| 1.00(A) SUPPLY:- Design, Manufacture, Supply, Packaging, fabricating, galvanising & Forwarding, Transportation, Delivery at site of 132 KV Transmission tower materials. | |||||
| 1.01TOWER STRUCTURES | |||||
| 1.02 | Designing, Fabrication, Testing and Supply of Lattice Type Hot Dip Galvanized Steel Towers including packing and forwarding, transportation charges etc for 132 KV D/C Transmission Line complete with all tower parts & Extensions including step bolts, hangers, D-shackles etc. complete in all respect as per scope & Technical specifications | 13.08 | MT | 1,75,600 ₹22,96,848 Lowest | 1,82,700 ₹23,89,716 |
| 1.03 | Supply of Hot Dip Galvanised Nuts & Bolts of sizes as per the IS in vogue. | 0.63 | MT | 1,79,600 ₹1,13,148 Lowest | 1,82,700 ₹1,15,101 |
| 1.04 | Fabrication, galvanisation and supply of stub legs (110x110x10x3500) with requisite cleats. | 0.69 | MT | 1,82,333 ₹1,25,809.77 Lowest | 1,82,700 ₹1,26,063 |
| 1.05 | Fabrication, galvinisation and supply of anti climbing devices, Bird guard, Danger plates, phase plates, number plates , circuit plates and other allied accessories for 03 No. A+3 Kamani Type tower ( Complete 03 set for 03 No. A+3 Kamani type Tower) | 3 | Set | 15,000 ₹45,000 | 13,200 ₹39,600 Lowest |
| 1.06 | Supply of earthing material for A+3 Kamani Type tower including all accessories ( Normal earthing) | 3 | Set | 6,000 ₹18,000 Lowest | 22,000 ₹66,000 |
| 1.07CONDUCTOR AND HARDWARE FITTINGS SUITABLE FOR 0.2 ACSR CONDUCTOR | |||||
| 1.08 | Vibration Dumpers 2no./phase/tower for panther conductor. | 36 | No. | 3,400 ₹1,22,400 Lowest | 4,300 ₹1,54,800 |
| 1.09 | Vibration Dumpers 2no./tower for earthwire. | 6 | No. | 3,000 ₹18,000 Lowest | 3,200 ₹19,200 |
Tender Value
₹1.1 Cr
EMD Value
₹2.3 L
Closing Date
21 Dec 2023, 4:00 pmClosed
THE EXECUTIVE ENGINERR TLMD III AMARGARH SOPORE
OFFICE OF THE EXECUTIVE ENGINERR TLMD III AMARGARH SOPORE
TURNKEY PROJECT FOR INSERTION OF 03 NO TOWERS ON 132 KV D C AMARGARH KUPWARA TRANSMISSION LINE
2023_PDD_235642_1
EE/TLMDA/09 OF 2023
Open Tender
Electrical Works
Turn-key
180 days
BARAMULLA KUPWARA
AS PER SBD
8 documents required · 8 mandatory
₹1,500
THE EXECUTIVE ENGINEER TLMD III AMARGARH SOPORE
₹2.3 L
OFFICE OF THE EXECUTIVE ENGINERR TLMD III AMARGARH
30 Jan 2024
2 Nov 2023
23 Dec 2023
2 Nov 2023
21 Dec 2023
9 Nov 2023
2 Nov 2023 - 15 Dec 2023
16 Dec 2023
Amount
(A) SUPPLY:- Design, Manufacture, Supply, Packaging, fabricating, galvanising & Forwarding, Transportation, Delivery at site of 132 KV Transmission tower materials.
TOWER STRUCTURES
Designing, Fabrication, Testing and Supply of Lattice Type Hot Dip Galvanized Steel Towers including packing and forwarding, transportation charges etc for 132 KV D/C Transmission Line complete with all tower parts & Extensions including step bolts, hangers, D-shackles etc. complete in all respect as per scope & Technical specifications
Supply of Hot Dip Galvanised Nuts & Bolts of sizes as per the IS in vogue.
Fabrication, galvanisation and supply of stub legs (110x110x10x3500) with requisite cleats.
Fabrication, galvinisation and supply of anti climbing devices, Bird guard, Danger plates, phase plates, number plates , circuit plates and other allied accessories for 03 No. A+3 Kamani Type tower ( Complete 03 set for 03 No. A+3 Kamani type Tower)
Supply of earthing material for A+3 Kamani Type tower including all accessories ( Normal earthing)
CONDUCTOR AND HARDWARE FITTINGS SUITABLE FOR 0.2 ACSR CONDUCTOR
Vibration Dumpers 2no./phase/tower for panther conductor.
Vibration Dumpers 2no./tower for earthwire.
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255 mm dia. Creepage total 430 mm and 260 mm protected. 3 no. for S/C, 6 no. for D/C suspension strings per tower @ 10 discs per string
Single Suspension Fittings for panther shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 16 mm. (3 No,S/C 6NoD/C Per Sus. Tower)
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
Earthwire Suspension Clamps of standard make, as per the IS in vogue.
Earthwire Vibration Dampers of standard make, as per the IS in vogue
(B) HANDLING, STORAGE, PRESERVATION, WATCH AND WARD , ERECTION / INSTALLATION, TESTING AND COMMISSIONING OF MATERIAL (EXCEPT CIVIL WORKS)
TOWER STRUCTURES
Erection of Lattice Type Hot Dip Galvanized Steel Towers including packing and forwarding, transportation charges etc for 132 KV D/C Transmission Line complete with all tower parts & Extensions including step bolts, tower nuts and bolts, hangers, D-shackles etc. complete in all respect as per scope & Technical specifications
Erection of anti climbing devices, Bird guards, Danger plates, phase plates, number plates, Circuit plates and other allied accessories for 03 No. A+3 Kamani type tower.
Placing/Fixing of earthing for towers including all accessories ( Normal earthing)
Tag welding of towers 1st two stories/ sections including all the material required for the said Job ( Complete job)
CONDUCTOR AND HARDWARE FITTINGS SUITABLE FOR 0.2 ACSR CONDUCTOR
Erection/fixing of Vibration Dumpers 2no./phase/tower for panther conductor.
Erection/fixing of Vibration Dumpers 2no./tower for earthwire.
Erection/fixing of Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255 mm dia. Creepage total 430 mm and 260 mm protected. 3 no. for S/C, 6 no. for D/C suspension strings per tower @ 10 discs per string
Erection/fixing of Single Suspension Fittings for panther shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 16 mm. (3 No,S/C 6NoD/C Per Sus. Tower)
Erection/fixing of Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
Erection/fixing of Earthwire Suspension Clamps of standard make, as per the IS in vogue.
Erection/fixing of Earthwire Vibration Dampers of standard make, as per the IS in vogue
(C) Civil Works including Design, Supply, Execution/Laying of A-Type Tower foundation.
(A) Foundation work for 132 KV A-Type Tower structure foundation including Earthing of this tower structure etc. ( Complete Job)
Site clearance at tower foundation including removing of vegetation , thorns, shrubs , trees, Jungle clearance.
Surveying, Tower spotting , tower profiling and scheduling , pit marking including checking of alignments, framing of drawings and other allied design works for such 03 No. A -type Tower ( Complete Job for three no towers to be inserted at various locations)
Excavation in 30% dense/hard/muddy soil and 70% in diintegrated or soft rock for any section including all labour, POL, hire charges of equipments, dewatering of pits and T&Ps etc. including sheeting & shoring, dewatering, lifting, handling and stock piling of excavated materials, back filling with excavated or borrowed earth once foundation is laid and disposal of surplus excavated earth as directed for all leads & lifts complete as per specification, construction drawings and direction of Engineer-in-charge.
Stub setting using proper template as per approved design including its transportation and carriage.
Fixing and placing in position of stub legs including alignment of tower foundation.
High yield strength cold deformed steel reinforcement bars conforming to IS: 1786 for R.C.C. or any other work including the cost of all materials, binding wire, labour, hire charges of equipments and T&P, bending, binding, placing and tieing in position, POL etc. complete as per specification, construction drawings and direction of Engineer-in-charges.
Providing, transportation, laying of dry stone soling
Plain cement concrete of specified grade and strength conforming to IS: 456 placed as sub-base under structural concrete or as shown in approved construction drawings at all levels including cost of all materials, labour, hire charges of equipments and T&P, POL, shuttering etc complete for handling, transportation, batching, mixing, placing, vibrating, compacting, leveling, curing etc. as per specification, construction drawings and direction of Engineer-in-charge.
Concrete of M-10 grade having cube strength of 10 N / mm2 with 40 mm nominal size coarse aggregate for tower foundation.
Structural cement concrete ( plain/ reinforced) of specified 28 days strength (nominal size of coarse aggregate 20 mm) at all levels, including cost of all materials, labour, hire charges of equipments and T&P, POL, form work/shuttering, curing, etc complete for handling, transportation, batching, mixing, placing, vibrating, and rendering, cleaning and finishing /Coping the exposed over ground surfaces with cement mortar 1:3 (1 cement : 3 sand) to give smooth and even surface ( as applicable) but excluding the cost of reinforcement complete as per specification, construction drawings and direction of Engineer-in-charge.
Concrete of M-20 grade having cube strength of 25 N / mm2 with 20 mm nominal size coarse aggregate for Tower foundation
(D) DISMANTLING OF OLD CONDUCTOR AND RE-LAYING & STRINGING OF PANTHER CONDUCTOR AT 03 (THREE) TOWER INSERTION LOCATIONS OF Double Circuit 132kv Amargarh-Arampora Transmission Line.
Dismantling of existing conductor along with hardware fittings and placement of conductor on ground without damaging the trees and crops underneath ( Complete Job)
Stringing of panther condcutor 1 Km + 1.5% for sag for 6 phase including errection of insulator strings/fittings
Extra for laying / stringing of conductor through nallah P&T lines, LT/HT lines ( If applicable)
Erection/fixing of jumpers at tension towers.
( E) REPAIR AND RENOVATION OF STONE MASONRY PROTECTION WALL AROUND 132KV AMARGARH-KUPWARA TRANSMISSION LINE AT TOWER LOCATION NO'S. 89,91,94,95,96 and 98 .
Demolishing stone rubble masonary manually/by mechanical means including stacking of serviciable material and disposal of unserviceable material within 50 mtrs lead as per direction of Engineer in charge Approx of the existing structure = (10*5)+60 = 110 cum
Providing & laying in position cement concrete . All work upto plinth level in 1:4:8 aggregate 40mm nominal size (curshed stone) 20x5'0''x0'3''x5=125=3.54 cum and 80x4'6''x0'3''=90=2.54cum Total=6.08cum
Dry random rubble masonary with hard stone in foundation and plinth with bond stone 80*4'6''*3'6''=1260=35.68 cum
Random Rubble masonary with hard stone in superstructure above plinth level and upto floor fivel level including levelling up with cement concrete 1:6:12( 1 cement : 6 coarse Sand :12 grade stone aggreage 20 mm nominal size ) and complete curing at window slls,ceiling level and the like 20x(5'0''+2'0'')/2x14'0''x2=1960=55.524 cum and 86.15 x(4'6''+2'0'')/2x11'0''=3080=87.236 Cum Total= 142.76 Cum
Providing & laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement :2 course sand :4 graded stone aggregate 20mm niminal size (crushed) 90*2'0"x5=900sqft=83.64 sqm 80*2'0''=160sqft=14.869sqm total 98.509 sqm
Carriage of materials by Mechnical Transport average lead 20KM
Stone.
Aggregates 40mm size
Aggregate 20mm size
Cement
Carriage of materials by head load from unloading site average lead 1.50 KM
Stone
Aggregates 40mm size
Aggregate 20mm size
Cement
(F) DESIGN, MANUFACTURE, SUPPLY, PACKAGING, HANDLING, STORAGE, PRESERVATION, WATCH AND WARD , ERECTION / INSTALLATION, TESTING AND COMMISSIONING OF 132 KV SF6 BREAKER AT GSS ARAMPORA INCLUDING DISMANTLING OF OLD BREAKERS, THEIR TRANSPORTATION AND SAFE STOCKING OR AS PER THE DIRECTIONS OF ENGINEER INCHARGE.
Supply, Installation, testing and commissioninig of 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries ,marshalling boxes/Kiosks and any sort of modifications to the existing breaker foundations etc, (145KV, 1250 Amps of 3 phase, 50 c/s and 31.5KA for 1 second) Complete job.
Dismantling of these old 132 KV Breakers ( 04 No) spared after erection and commissioning of new breakers, their safe handling, dragging, loading at site, its transportation, unloading either at divisional / site store or as per the instructions of Engineer incharge.
(G) Supply, Fabrication, transportation, measurement and fixing of galvanised missing members of various sizes at various tower locations of 132kV Amargarh -Arampora transmission line.
Providing, fabricating,transportation, measurement and fixing of galvanised iron missing members of various sizes at various tower locations of 132kV Amargarh -Arampora transmission line( the missing members are to be fixed at different locations including fabricating, loading,unloading ,carriage and maesurements at site). COMPLETE JOB
Trade Linkers Associates
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.56 MB
sbd.pdf
Tender Documents • 2.04 MB
techtowers.pdf
Other Document • 1.35 MB
BOQ_690593.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .