| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.9 LAccepted-AOC | L1 | Accepted-AOC Accepted being L1 tenderer | |
| 2 | L2₹29.5 L+₹1.1 L (3.98%)Rejected-AOC | L2 | Rejected-AOC L2 tenderer | |
| 3 | L3₹29.7 L+₹1.4 L (4.84%)Rejected-AOC 364 MAHAVEERPURAM BEHIND FUN WORLD CHOPASNI ROAD JODHPUR RAJ | JODHPUR | RAJASTHAN | 342001 | L3 | Rejected-AOC L3 tenderer |
Tender Value
Refer Docs
EMD Value
₹71,900
Closing Date
26 Apr 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF JODHPUR
HQ CWE AF JODHPUR
85880 E8 Repair Replacement and servicing of AC Plants VRVs and allied works at AF Stn Jodhpur
2021_MES_432681_1
85880/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE AF JODHPUR
As per Tender documents
7 documents required · 7 mandatory
₹500
Yes
GE AF JODHPUR
₹71,900
Yes
31 Jul 2021
24 Mar 2021
28 Apr 2021
24 Mar 2021
26 Apr 2021
12 Apr 2021
60 days
Amount
M&L for servicing of water cooled reciprocating chiller unit capacity 60 TR Make:- Voltas model No. 5 H 66 (Auditorium) first checking of all safety controls & setting parameter, electrical panels pneumatic testing and leak testing ,before servicing first to do proper pump down the compressor unit and drainout the old compressor oil ,cleaning the oil chamber and replacement of defective compressor assessories and reassembling the compressor after servicing charging the compressor fresh oil, start & testing the compressor net oil, off load & full load testing completely up to entire satisfaction of Engineer-in-Charge. NOTE:- (i) The spare parts required for replacement shall be measured and paid separately. (ii) All spare parts shall be of make Voltas. (iii) All spare parts,consumable items shall be first brought to stock by Engg-in-Charge.
(a) Supply and fix in replacement of oil filter of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(b) Supply and fix in replacement of liquid line strainer of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(c) Supply and fix in replacement of pressure transducer 0.30 BAR AKS 3000(060G1081) of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(d) Supply and fix in replacement of solenoid valve with coil 220v of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(e) Supply and fix in replacement of oil pump of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(f) Supply and fix in replacement of oil seal of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(g) Supply and fix in replacement of seal plate of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
(h) Supply and fix in replacement of safety valve size 5/8” of water cooled reciprocating chiller unit capacity 60 TR Make- Voltas Model No 5 H 66 as per existing specifications as directed by Engr-in-Charge
M&L for servicing of water cooled reciprocating chiller unit capacity 50 TR Make:- Voltas model No. 5 H 60 (IACCS 33 SU) first checking of all safety controls & setting parameter, electrical panels pneumatic testing and leak testing ,before start over hauling first to do proper pump down the compressor unit and drainout the old compressor oil ,cleaning the oil chamber and replacement of defective compressor assessories and reassembling the compressor after over hauling, charging the compressor fresh oil, start & testing the compressor net oil, off load & full load testing completely up to entire satisfaction of Engineer-in-Charge. NOTE:- (i) The spare parts required for replacement shall be measured and paid separately. (ii) All spare parts shall be of make Voltas. (iii) All spare parts,consumable items shall be first brought to stock by Engg-in-Charge.
