| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.6 LAccepted-AOC PM 3 6 TEGHORIA MONDAL PARA 3RD LANE KOLKATA 700059 | 24 PARAGANAS NORTH | WEST BENGAL | 700059 | L1 | Accepted-AOC L1 | |
| 2 | L2₹22.9 L+₹35,182 (1.56%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹23.4 L+₹79,885 (3.54%)Rejected-Finance | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | PHINIX L1 | M/S MANAB ENTERPRISE L2 | M/s. Kar Electric Works L3 |
|---|---|---|---|---|---|---|
| 1.00 | Thoroughly Rackout the H.T. 2-Panel Switch gear along with busbar, risers and sockets contacts. 2 Nos. withdrawing, sectionwise megger (2.5KV) testing. Thorough checking of VCB’s with their mechanism. All the components of the switch board incld. spouts of the panel , P.T. plugging chamber .etc. thoroughly checking and cleaning as per direction of EIC. | 1 | item | 12,100 ₹12,100 | 11,800 ₹11,800 Lowest | 12,500 ₹12,500 |
| 2.00 | Testing and resetting the overload and earth fault tripping coils of all the gears of 11KV H.T. 2-Panel switch Board by Paimary/secondary injection RelayTesting Set incld. making necessary calibration for proper tripping according to full load current of the transformers incld. carrying the Relay Testing set to and from site with own tools and tackles as per standard safety measure and as per direction of EIC. | 1 | Item | 12,600 ₹12,600 | 12,800 ₹12,800 | 12,500 ₹12,500 Lowest |
| 3.00 | Carrying out High Voltage Pressure Test, Insulation Registance test etc. of the 01 no. of 11KV 2 panel HT Gear and H.T.cables seperately at required D.C. voltges (rectified A.C.) for ONE minute for the transformer,VCB, and also per phase of the cable with own tools and tackles as per standard safety measure and as per direction of EIC. | 1 | Item | 14,100 ₹14,100 Lowest | 14,500 ₹14,500 | 14,600 ₹14,600 |
| 4.00 | Servicing of 1400KVA Dry Type Transformer with necessary testing checking Cleaning and tightening all visible components as per direction of EIC. | 1 | set | 8,000 ₹8,000 Lowest | 8,400 ₹8,400 | 8,200 ₹8,200 |
| 5.00 | Servicing, testing, checking and repairing of 1010KVA AMF control panel connected with 1010KVA Diesel Generator automatic power back up in absence of raw power from 1400KVA Dry Type Transformer along with necessary testing checking Cleaning and tightening all visible components as per direction of EIC. | 1 | set | 8,300 ₹8,300 Lowest | 8,700 ₹8,700 | 8,800 ₹8,800 |
| 6.00 | Supply & Fixing of new Power Pack(Brand approved by EIC) for HTVCB, Input 110V AC, Output 110V DC with own tools and tackles as per standard safety measure and as per direction of EIC. | 1 | set | 22,500 ₹22,500 | 22,400 ₹22,400 Lowest | 23,000 ₹23,000 |
| 7.00 | Supply & Fixing of 240V Tripping coil for Schneider make HT gear with circuit with own tools and tackles as per standard safety measure and as per direction of EIC. | 2 | Set | 5,300 ₹10,600 | 5,350 ₹10,700 | 4,900 ₹9,800 Lowest |
| 8.00 | Supply & Fixing of 240V Closing coil for Schneider make HT gear with circuit with own tools and tackles as per standard safety measure and as per direction of EIC. | 2 | Set | 5,400 ₹10,800 | 5,200 ₹10,400 | 4,900 ₹9,800 Lowest |
| 9.00 | Supply & Fixing of self amalgating HV Tape with own tools and tackles as per standard safety measure and as per direction of EIC. | 5 | Roll | 810 ₹4,050 | 840 ₹4,200 | 790 ₹3,950 Lowest |
| 10.00 | Supply and fixing of good quality 11KV Heat sink insulation jacket with proper size for cable terminal socket end for 02 panel HT gear terminal with own tools and tackles as per standard safety measure and as per direction of EIC. | 9 | Set | 3,600 ₹32,400 Lowest | 3,750 ₹33,750 | 3,650 ₹32,850 |
Tender Value
Refer Docs
EMD Value
₹47,795
Closing Date
16 Feb 2026, 11:00 amClosed
Room No. 108, Purta Bhawan, Salt Lake
Room No. 108, Purta Bhawan, Salt Lake
Repair and Renovation of E.I. Air conditioners Sub-Station Fire detection system of Madinat-ul-Hujjaj campus at New Town Rajarhat Kolkata700160 in connection with Haj Operation 2026--Repair and renovation of Electrical Installation work
2026_WBPWD_992623_1
WBPWD/EE/BED/e-NIQ-141/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Madinat-ul-Hujjaj campus
Please refer Tender documents.
5 documents required · 5 mandatory
₹47,795
2 Mar 2026
21 Jan 2026
18 Feb 2026
2 Feb 2026
16 Feb 2026
2 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Thoroughly Rackout the H.T. 2-Panel Switch gear along with busbar, risers and sockets contacts. 2 Nos. withdrawing, sectionwise megger (2.5KV) testing. Thorough checking of VCB’s with their mechanism. All the components of the switch board incld. spouts of the panel , P.T. plugging chamber .etc. thoroughly checking and cleaning as per direction of EIC. | 1 | item | - | - |
| 2 | Testing and resetting the overload and earth fault tripping coils of all the gears of 11KV H.T. 2-Panel switch Board by Paimary/secondary injection RelayTesting Set incld. making necessary calibration for proper tripping according to full load current of the transformers incld. carrying the Relay Testing set to and from site with own tools and tackles as per standard safety measure and as per direction of EIC. | 1 | Item | - | - |
| 3 | Carrying out High Voltage Pressure Test, Insulation Registance test etc. of the 01 no. of 11KV 2 panel HT Gear and H.T.cables seperately at required D.C. voltges (rectified A.C.) for ONE minute for the transformer,VCB, and also per phase of the cable with own tools and tackles as per standard safety measure and as per direction of EIC. | 1 | Item | - | - |
| 4 | Servicing of 1400KVA Dry Type Transformer with necessary testing checking Cleaning and tightening all visible components as per direction of EIC. | 1 | set | - | - |
| 5 | Servicing, testing, checking and repairing of 1010KVA AMF control panel connected with 1010KVA Diesel Generator automatic power back up in absence of raw power from 1400KVA Dry Type Transformer along with necessary testing checking Cleaning and tightening all visible components as per direction of EIC. | 1 | set | - | - |
| 6 | Supply & Fixing of new Power Pack(Brand approved by EIC) for HTVCB, Input 110V AC, Output 110V DC with own tools and tackles as per standard safety measure and as per direction of EIC. | 1 | set | - | - |
| 7 | Supply & Fixing of 240V Tripping coil for Schneider make HT gear with circuit with own tools and tackles as per standard safety measure and as per direction of EIC. | 2 | Set | - | - |
| 8 | Supply & Fixing of 240V Closing coil for Schneider make HT gear with circuit with own tools and tackles as per standard safety measure and as per direction of EIC. | 2 | Set | - | - |
| 9 | Supply & Fixing of self amalgating HV Tape with own tools and tackles as per standard safety measure and as per direction of EIC. | 5 | Roll | - | - |
| 10 | Supply and fixing of good quality 11KV Heat sink insulation jacket with proper size for cable terminal socket end for 02 panel HT gear terminal with own tools and tackles as per standard safety measure and as per direction of EIC. | 9 | Set | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.89 MB
2911_ii.pdf
Tender Documents • 0.50 MB
BOQ_2427434.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .