Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.7 LAccepted-AOC 4578 STREET 15 15A AGGARWAL ROAD DARYAGANJ CENTRAL DELHI DELHI 110002 UDYAM DL 01 0031798 | CENTRAL DELHI | DELHI | 110002 | L1 | Accepted-AOC AOC accepted. | |
| 2 | L2₹48.2 L+₹1.4 L (3.00%)Rejected-AOC SHOP NO 5 OPP SHANI MANDIR PROFESSOR COLONY DISTT YAMUNA NAGAR HARYANA 135001 | YAMUNANAGAR | HARYANA | 135001 | L2 | Rejected-AOC AOC rejected. | |
| 3 | L3₹55.3 L+₹8.6 L (18.4%)Rejected-AOC H NO 698 SECTOR 10 PANCHKULA HARYANA 134109 | PANCHKULA | PANCHKULA | HARYANA | 134109 | L3 | Rejected-AOC AOC rejected. |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
6 Nov 2023, 6:00 pmClosed
GE Dehradun
GE (MES) Dehradun, Garhi Cantt, Mall Road, Tele - 01352750580
Repair and replacement of Over Head line, Cable, VCBs, Panels, Transformers and connected items at Anarwala cantt under AGE E/M-II of GE Dehradun.
2023_MES_612619_2
8660/A/E8
Open Tender
Civil Works
Item Rate
334 days
GE Dehradun
Class D cat b (ii)
8 documents required · 8 mandatory
₹500
GE Dehradun
₹98,000
Yes
31 Jan 2024
16 Oct 2023
8 Nov 2023
16 Oct 2023
6 Nov 2023
23 Oct 2023
Amount
Material and labour attending fault/ breakdown in LT Over Head line/ LT UG Cable/Service connection Cable/AC Connection due to any reason including removing of fault, and restoring the electric supply whole Anarwala area incl MH complete all as specified and directed.
Material and labour for attending fault/ breakdown in HT Over Head line /UG Cable due to any reason like falling of tree branches, Bird hits, Cracking of Pin/ Disc insulator, breaking Over Head conductor complete including patrolling of LT line, Meggering, removing of fault, replacement of insulator any type, replacement of fuses and restoring the feeder by trained person complete all as specified and directed for following areas :- Notes : (i) All T&P & safety tools required to complete job are included in the unit rate. (ii) Unit rates also included the conveyance & communication facilities required to complete the job. (iii) Unit rates also included the HT/LT fault rectification round the clock (24X7hrs) as fault rectification Electricians party should have ITI Passed & sound knowledge/experience in HT/LT field. (iv) Unit rate also incuded the suitable current rating of tinned copper fuses HT/LT tapes, suitable size of Alumn thimble lugs etc for insulated of cables(HT/LT)
(a) Patiya Pump house,ASC,127 EME incl jcoSupply and fix afa md accn and MH feeder (Approximate 8 KM go and back ) incl operation of VCB's installed at Sub stn MH Dehradun as and when required complete all as specified and directed.
(b) MAP Qtrs, KV school and 5gdr/414 fd hosp Feeder (Approximate 6 KM go and back) complete all as specified and directed.
(c) Old Anarwala Md Accn/Map qtrs of upper camp and 3 Punjab incl AW Pump house feeder (Approximate 4 KM go and back ) complete all as specified and directed.
Supply and fix Tinned copper fuse wire of different cap & size as required complete all as specified and directed.
Supply and fix Indoor type single phase Epoxy cast current transformer of ratio 100/50/1+1A,class : 1.0,burden : 15 VA,STC : 18.4 at 1 Sec ,SV/HSV : 11 KV/110V,ILV ; 70 KVp as per IS :2705 complete all as specified and directed.
Supply and fix in repair of disc type Insulator (three disc in series assembly) porcelain vitreous, white brown or green 145 mm height and 255 mm dia ball and socket type with tension clamp galvanized iron nut bolts & washers for conductors working pressure 33000 volt grade complete all as directed incl disconnection and taking down existing complete all as specified and directed.
Supply and fix in repair of Insulator pin type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 33000 volt grade complete all as directed incl disconnection and taking down existing complete all as specified and directed.
Supply and fix disc type insulator (single disc assembly) porcelain vitreous, white brown or green 145 mm height and 255 mm dia ball and socket type with tension clamp galvanized iron nut for conductors working pressure 11000 volt grade complete including disconnection and taking down existing insulator complete all as specified and directed.
Supply and fix Insulator pin type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 11000 volt grade complete including disconnection and taking down existing insulator complete all as specified and directed.
Supply and fix Insulator Post type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nut for conductor working pressure 11000 volt grade complete with fuse clamps including disconnection and taking down existing insulator complete all as specified and directed.
Material and labour for spraying of agricultural based chemical inside the installation of 33/11 KV MRS Anarwala sub stn & its surrounding to control the growth of unwanted herb, shrubs etc incl cutting, removing the vegetation growth & surface dressing all around the installation yard/ transformer /LT panel Board area external only to keep installation always clean and tidy condition. Note:-Installation/Yard shall be kept clean by removing shrub/bushes etc throughout contract period and same shall be measured & paid only once after completion of contract.
Repair to 33 KV Outdoor VCBs control wiring incl tripping ,measuring & protective devices with outdoor Marshaling box of 3.15 MVA ,33./11 KV OLTC TFR having OTI,WTI,Buckholz relay with Outdoor VCBs,OLTC& Indoor control tfr & Control panels with changing of Minor spares if reqd as per directed by Engrin charge. Note : (i) Control cable & Major Spares shall be measured & paid separately under relevent items.
Servicing 33 KV yard structure complete including replacement unserviceable jumper, sleeves vice type conductor, bolt nut and washers connecting lugs / thimble knife contact, PG clamps applying petroleum jelly to the moving as well as fixed contacts tightning all the connection for its smooth functioning preparing old painted surface of this structure such as poles, cross arms, bracing supports, clamp and back plate complete painting of two coats of anti corrosive weather proof heat resistant aluminium paints over a coat of red oxide zinc chrome primer and phase marking of post insulators, GOD, lightening arrester, CT,PT etc with red, yellow blue paint on all equipments inside the MRS all as directed at site by Engr-in -charge. Note: No extra payment will made for the spares reqd to keep the yard structure in satisfactory functional throughout contract period other than given in schedule complete all as specified and directed.
Supply and fix in repair/ replacement following parts of HT VCB 11 KV, AC 3 phase, 50 HZ indoor type & 33 KV Out door VCB for complete as per existing make all as specified and directed incl disconnection and taking down existing complete Make: Alstom/ABB HT VCB's complete all as specified and directed.
Spout set (set of three) shower and rose contacts.
Auxiliary Contactor.
Closing Coil 110/30 DC volts.
Shunt tripping Coil 110/30 DC volts.
Relay (PLA/Defferencial etc) 30/110 V DC,6A 250 V AC
Tripping lever.
Charging lever.
Changing gear for VCB.
Tripping pin.
Spring Charging Motor complete 220 Volts.
Vaccume interrupter bottle as per sample suitable for 11//33 KV VCB at MRS.
Digital 3 line display multifunction meter having features to measure Volt Ampere power factor active load reactive load etc.
HRC fuse 2/5/10 Amp complete all as specified and directed
Digital Volt meter 11/33 KV 3 phase range of accuracy 0.5 complete all as specified and directed
Digital Amp meter 11KV, 3 phase range of accuracy 0.5 for CTR 100/50/1+1 A complete all as specified and directed
Supplying in replacement of existing unserviceable control cable including laying or fixing with saddles or cable tie etc, jointing and testing LT PVC insulated copper conductor armoured electric power cable ISI marked with multistranded copper conductor heavy duty 1100 volts grade of 2.5 Sq mm 4 core complete all as specified and directed incl disconnection and taking down existing complete all as specified and directed.
Supply & fixing powder coated or hot dipped GI preforated type cable trays of size 100mm wide x 40mmx1.6 mm thick fixed to wall or iron gantery inclding all the try accessories,supports,bends,ankor fasteners,GI hardware etc complete all as specified and directed.
Excavation in trenches not exceeding 1.5m wide and not exc. 1.5m depth and getting out in soft/loose soil complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and exc. 1.5m depth and getting out in soft/loose soil complete all as specified and as directed.
Removing of excavated soil to a distance n exc 50 mtr and deposited where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25 cm in soft/loose soil complete all as specified and as directed.
Supply and laying dry river sand filling for cable protection in trenches/cable ducts complete all as specified and as directed. (Note : only punned thickness shall be measured).
Material and labour sub class B bricks locally available of size 23 x 11.5 x 7.5 cm laid dry width wise across the line of cable in trenches for protection of UG cable complete all as specified and directed.
Material and labour for un-reinforced precast concrete cable cover HV type 1, flat size 300mmx180mmx40mm as protection to under ground cable laid dry and flat adjoining each other complete all as specified and directed.
Supply and laying LG GI Pipe of size 150 mm bore on pole or road crossing for cable protection with complete making good surface of road complete all as specified and directed.
Supply and laying LG GI Pipe of size 100 mm bore on pole or road crossing for cable protection with complete making good surface of road complete all as specified and directed.
Supply and laying LG GI Pipe of size 50 mm bore on pole or road crossing for cable protection & earthing strip protection with complete making good surface of road complete all as specified and directed.
Supply and laying LG GI Pipe of size 40 mm bore on pole or road crossing for cable protection & earthing strip protectionwith complete making good surface of road complete all as specified and directed.
Material and labour for spraying of agricultural based chemical inside the installation to control the growth of unwanted herb, shrubs etc incl cutting, removing the vegetation growth & surface dressing all around the LT transformer installations /LT/Capacitor bank panel Board area and twp/four HT pole structure to keep installation always clean and tidy condition. Note:-Installations shall be kept clean by removing shrub/bushes etc throughout contract period and same shall be measured & paid only once after completion of contract.
Material and labour for removing the herb, shrubs, creepers etc on the LT/HT Poles(sigle/two/four) the to keep poles/structures always clean and tidy condition. Note:- All the Poles shall be kept clean throughout contract period by repeatedly by removing the grass / shrubs as many times reqd depending on the growth of grass measurement will be measured & paid only once throughout contract period only once.
Material and labour for stone graded course aggregate of 40 mm grade nominal size with out any vegitation or chemical including levelling/spreading surrounding HT/LT 2/4 pole structure,LT/HT panel complete all as specified & directed
Taking out of HT /LT cable ,11KV OR 1.1 KV of any size from ground or poles etc and testing for serviceability and kept aside for reuse including proper rolling, loading unloading, transportation etc complete all as specified and directed. Note:- Earth work for the same shall be measured and paid separately.
Laying only of existing serviceable cable HT/LT ,11KV OR 1.1 KV in ground retrieved against item No 31 here and before complete including unrolling, unloading, transportation etc testing connections complete all as specified and directed.
Material and labour PCC (1:3:6) type C2 using 40mm graded aggregate as in foundation for Post/Pole/ FPB /Transformer plinth plateform etc including fair finish even and fair to exposed surfaces without using extra cement complete all as specified and as directed.
Material and labour PCC (1:3:6) type C-1 (with using 20 mm graded stone aggregate) as coping of pole/FPB/TFR plinth plateform including necessary form work as required complete all as specified and directed.
Material and labour for fault detection in UG HT cable of any size any type at any depth with fault locator incl material T&P required for the same and testing complete all as specified and directed. Note 1- Joint, excavation laying only of cable shall be measured and paid seperately 2. Each fault shall be treated as one job and contractor have to address the said fault immediately.
Material and labour for under ground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 33000 volts (earthed) grade copper sheet wrapped cross sectional area 240 sqmm 3 core cable complete all as specified and directed.
Material and labour for under ground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts (earthed) grade copper sheet wrapped cross sectional area 95 sqmm 3 core including taking down of old unserviceable cable complete all as specified and directed.
All asper item no 37 here-in-before but cross- sectional area 120 sqmmx3core complete all as specified and directed.
All asper item no 37 here-in-before but cross - sectional area 240 sqmmx3core complete all as specified and directed.
Material and labour disconnecting and taking out old unserviceable damaged/burn out cable of any size & make and supplying, laying, jointing and testing LT underground cable, heavy duty cable of size 240x3.5 core, 1100 Volts, XLPE insulated and PVC sheathed, armoured, multi-stranded aluminium conductor cable conforming to IS , laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts duly protected in galvanised steel pipe of suitable sizes all bare conductor of cable including cable gland and lugs etc at both ends incl disconnecting and taking out unserviceable damaged cable complete all as specified and directed. Note : Excavation, earth work, cable sand cushioning & cable protection shall be measured separately under relevant items of this schedule.
All as per item no 40 here-in-before but cross -sectional area 95 sqmm x 3.5 core complete all as specified and directed.
All as per item no 40 here-in-before but cross -sectional area 50 sqmm x 3.5 core complete all as specified and directed.
All as per item no 40 here-in-before but cross -sectional area 16 sqmm x 4 core complete all as specified and directed.
All as per item no 40 here-in-before but cross -sectional area 10 sqmm x 2 core complete all as specified and directed.
S& fixing 1100 voits grade of heavy duty of size 16 x2 core (two single core flat or circular) stranded coductor of caple PVC insulated aluminium conductor ,served with inner sheathing of PVC tape and overall PVC sheathed in service connection complete all as specified and directed.
Material and labour for cable end jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185 sqmm including testing after jointing complete all as specified & directed.
All as per Item No 46 here-in-before but 11 KV 240 to 300 Sqmm indoor type complete all as specified and directed.
Material and labour for cable end jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185 sqmm including testing after jointing complete all as specified & directed.
All as per Item No 48 here-in-before but 11 KV , 240 to 300 Sqmm outdoor type complete all as specified and directed.
All as per Item No 48 here-in-before but 33 KV , 240 to 300 Sqmm outdoor type complete all as specified and directed.
Material and labour for straight through cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185 sqmm including testing after jointing complete all as specified & directed.
All as per Item No 51 here-in-before but 11 KV 240 to 400 straight through type complete all as specified and directed.
Material and labour for LT Cable,1.1 KV grade straight through jointing kit ,heat shrinkable type joint complete with jointing materials and accessories for 120 to 185 sqmmx3.5 core complete all as specified and directed.
Material and labour for LT Cable,1.1 KV grade straight through jointing kit ,heat shrinkable type joint complete with jointing materials and accessories for up to 95 sqmmx3.5/4 core complete all as specified and directed.
Material and labour for LT Cable,1.1 KV grade cable end jointing kit ,heat shrinkable type joint complete with jointing materials and accessories for 120 to 240 sqmmx3.5 core complete all as specified and directed.
Material and labour for LT Cable,1.1 KV grade cable end jointing kit ,heat shrinkable type joint complete with jointing materials and accessories for up to 50 to 95 sqmmx3.5 core complete all as specified and directed.
Material and labour for switch air break gang operated triple pole out door type 11 KV 50 cycle AC suitable for current rating upto 200 Amps mechanically operated mounted on porcelene insulators (9 insulators) and frame with operating mechanism from ground level with earth switch and including locking arrangement complete including taking out unser GOD complete all as specified and directed.
Material and labour for switch air break gang operated triple pole out door type (Vertical/Horizental) as reqd at site ,33 KV 50 cycle AC suitable for current rating upto 400 Amps mechanically operated mounted on porcelene insulators (9 insulators) and frame with operating mechanism from ground level with earth switch including taking out unser GOD complete all as specified and directed.
Supply and fix horn gap type of fuses,expuision type single pole, 33 KV mounted on post insulators porcelene type with gun metal clamps and copper horn complete of 400 Amp including two coats of aluminium paint over a coat of red oxide primer on MS work complete including taking out unser GOD complete all as specified and directed.
Supply and fixing female contact spring loaded having brass contacts suitable for GOD up to 400 Amp for working p[ressure 11000 volts ,galvanised iron bolts,nuts and washers for fixing with post insulaor or any other indicating situation complete all as specified & directed
Supply and fixing Male contact spring loaded having brass contacts suitable for GOD up to 400 Amp for working p[ressure 11000 volts ,galvanised iron bolts,nuts and washers for fixing with post insulaor or any other indicating situation complete all as specified & directed
supply and fixing copper braided belt 400mm long with MS Carrier suitable suitable for GOD up to 400 Amp for working p[ressure 11000 volts ,galvanised iron bolts,nuts and washers for fixing with post insulaor or any other indicating situation complete all as specified & directed
Material and labour for lightning arresters porcelene type 12 KV grade complete with all fittings, expulsion type,tranmission class, discharge capacity 65 Kilo Amps complete all as specified and as directed incl taking down old u/s complete all as specified and directed.
Material and labour for lightning arresters porcelene type 33 KV grade complete with all fittings, expulsion type, transmission class ,discharge capacity 65 Kilo Amps complete all as specified and directed.