(a) Supply and fix in replacement of crank shaft of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(b) Supply and fix in replacement of oil seal of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(c) Supply and fix in replacement of seal plate of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(d) Supply and fix in replacement of pump end bearing of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(e) Supply and fix in replacement of seal end bearing of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(f) Supply and fix in replacement of connecting rod bush bearing of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(g) Supply and fix in replacement of oil pump 5H40 BRG HD of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(h) Supply and fix in replacement of piston of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(i) Supply and fix in replacement of piston pin of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(j) Supply and fix in replacement of 5h connecting rod assy of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(k) Supply and fix in replacement of NYL NUT 7/16” UNF of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(l) Supply and fix in replacement of Brg con rod 5h of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(m) Supply and fix in replacement of cylinder sleeve of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(n) Supply and fix in replacement of DV SPRING 5H40 of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(o) Supply and fix in replacement of DV lock washer (valve guide lock) of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(P) Supply and fix in replacement of pressure regulator valve of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(q) Supply and fix in replacement of piston ring of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(r) Supply and fix in replacement of oil ring of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(s) Supply and fix in replacement of suction reed valve of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(t) Supply and fix in replacement of discharge reed valve of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(u) Supply and fix in replacement of felt filter of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(v) Supply and fix in replacement of thrust washer- pump end of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(w) Supply and fix in replacement of thrust washer- seal end of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(x) Supply and fix in replacement of gasket set of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(y) Supply and fix in replacement of reed spring of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(Z) Supply and fix in replacement of PRSS TRMIT 0.30 BAR AKS 3000(060G1081) of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(aa) Supply and fix in replacement of suction valve of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(ab) Supply and fix in replacement of discharge valve of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
(ac) Supply and fix in replacement of liquid line strainer of water cooled reciprocating chiller unit capacity 50 TR Make- Voltas Model No 5H 60 as per existing specifications as directed by Engr-in-Charge
Supply and charging of compressor oil (mineral) suitable for voltas water cooled recirocating chillers model 5H 60/5 H 66 complete all as specified and directed.
Supply and charging for refrigerant R-22 Gas complete all as specified and directed. Make:- Mafron/ Feron/floron.
M&L for replacement of micro processor controller panel, suitaable for voltas water cooled recirocating chillers model 5H 60/5 H 66 Digital display of all vital parameter for water cooled reciprocating pkg chiller plant 50 TR as per sample Model No-VLRP SINGLE V2A,Type -DELUX Range-6/5/4 ,Aux supply-8v &12 V, Make:-SOFTHARD or equivalent complete all as specified and directed.
M&L for replacement of microcomputer voltage protection device(MVPD) with display complete model-EC, Type-MVPD, Range 30-220 Amps,Aux supply-230V,Special -5 sec Curve MPD Make -SOFTHARD or equivalent as per existing specifications
M&L for finding out the leakage with the pressure test of scroll compressor circuit unit capacity up to11 TR, identifying gas and oil leakage and removing the same and Leak repairing by brazing/flaring and flushing the sysytem by nitrogen gas and pressure testing for leakage and rectified and after rectification vacumacation, pressure testing, and gas charging R-407c for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge. Note :- Gas charging required shall be measured and paid separately under respective items of BOQ.
Ditto all as per Ser item No 7.00 above but capacity up to 11 TR to 25 TR,complete to the entire satisfaction of Engineer-in-Charge.
Ditto all as per Ser item No7.00 above but capacity up to 25 TR to 50 TR,complete to the entire satisfaction of Engineer-in-Charge.
M&L for Repair of chiller unit capacity up to 25 TR with Nitrogen pressure testing ,removing of end shield of evaporator and condenser to check and repair of leakage , plugging of tubes ,dismantling the defective compressor and replace the same with new one refrigerant charging and re commissioning of the chiller and compressor and gas charging R-407c for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge. Note :- Gas charging required shall be measured and paid separately as supply only under respective items of BOQ.
M&L for taking out unserviceable sealed unit (compressor) as existing and replacing the same with new packaged type sealed unit (compressor) 12.5 ton capacity ,model-SZ185S4RC , three phase, 415 volt of models Danfoss make including necessary modification of the foundation as required to suit the compressor, flushing the sysytem by nitrogen gas and pressure testing for leakage and rectified (by brazing) and after rectification vacumacation, pressure testing, and gas charging R-407c for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge. Note :- Gas charging required shall be measured and paid separately as supply only under respective items of BOQ.
Supply & Charging refrigerant R-407c Gas (Make:- Mafron/ Feron/floron/du point) complete all as specified and directed
M&L for replacement of pilot solenoid valve suitable for water cooled scroll chiller unit cap 25/37/50 TR all as per specified and directed.
M&L for replacement of solenoid coil 220v suitable for water cooled scroll chiller unit cap 25/37/50 TR all as per specified and directed.
M&L for replacement of thermostatic expansion valve suitable for water cooled scroll chiller unit cap 25/37/50 TR all as per sample, including brazing at both ends all as required and directed.
M & L for replacement of HP/LP switch suitable for scroll compressor cap up to 12.5 TR all as per specified and directed.
M&L for replacement of Drier filter suitable for Package type AC Plant size 5/8" Make: Catch All Model : C-165 or equivalent as per existing specifications.
M&L for replacement of chilled water sensor complete all as specified and directed.
M&L for replacement of old unservicable pressure relief valve of condenser 5/8" BSP threaded suitable for 300 PSI complete all as specified and directed.
M&L for replacement of pressure transducer range 18 bar/30 bar connection type 1/4 BSP complete all as specified and directed.Make:-Meas or equivalent as per existing specifications
M&L for replacement of micro processor controller panel, Digital display of all vital parameter for water cooled scroll type chiller plant as per sample Model No-SCR44TR(MPD) ,Type -DELUX Range-5-30 Amp complete all as specified and directed. Make:-SOFTHARD or equivalent as per existing specifications
M&L for replacement of micro processor controller panel VLRP, Digital display of all vital parameter for water cooled scroll type chiller plant cap 22TR as per sample Model No-V3A ,Type -DELUX Range-16/4/12 ,Aux supply -15 VAV complete all as specified and directed. Make:-SOFTHARD or equivalent as per existing specifications
M&L for replacement of micro processor controller panel VLRP, Digital display of all vital parameter for water cooled scroll type chiller plant cap 11TR as per sample Model No-V3A ,Type -DELUX Range-7/2/2 Aux supply -15VAV complete all as specified and directed. Make:-SOFTHARD or equivalent as per existing specifications
M & L for replacement of microcomputer voltage protection device(MVPD) with display complete model-EC, Type-MVPD, Range 5-30 Amps,Aux supply-230V,Special -5 sec Curve MPD complete all as specified and directed. Make:-SOFTHARD or equivalent
S&F in replacement of HMI (SCR44TR) display make softhard forwater cooled scroll chiller unit complete all as specified and directed.
M&L for repairs of condenser/chiller pumps from 2HP Upto 7.5 HP including dismantling of Pump of following capacity and segregating to its parts for repairs and maintenance, replacement only of shaft bearing, impeller key, shaft sleeve, impeller and grinding / polishing, bend removing etc complete including painting by two coats of synthetic enamel paint reassembling of pump after completion of work & testing complete all as per direction and satisfaction of Engineer in charge. Note:- Supply only of bearing and sleeve, impeller will be measured and paid under relevent item of BOQ.
Supply and fix in replacement of srare parts of pumps sets (To be incorporated under respective item above ) :- (a) Shaft bearing as per existing specifications.
(b) Ditto all as per Ser item No 25.00 above but Shaft sleeve as per existing specifications.
(c) Ditto all as per Ser item No 25.00 above but Impeller with key as per existing specifications.
(d) Ditto all as per Ser item No 25.00 above but Mechanical Couplings as per existing specifications.
(e) Ditto all as per Ser item No 25.00 above but rubber type coupling as per existing specifications.
M&L for repairing /Disconnecting the electrical and mechanical connection of burnt electrical motors from the site / location, transporting to and from to work shop. Rewinding of electrical motors/ pump motors by dismantling and removing the burnt cut copper winding wire cleaning the slots of stator with petrol and brushes winding polyster based super enamelled copper wire of same gauge of original one with proper class of insulation including varnishing and heating the coil and remove air bubbles complete stator / roter after rewinding reassembling all parts including reinstalling connection to original position and testing on full load all as directed by Engineer- in -Charge for different capacity of motor as per following :- (a) 1 to 2 HP
(b) Ditto all as per Ser item No 26.00 above but 3 to 5 HP
(c) Ditto all as per Ser item No 26.00 above but 7.5 to 15 HP
(e) Ditto all as per Ser item No 26.00 above but 50 to 100 HP
M&L for replacement of Hexagonal Green Plastic Wire Mesh for cooling tower as per sample and directed by Engineer -in -Charge.
M&L for replacement of Thermostat Honey well 0-30 degree C complete all as specified and directed.
M&L for disconnecting electrical connections motor located at the top of cooling tower,keep cables at safe custody for reconnection and dismantling and taking out fan blade assembly along with motor mounted on base frame at the top of cooling tower after cutting/dismentaling all nuts, bolts and fixtures from the mounting frame and removing whole assembly including motor and base frame from the top of cooling tower with the help of T&P for servicing of cooling tower suitable for 100-120 TR capcity including following complete:- (i) Cleaning /scrapping of inner& outer surface of FRP basin, repair of damaged portion if any incuding FRP lining of all surfaces joints to avoid leakage including replacement of all nuts and bolts joining all parts of Basin complete. (ii) servicing cooling tower plant through cleaning re-agent complete pipe line, including servicing of cooling tower motor and fan and make the necessary alignment with motor. (iii) replacement of bearing if any of suitable cap if any after necessory work including gressing and replacement of nut bolts and preventing leakage if any by means of suitable adetives etc all as directed and specified. (iv) taking out PVC fills blocks, cleaning and refixing as per existing location and channel direction if pvc fills vintage then replace with new one measure seprately . (v) servicing of spray header and sprinkler assy complete. (vi) repair of water strainer complete.
Ditto all as per Ser item No 29.00 above but cooling tower suitable for 25- 60 TR capcity
Supply only spare parts of cooling tower of capacity 15 TR to 150 TR for the following Make:- Kool Drop / MIHIR / ADVANCE / HIMGIRI. (To be incorporated under item above :- (a) cooling tower PVC fills in colums of size 600mm x 300mm x 150mm size and min wt 600 gram as per existing specification and requirement.
S&F in replacement of Cooling Tower Sprinkler Assembly such as Sprinkler, Sprinkler Pipe, Elimentor, Tension bar and Turn buckle for Cooling Tower capacity 120 TR model no 9062 make :-MIHIR or equivalent suitable as per existing and ali as per directed by Engineer- in- Charge.
S&F in replacement of Cooling Tower Sprinkler Assembly such as Sprinkler, Sprinkler Pipe, Elimentor, Tension bar and Turn buckle for Cooling Tower capacity 50 TR/30 TR model no 5051 ,model no 5022 &model no 5021 make :-Delta or equivalent suitable as per existing and ali as per directed by Engineer -in -Charge.
S&F Cooling tower PVC nozzles size 2" dia suitable as per existing al as per directed by Engineer- in- Charge.
S&F Roler bearing/Pedestal bearings for fan motor as per sample of Make:- SKF/AKB.
S&F Ball / Roller bearing for Sprinlkler top and Bottom Hub for 25 TR to 120 TR capacity .
M&L for coating FRP lining of 6 mm thickness on cooling water piping near cooling towers to minimize corrosion of MS piping of 125/100/80 mm diameter complete all as per specified and directed.
S&F in replacement of of PN 1.6 butterfly valves size 150 mm duly insulated with companion flanges,nuts,bolts,gaskets etc.as specified . butterfly valves with cast iron body, seat of black nitrile rubber ,nylon coated S.G.iron disc,epoxy powder coated shaft AISI 410 etc.complete all as specified and directed. Make:- Audco/castel/kirloskar.
(a) Ditto all as per Ser item No 37.00 above but size 100mm.
(b) Ditto all as per Ser item No 37.00 above but size 80mm.
(c) Ditto all as per Ser item No 37.00 above but size 65mm.
(d) Ditto all as per Ser item No 37.00 above but size 50mm.
(e) Ditto all as per Ser item No 37.00 above but size 40/32mm.
M&l for replacement of rotational moulded polyethylene water storage tank (cylinderical vertical with closed top) of cap 5000 ltrs hoisted and fixed in position all as specified in SSR Part-I 2009.
Ditto all as per Ser item No 38.00 above but of cap 500 ltrs.
M&L Pre-cast cement concrete block masonry with solid blocks, exc. 10 cm in width and setting in CM 1:6,complete 1:2:4 type B1 of 20 mm greaded aggregate for foundation of any requirements as specified in SSR Part-I 2009.
M&L for Descaling the condenser by descaling compound / hydrochloric acid by soaking method,disconnecting condensor from the system by taking out nuts, bolts, studs, valves and MS/GI pipe line from both side cover, cleaning each tube with nylon brush,flushing with alkaline solution,connecting back both side cover including replacingleather gasket 4 mm thick for following capacities of condensers suitable for AC Plant installed as indicated below complete all as specified and directed and all as per manufacturers instruction and to the entire satisfaction of Engineer-in-Charge. (a) chiller unit cap 60 TR (Auditorium)
(b) Ditto all as per Ser item No 40.00 above but chiller unit cap 50 TR (IACCS 33SU, ILS)
(c) Ditto all as per Ser item No 40.00 above but chiller unit cap 37 TR( ccc & FMS )
(d) Ditto all as per Ser item No 40.00 above but chiller unit cap 25 TR (23MMPU,parachute,EW lab &instrument lab)
(e) Ditto all as per Ser item No 40.00 above but chiller unit cap 11 TR(ACMI, Base opps,bomb dumpem25 &em26)
(f) Ditto all as per Ser item No 40.00 above but chiller unit cap 7.5 TR(bomb dump)
M&L for servicing and cleaning of AHU cooling coil 4-6 rows deep of capacity 8000cfm to 18000 cfm through cleaning agent and remove the oil and dust from fins and cooper tubes/ pipes complete checking of copper tubing for leakage maching/ repairing /brazing of leakaged tubes complete including sealing of joints all as directed by Engineer-in-Charge.
S&F in replacement of air filter for AHU, Filter section consists of 50 mm thick washable HDPE 90% down 10 micron Pre-Filters, AHU pre filter having HDPE media with aluminium / GI frame & filter as per the existing size of 600mmX600mmX50/40 mm mm complete all as specified and directed by Engineer-in-Charge. Make:- Supreme/Athlete or equivalent
M&L for replacement of' V Belt of A & B Series any sizes for AHU 's as per site requiement complete all as specified and directed.
M&L for repair of chilled water piping size 100 mm bore duly insulated 50 mm thick TF quality EPS pipe section insulation of 18 kg/cu.mt density & covered with GI chicken wire mesh and two coats 12mm sand cement plaster as per specification complete all as specified and directed by Engineer-in-Charge. .
M&L for repair of chilled water piping size 80 mm bore duly insulated 50 mm thick TF quality EPS pipe section insulation of 18 kg/cu.mt density & covered with GI chicken wire mesh and two coats 12mm sand cement plaster as per specification complete all as specified and directed by Engineer-in-Charge. .
S&F in replacement of water presuure gauge 0-7 kg / cm2 including Female Stainless Steel Gauge Fittings, Material Grade: SS304 type Make:- Febig or equivant suitable makes as per appx 'B' complete all as specified and directed.
S&F in replacement of thermometer to condenser/chiller, inlet or outlet water pipes including addition alteration to pipe line for fixing thermometer Range 0-100 degree F / degree centigrade complete all as specified and directed.
M&L for replacement of 25 mm dia. Auto Air Purge valve for chilled water piping complete all as specified and directed.
M&L for replacement of gun metal gate valve (ISI marked) butter fly valve 15 mm dia complete all as specified and directed.
S&F in repair MS pipe medium grade welded in shape i.e bend . Elbow. Tee. flange etc for condensser and water pipe laid on floor, ground including making hole in wall, brics work and welding of nipple for installing of pressure gauge, thermameters , plug cock etc,including painting with two coat of synthetic enameled paint over a coat of red oxide primer complete all as specified and directed of sizes. 80mm dia.
S&F steel water Tubing medium grade with all fitting laid in trenches/floor or fixed to wall of size:- (a) 15 mm bore
(b) Ditto all as per Ser item No 51.00 above but 25 mm bore
S&F in repairs worn out HRC fuses (Cylindrical / DIN type / Bolted) conforming IS 13703 Part - II with high breaking capacity suitable for existing holders all as specified and as directed for the following capacities :- (a) 10 Amps to 100 Amps
S&F in repairs worn out fuses (Cylindrical / DIN type / Bolted) conforming IS 13703 Part - II with high breaking capacity suitable for existing holders all as specified and as directed for the following capacities :- (a) 2Amps to 10 Amps
Supply & laying in replacement LT cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 3.5 core x 70 sqmm complete all as specified and directed.
Supply & laying in replacement LT cable XLPE insulated , armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 3.5 core x 50 sqmm complete all as specified and directed.
S&F in replacement of PVC insulated 4 Core copper Cable of size 16 Sqmm complete all as specified and directed.
S&F in replacement of PVC insulated 4 Core copper Cable of size 4 Sqmm complete all as specified and directed.
S&F in replacement of Digital AC Voltmeter input 0-60 VAC,Range1%-150% of input complete all as specified and directed.
S&F in replacement of Digital AC Ammeter input programmable (1A to 5A) Range 2%-12% of input complete all as specified and directed.
M&L for replacement of Indicating Light, 240V AC, LED Type Red, Yellow, Blue complete all as specified and directed.
M&L for replacement of Mushroomhead Push Button, Press to Lock Turn To Release complete all as specified and directed.
M&L for replacement of ON/OFF Push Button complete all as specified and directed.
M&L for replacement of repair of thermal Relay MNX 32A 3-6 Amp complete all as specified and directed.
M&L for replacement of thermal Relay MNX 32A 6-10 Amp complete all as specified and directed.
M&L for replacement of MNX -A1 size contactor complete all as specified and directed.
M&L for replacement of MNX -A2 size contactor complete all as specified and directed.
M&L for replacement of MNX 32A contactor with NO/NC switch complete all as specified and directed.
M&L for replacement of MNX 18A contactor with NO/NC switch complete all as specified and directed.
M&L for replacement of MNX 12A contactor with NO/NC switch complete all as specified and directed.
M&L for replacement of Timer GIC star/delta complete all as specified and directed.
M&L for replacement of connector for suitable to chiller panel complete all as specified and directed.
M&L for replacement of starter block contactor 3TF34-C3 with NO/NC switch complete all as specified and directed.
M&L for replacement of starter block contactor 3TF46-C3 with NO/NC switch complete all as specified and directed.
S&F in replacement of MCCB 400 Amp 4Pole 25 KA complete all as specified and directed.
S&F in replacement of MCCB DU 250 Amp 4 Pole 25 KA complete all as specified and directed.
S&F in replacement of MCCB DU 160 Amp 4 Pole 25 KA complete all as specified and directed.
S&F in replacement of MCCB DU 100 Amp 3 Pole 25 KA complete all as specified and directed.
S&F in replacement of MCB TP C63 Amp 415 Volt complete all as specified and directed.
S&F in replacement of MCB TP C40/32 Amp 415 Volt complete all as specified and directed.
M&L for replacement of remote control hand set complete for ductable AC 5.5/8.5/11 TR with suitable size of copper conductor cord for operation of AC & having provn of display for current ,room temp fault diagnosis i.e reverse phasing single phasing sensor fault over voltage &under voltage completeall as specified and directed by Engineer-in-Charge.
M&L for taking out unserviceable sealed unit (compressor) 5 ton capacity , three phase, 415 volt of models as existing and replacing the same with new packaged type sealed unit (compressor) of Hitachi/Danfoss make including necessary modification of the foundation as required to suit the compressor, vacumacation, pressure , testing, leaking, rectification including gas charging R-22 for achieve desire pressure and testing complete to the entire satisfaction of Engineer-in-Charge.
S&F in replacement of PCB control card with outer & inner set complete suitable for 5.5 TR ductable AC all as specified and directed by Engineer-in-Charge.
M&L for any size of ductable AC servicing of indoor and out door unit and finding out the leakage the pressure test of the condenser of cooling coil of ductable type AC of any capacity and dismantling the same for repair the leakage point by brazing/soldering including charging the gas R-22/410, taking down/refixing the inner unit/outer unit and testing the AC to the entire satisfaction of Engineer-in-Charge.
M&L in repair of PCB control card with outer & inner set complete suitable for any type ductable AC of any capacity requirement complete and testing the AC after the replacement of PCB as specified.
M&L for replacement of Indoor blower fan motor of capacity 5.5 Ton, suitable for ductable AC cooling coil (as per sample ) complete all as specified and as directed by Engineer-in-Charge. Make:- Hitachi/Danfoss/Tecumesh
M&L for replacement of Outdoor fan motor of capacity 5.5 Ton, suitable for ductable AC (as per sample ) complete all as specified and as directed by Engineer-in-Charge. Make:- Hitachi/Danfoss/Tecumesh
M&L for replacement of blower of dia 5/8 suitable for ductable AC 5.5 ton capacity complete all as specified and as directed by Engineer-in-Charge. Make:- Hitachi/Danfoss/Tecumesh
M&L for replacement of Aluminium Fan blade for out door Fan motor assembly suitable for ductable AC 5.5/8.5 ton capacity complete all as specified and as directed by Engineer-in-Charge. Make:- Hitachi/Danfoss/Tecumesh
M&L for replacement of PCB control card set complete suitable for Tower AC of capacity 4.0 TR requirement complete and testing the AC after the replacement of PCB complete all as specified and as directed by Engineer-in-Charge.
M&L for repair of VRV out door unit Make - DAIKIN ,cleaning the dust particals , tightened all loose connection, servicing all connected components finding out the leakage & the pressure test of the condenser of cooling coil of VRV type AC of capacity 18 HP,22HP & 32 HP and the same for repair the leakage point by brazing/ soldering including gas charging R-22/R-407C/R-410, and testing the AC to the entire satisfaction complete all as specified and as directed by Engineer-in-Charge.
M&L for WATER JET servicing of VRV (complete indoor and outdoor unit by using service bag cover & cooling coil rinse solution for cleaning of coils),cassette type AC of 2.5/3.0/4.0/5.0 HP capacity taking out the indoor top cover outdoor top cover from existing location, cleaning of cooling coil , condenser coil, and other components using clean water greasing of fan, motor, blower etc without damage any part and reinstall at the same location all as directed by the Engineer-in-Charge.
S&F in replacement of PCB control card for VRV Indoor unit cassette type AC all as specified and directed by Engineer-in-Charge.
M&L for repair of cassette type AC, PCB control card by finding out the fault and changing of diod, transformers, IC, display , connecting cord what ever required on ground and testing the AC after the replacement of components all as specified and directed by Engineer-in-Charge.
M&L for WATER JET servicing of package type AC 's cap 7.5/5.5/30 TR complete indoor and out door unit from existing location for servicing inner and outer filter complete with T&P and other accessories all as specified and directed by Engineer-in-Charge.
M&L for WATER JET servicing of tower AC cap 4TR by taking out the same from existing location , cleaning all dust particals of cooling coil with cooling coil rinse solution and other components by the help of blower, motor , blower etc without damage any part and reinstall at the same location all as specified and directed by Engineer-in-Charge.
M&L for repair of EXV board part no. 2008539 for air cooled pkg chiller plant 30 TR as per sample Make-TOTALINE(CARRIER) or equivalent complete all as specified and directed.
M&L for repair of HMI DISPLAY BOARD W/O PRAGRAMME(30RB) PART NO.2021580for air cooled pkg chiller plant 30 TR as per sample Make:-TOTALINE(CARRIER) or equivalent complete all as specified and directed.
S&F thermometer humidity meter clock with sensor cable Temperature and Humidity Functions: With temperature range from -10 degC to +50 degC and humidity 10 % sim 99 % RH, temperature and humidity readings show directly all as specified and directed by Engineer-in-Charge.
M&L for repiar of Wafer Swing Check type Non- Return Valve, PN -1.6 rating with cast iron body,flanges, gaskets etc . (a) 100 mm bore of pipe
(b) Ditto all as per item no-99.00 above but 80 mm bore of pipe
(c) Ditto all as per item no-99.00 above but 65 mm bore of pipe
(d) Ditto all as per item no-99.00 above but 50 mm bore of pipe
M&L for repair of electrical strip heater ,finned type ,capacity 6 kw consisting of stainess steel sheathing having heat resistent chrome -nickel 80/20 element protected under best insulation to avoid the leakage of current and with screwed type terminal at one end, 240 volts, AC, 50Hz ,single phase complete with heater plenum for humidity control with humiditstat/ thermostat & saftey thermostate with all necessary electric cabling complete all as specified and as directed for parachute heating plant.
M&L for replacement of electrical strip heater ,finned type ,capacity 2 kw consisting of stainess steel sheathing having heat resistent chrome -nickel 80/20 element protected under best insulation to avoid the leakage of current and with screwed type terminal at one end, 240 volts, AC, 50Hz ,single phase complete all as specified and as directed.
S&F in replacement of humidistat H6000 to control humidity range 15 to 80 % RH all as per specified and directed .
S&F in replacement of blower motor 3 phase 415 volt 50 Hz of cap 1 Hp suitable as per site condition for parachute heating plant all as per directed .
M&L in repairs of Existing U/S LT panel to new floor mounted , indoor ,cubicle,&compartmentalized , front access type ,medium voltage electric panel of dust and vermin proof ,fully tropicalised construction ,front openable doors and shutters with locking arrangement, made out of 14 SWG (2.0 mm thick) CRCA sheet steel ,factory fabricated ,powder coated ,suitable for operation on 450 Volts ,3 phase ,4 wire ,50 Hz,AC supply complete with all interconnections and consisting of all accessories like copper Bus Bar ,Indicating Lamps,Push buttons ,CTs ,Digital Ampere ,Voltage ,Frequency & KWH meter ,danger Plate,Lifting Hooks ,feeder Name Plates suitable for the following feeders (Note: the Panel shall be of suitable size to accomodate all the accessories mentioned below ,installed on Pedestal made out of angle iron of size 50mm x50mm 6mm &earth work, PCC foundation ,suitable cable glands for cable entry etc. (a) MCCB 100 Amps TPN 25 KA, 415 V - 01 No. Incoming (b) MCCB 63 Amps TPN 25 KA 415 Volts-03No (c) MCB 63 Amps TPN 10 KA 415 Volts-3 Nos
M&L for replacement of float valve complete all as specified and directed. (a) 15 mm bore of pipe
(b) Ditto all as per item no-105.00 above but 25 mm bore of pipe
M&L for servicing and cleaning of HOT WATER GENRATOR through cleaning agent and oil and dust complete all as directed by Engineer- in- Charge.
Mahesh Dave
M/s. Dhananjay Construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .