning & painting of floor mounted
powder coated cubicle panel board (Modular look)
of suitable size (neither big nor small) ), outdoor
type with double door made of suitable size MS/GI
angle 50 x 50 x 6 mm, MS/GI flat 50 x 6 mm, 14
SWG MS sheet/Powder coated CRCA sheet with
provision of weather proof,rust proof,dust
proof,water proof having internal rubber gasket
with supply and fixing of following ACB/MCCB/Bus
bar/Meter etc. (Connections to be made by
copper strips, glands should be provided at cable
entry and exit, components should be
compartmentalized, Each compartment will be
provided with the door and pad locking
arrangement. The compartment illumination lamp
with door operated switch shall be provided for
each compartment. Panel board drawing
approval must be obtained with clear indication
of make of items of components):-
19 19 (B) Supply & fixing of onload changeover switch Numbers 2.00 24733.00 49466.00
630 amps Four Pole, 415 V 50 Hz, with Sheet
Steel Enclosure (with front handle) as per IS/IEC
60947-1&3 as per instruction of Engineer
Incharge at Site.
22 22 (E) Supply, Fixing & Testing of Copper bus bar Set 2.00 6830.00 13660.00
800 amps made of electrolytic grade copper
consisting of 4 bars ( 3 Ph and Neutral ) ( Bus bar
should have insulation cover)
23 23 (F) Digital voltmeter (0-500) amps and Digital Set 2.00 5581.00 11162.00
ammeter (0-500) amps with s/switch and CTs
KATIHAR DIVISION-ELECTRICAL/N F RLY
25 25 Laying, commissioning & testing of HT/LT Metre 1150.00 55.00 63250.00
XLPE/PVC cable of different sizes partly along the
pole and partly through ground in cable trench by
excavation of ground below 1/1.5 mt from ground
level with suitable fixing arrangement by MS
clamp of size 50x6 mm and suitable size nut,
bolt. Loading, Unloading & Carrying of cable to
actual work site by contractor's own
arrangement. (Aluminium Crimping Socket should
be provided for each Cable Termination). (Cable
will be supplied by Railway)
26 26 Excavation of cable trench (0.3 x 1.5) mtr below Metre 750.00 148.00 111000.00
ground level for laying of cable & refilling the soil
after digging the earth as per instruction of
Engineer incharge at site. Cable should be laid on
bedding of height 75 mm sand at the bottom of
trench, and covering it with additional sand of
height 75 mm and thereafter protecing it by
mean of bricks before refilling the soil as per IS
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.