Dismantling and taking out old unserviceable cross arms and Material and labour for cross arms, bracing, supports clamps back plates, gantry bay structure etc fabricated from structural steel section such as suitable I section channel ISMC angle iron and flat iron GI nut, bolt & Washers with welding, cutting, drilling hole etc for insulator bolts clamps in any shape and size including one coat of red oxide and two coats of epoxy heat resistant paint all complete all as specified and directed.
Dismantling existing steel poles/ struts, any size carefully for reuse including necessary excavation demolition of concrete shifting cost etc. and removing the old unserviceable rubbish etc complete all as specified and directed.
Fixing only Steel pole of any length & dia retreived against respective item no 66 incl loading,shifting,unloading errection in the vertical position all as directed & specified (Excavation and earth work and PCC for foundation channels, clamps ,nuts and bolts to be measured and paid for separately)
Supply and fix in repair of Aluminium conductor steel reinforced (ACSR) for over head line of any size stringing and jointing on poles fixed to insulator including, binding wires pointing sleeves, aluminium tap and PG clamp etc complete all as specified and as directed including taking out old u/s ACSR conductor any size and type complete all as specified and directed.
Material and labour for Earth continuity conductor on main earthing lead fixing to pole wall or buried in ground including bending/welding as per site requirement for earthing of GI strip 32 x6 mm including welding and jointing 02 Nos Nut, bolt & washer etc all as directed incl disconnection and taking down existing complete all as specified and directed.
Material and labour for Earth continuity conductor on main earthing lead fixing to pole wall or buried in ground including bending/welding as per site requirement for earthing of GI wire 8mm with protecton of 15 mm MG PVC pipe including welding and jointing 02 Nos Nut, bolt & washer etc with earthing point all as directed incl disconnection and taking down existing complete all as specified and directed.
Material and labour for earth continuity conductor or main earthing strip fixed to wall on batten or porcelain insulators or recess or chases or buried in ground fixed with poles or any other indicating situation for loop earthing etc as required using copper strip of size 32x6 mm complete all as specified and directed
Material and labour for Trimming/ prunning of tree branches upto 5 meters below & both sides to obtain clearance all around the LT over head lines / HT over head lines conductor upto 5 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as directed.
Supply and fixing HT Cable root indicator of cast iron embedded in PCC 1:3:6 type C2 (using 20 mm graded stone aggregate) of size 100x100x200 mm foundation up to ground level including necessary earh work in any of soil complete all as specified and directed
Supply and fixing danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white letters, figures and conventional skull bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT 25 x 20cm (11 KV) size complete all as specified and directed.
Material and labour servicing of four pole structure complete including replacement of unserviceable jumper ,sleeve vice type connector GI Clamps T Connector run through clamps,bolt nuts washer connecting lugs/thimbles knife ,contacts applying petrolling jelly to the moving as well fixed contacts ,tighting all the connection for its smooth functioning and prepararing old painted surface of the structure such as poles ,crooss arms,bracing and supports clamps ,back plate complete painting of one coats of anti corrosive aluminium paint complete all as specified and directed ,Marking the pole no/feeder name with black enamell paint complete all as specified and directed Note :No extra payment will be made for the spares reqd to keep the four pole structure in satisfactory functioning state throughout contract period other then given in schedulesdirected at site by Engr in charge.note : contacs & copper braided belt shall be paid & measured separately from the respective items if required.
All as per item no 75 here-in-before but 2 Pole structure complete all as specified and directed.
Material and labour for scraping of old paint from steel tubler pole 11 mtr height incl cross arms with out removing accessories and preparation of surfaces for repainting complete painting of one coats of anti corrosive aluminium paint complete all as specified and directed ,Marking the pole no/feeder name with black enamell paint complete all as specified and directed.
Cutting existing road/hardstand of any type by using crow bar chisel uprto a depthof 30 cm for laying GI pipe including making good the surface by returning filling watering ramming in layers 150 mm thick PCC 1:2:4 over 200 mm thick hard core of broken bricks/stones over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Material and labour for transformer cable boxes or LT panel board cover/ panel doors etc made out of 3.0 mm CRCA sheet duly powder coated complete to make the system safe and secure complete including making hole nut bolts washer etc all as per site requirement complete all as specified and directed.
Material and labour for earthing complete with galvanized steel plate electrodes of size 600mm x 600mm x 6mm thick buried directly in ground with earth pit not less than 2.25m deep below normal ground level with top edge of plate not less than 1.5 m below normal ground level connected to galvanized strip of 32x6 mm earth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanized iron pipe 40 mm bore (light grade) including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 30x30x10 cm with one handle for lifting made out of 8 mm dia MS bar funnel wire mesh 20 mm bore galvanized iron pipe (medium grade) for watering charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part 1 including testing on completion all as specified and directed including demolition to existing earthing. NOTE 1. The unit rate includes for protection pipe 40 mm dia and GI strip 32x6 mm dia from top of earth plate up to 7.5 meter above ground level complete all as specified and directed.
Material and labour for replacement of unserviceable earthing with Copper electrode chemical advance maintenancefree chemical gel earthing copper electrode 50mm dia thick buried directly in ground vertically to a depth not less than 3.00 mtr below ground level filled with highly conductive metalic compound mixture CCM with the permanent sealing of the both end, outer dia pipe 50mm with strip terminal 50x6 with terminal holes incl one bag 50 kg of bfc compound, earth connected with earth lead copper strip of size 32x6mm by means of bolts, Nuts, Check Nuts and washers of galvanized iron and thimbles and other end of the earth wire connected to transformer body/neutral point/panel boards etc protected by galvanized iron pipe LG 40/50 mm bore, PVC chamber as per manufacturer instruction and testing on completion. Note: (i) Earthing has to done by CPRI approved firm and if the desired earth resistance is not found within permissible limit shall be redone by contractor at no extra cost(ii) Copper strip and Protection pipe of GI shall be measured & paid separately in the relivent items.
Discnnecting all electrical connections of transformers outdoor type up to 500 KVA HT 11KV/433 V, 3 Phase 50 HZ with off load tapping and standard fitting or 3 way HT 11 KV RMU/ LBS dismounting from plate form or structure(four/two pole) as directed,shifting of proposed site (with in juridistiction of GE DDN,reinstalling on plateform or proper load balancing as per engineering practice ,including connected panel all as directed including making all arrangements (cranes,truck etc) for lifting and transportation complete NOTE : Item rate incl necessary transport,tools & plant and labour ,lugs thimble PVC sleeves etc required for shifting ,installation,connection and commissioning of transformer.
Supply and fix in replacement of one set of 3 Pole micro processor based feeder protection relay with instantaneous 2 Nos over current (50, 50N) element and 1 No Instantaneous earth fault (50, 50N) (o/c setting 50% - 200% and earth fault setting 20 % - 80% having large LCD display of all the parameters ie all three phase current at a time, type of fault, fault history etc operating voltage 110 Volts DC suitable for 11 KV indoor VCB panel including calibration of relay accordingly complete all as specified and directed incl disconnection and taking out existing complete and making necessary modification in existing wiring (if any required). Make ABB Cat No REF611 or Equvalent in Schneider/Siemens/Crompton
Dismantling fencing wire mesh,any type complete all as specified and directed.
Dismantling RCC posts or sruts any section ,including taking out embedded portion and making good disturbed ground complete all as specified and directed.
Excavation in post holes (or similer holes) each n exc 0.5 cum.getting out and removing surplus soil to a distance n exc 50m complete all as specified and directed.
Supply and fixing mild steel work such as in angle iron for posts,horns including flat iron fillets ,nut,bolts,10mm dia MS bars as in the bar fixed to fencing posts for fixing of chain link fencing ,securing its etc including necessary cuttings,drilling,bolting or reveting etc as per site requirement and other similer works complete mild steel ,conforming to Fe-290 Gde E-165 complete all as specified and directed.
Supply only chain link fencing made of 4mm dia mild steel galvanised wire and 100x100mm mesh complete all as specified and directed.
Fixing only chain link fencing including line wires, any mesh,size and type to any any type to standards,rails,straining bolts etc including provision of binding wire complete all as specified and directed.
Taking down existing connection from LT Panel /Busbar chamber/Feeder Piller/Electric Poles/Building carefully (any capacity,any type) carring out repair work at site including replacement of unserviceable /defective screw/nut & bolts/washers/lugs/Spreaders/Hinges of doors/Repairt to locks& handles /Indication lamps/Meters/Cables glands/Busbar (Copper/Aluminium)etc rifixing the fittings in its original or other location after complete two coat of enamel paint over a coat red oxide primer after scrapping thorougly the existing correded paint ,dirt/dust,oil &grease with painting of inside & outside panel incl cleaning/scraping inclding removal of bushes,creapers and trimming of branches around the LT panel /busbar chamber/Feeder Piller/Electric poles inclding takingout fixing site complete all as specified and directed Note : (i) if any major repair is required , attending complaits and replacement of any nature in LT power network at any point and time,the major items ie MCCBs,ST through jont ,PCC etc shall be replaced with respective items of Sch A with paiad saparately (ii) Tools,ledder,vehicle required to carry out the work shall be provided by the contractor.
Painting to sub stn gates of size 230x170cm with two coat of enamel paint over a coat red oxide primer after scrapping thorougly the existing correded paint , dirt /dust,oil & grease complete all as specified and directed.
Material and labour for preparing old surface plastered on wall and one coat white washing on old decorateed surface of existing structure wall at MRS complete all as specified and directed.
Supply and fix MCCBs in existing LT panel box /Feeder piller boxes of capacity 400 Amps 4pole breaking capacity 35KA Ics=100% Icu with thermal as well as magnetic balance adjustable setting type inclding taking down old unserviceable burnt out MCCB complete all as specified and directed.
Supply and fix MCCBs in existing LT panel box /Feeder piller boxes of capacity 200 Amps 4pole breaking capacity 25 KA Ics=100% Icu with thermal as well as magnetic balance adjustable setting type inclding taking down old unserviceable burnt out MCCB complete all as specified and directed.
Supply and fix MCCBs in existing LT panel box /Feeder piller boxes of capacity 100 Amps 4pole breaking capacity 16 KA Ics=100% Icu with thermal as well as magnetic balance adjustable setting type inclding taking down old unserviceable burnt out MCCB complete all as specified and directed.
Taking out transformer from its position from location under GE DDn for repair/servicing/rewinding of following capacity with OLTC ,11/.415 KV, disconnecting/ opening HV,LV electrical ,earthing connections complete with transportation to authorised workshop (upcl authorised company as approved by accepting officer making necessary arrangements of T&P (Crane,recovery,vehicle etc) complete all as specified and directed.
100 to 250 cap
315 to 500 cap
Material and labour for opening of transformer top cover by extraction ,removing of serviceable/unserviceable nuts bolts and washers etc and Lifting primery(HT) and secondry coil (LT) ,dismatling of transformer complete part by part carefully & display all the parts with out damaging any portion for inspection complete ,removing of trf oil for filtteration or changing as per die elecric strengh and condition of oil incl checking of leakage of transformer body and welding wks required for making tfr body leak proof complete all as specified and directed for the following capacity transformers Note : Dehyderation,Filteration,new oil for changing/topping up, copper winding wire ,bushing,tfr cover gasket etc shall be measured and paid separetely under respective items of this sch.
100 to 250 cap
315 to 500 cap
Material and labour for trasformer winding including taking out and testing for serviceability and rewinding the same with fresh copper wire or strip incuding insulation paper bobins,press board incl replacement of sudry itens whereever required comlete and keeping the same into the hot air oven till the moisture will remove and insulating resistance improves to satisfaction level with heating ,drying etc complete ,reassembling the same in original position with all existing seviceable parts and new parts as per required complete all as specified and directed Note : Old unserviceable copper scrap will be retaned by contractor under sch of credit
Material and labour for unserviceable cracked/worn out synthetic rubberised cork gasket sheet 6mm thick for top cover of transformer of follwoing cap incl nut bolt ,washers complete all as specified and directed
Material and labour for defective worn out HT bushing rod(Stud) complete made out of copper/brass with nut &washers for as per site requirement of following cap complete all as specified & directed
Material and labour for defective worn out LT bushing rod(Stud) complete made out of copper/brass with nut &washers for as per site requirement of following cap complete all as specified &directed
Material and labour for complete overhauling of On Load Tap Changer (OLTC) and including replacement of wiring conductors ,connectors including wiring of control cable connections complete all as specified and directed
Supply & filling the new transformer oil, confirming to IS ,die electric strengh of oil shouid not less then 50 KV at 2.5 mm gap of for topping up/replacement to required level of transformer complete all as specified and directed.
Supply and fix transformer breathers transparent of standard size suitable for 3.15 MVA transformers 33/11 KV volts cast alluminium transparent type including removing the existing u/s one complete all as specified and directed.
Filtration/dehyderartion of the existing transformer oil at site of any make of transformer and capacity upto required dielectric strength as per IE rules and refilling in the transformer upto required level complete all as specified and directed. (The diectric strength should not be less than 50 KV at 2.5 mm gap after filtration process)
Supply & Fixing in replacment of aluminium body silica gel breathers of standard size suitable for up to 500 KVA Transformers 11KV/433 volt transparent type including removing to existing unserviceable one complete all as specified and directed.
Taking out the old Silica gel in the breather of transformer and supply and refilling new Silica gel in the breather complete all as specified and directed.
Return back from work shop with placement of transformer to its position at location under GE DDn after repair/serviceing/rewinding inclding painting complete with two coats of synthetic enemal paint on tfr body incl cooling coils/fins by removing of all dirt ,grease etc marks using chemical or hot blow lamp of cap 11/.433KV ,Reconnecting HV,LV electrical connections,along with following other wks like checking & testing of HT Line/HT Cable ,HT Switch gearr etc complete all as specified and directed for the following capacities transformerc NOTE : (a) All routine tests will be carried uut at work shops (b) Transformer will have warranty of 6 month from the date of refixing at site (c) Any other work required to carry out above job in inclusive
Material and labour for Preventive maintenace /repairs to transformer step down 11 KV/.433 KV of any type & cap up to 500 KVA of any make including cleaning the transformers externally througly with lint free cloth ,tightening the HT/LT terminal nuts,opening the top cover for replacing the gaskets & bushings etc replacing the worn out copper alloy nuts-bolts and replacing the LT side cable lugs with tapping of taplon taps incl tighting all connectins with earthing terminals complete inclding painting complete with two coats of synthetic enemal paint on tfr body incl cooling coils/fins by removing of all dirt ,grease etc marks using chemical or hot blow lamp all as specified & directed NOTE : all other items which are required shall be measured and paid separetely under respective items of this sch.
Supply,design,transportation,installation and commissioning of 11KV 3 phase 50 Hz 3way RMU (with 01 No SF6 insulated VCB for outgoing and two nos for LBS for incoming ) factory made, floor mounted,out door type enclosure of protection class IP 54 suitable for HT 11 KV 630 Amp 3 phase ,3 wire earthed system (switching in SF 6 filled tank at 1.2 bar with manometer ,pressure gauge indicator having protection Class IP 67) Rated Symetrically interrupted current 21 KA ,Rated Power frequency 50 Hz,dry withstand voltage 28 KV RMS for 1 minut, Rared Power frequency wet with stand voltage 21 KV RMS for 10 seconds, Rated lighting impulse eith stand peak voltage (BID) 75 KV ,capacitive indication for incoming and outgoing ,copper busbar with interlocking switch and earth bar with earth switch including self powered alfa numeric relay suitable for 3 O/C and E/F and short circuiting facility. The breaker shouid be for 240 Sqmm cable as incoming and outgoing complete all as specified and directed.
Supply,Installation, Commission and testing of type tested LT panel outdoor type LT(415 volts,50hz,3 phase 4 wire supply) factory assembeled,weather & vermin proof(protection class IP43) FABRICATED OUT OF 3.15mm thick CRCA sheet with front hinges opening ,rubber lining,locking arrangement,powder coated extermally and internally including cable glands of suitable to accommodate and inclding following including taking down old unserviceable panel complete all as specified and directed. (i)Aluminium busbar consisting of four no of capacity 300 amps duly insulated with heat shrinkable sleeve 1.1 KV grade mounted on heavy duty epoxy insulator . (ii) The minimum size of feeder piller box shold be 1000mmx600mmx500mm (iii) MCCB 415 volt ,200amps ,4pole,adjustable thermal magnetic release 80 to 100% ,35 KA (Ics=100%Icu)-01 (iv) The panel shoud be fixed on and including angle iron stand made out of 50x6mm thick 60 cm height duly grouted 30 cm below ground level in PCC all as directed. (v) Item rate includs excavation ,pcc &earth work reqd for taking out old existing cable incl lugs thimble &relaying the same.
Note :-(i) for srl no 111,112 - All type test cirtificates with switch gear (ACB/MCCB) confirmimg to IEC 614398/2011 para 1&2 shall be submitted by the contractor before execution of work. (ii) Drawing for LT Panel of suitable specific size shall be submitted with accommodate all the controls & suitable size of Bus bar incl provn of measuring instuments /indication lamps before execution of wks.
JS CONSTRUCTION COMPANY
bharat contrectors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .