| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.2 LAccepted-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹14.2 L Quoted ₹14.4 L | L1 | Accepted-AOC Competitive |
| 2 | L2₹14.5 LRejected-Finance | ₹14.5 L | L2 | Rejected-Finance Not Competitive |
| Sl No | Description | Qty | Unit | Unimech systems private limited L2 | Blue Star Ltd L1 |
|---|---|---|---|---|---|
| 1.00Supply | |||||
| 2.00DX-Air Handling Units | |||||
| 2.10Supply of DX Double skin draw thru type Vertical Air handling unit (as per the drawing) of 28mm panel thick duly sandwich insulated with PUF having 0.7mm Preplasticised steel complete with backward curved centrifugal fan having efficiency more than 60% , IE3 motor belt drive package, coil section with 6 Row deep copper tube aluminium fins DX cooling coil having fins 5 fins per cm, cooling coil shall be half inch OD copper tube of thickness not less than 0.4mm. Flat Filters section with Flat filters with efficiency of 80% down to 20 micron Approved Makes: Airprism/Luftek/ Thermoflex The AHU cost shall include 1set of commissioning filters, outlet Al. VCD etc. | |||||
| 2.11 | 0.0M LEVEL - UPS Room at 0 M level Vertical Floor Mounted AHU having 3740 M³ per hour against 40 mm static with capacity of 5.5TR with six row DX cooling coil connected to 1no. 5.5TR DX Condensing unit | 1 | Nos | 1,86,300 ₹1.9 L | 3,14,500 ₹3.1 L |
| 3.00DX CONDENSING UNIT Supply of air cooled DX outdoor condensing unit with high efficient scroll compressor, condenser coil etc. Each unit connected to and, interconnected refrigerant piping, full charge of refrigerant gas including additional top up and oil, control cabling etc. as per detail given in specifications and having following items. . with fan & motor,Integral refrigerant piping, safety controls & cutouts,drier with compressor service shut off valves, control panel housing the starters for the compressors /condenser fan motors,single phase preventor,compressor crank case heater, HP / LP cutouts, Oil safety switch overload thermal overload protectioncontrol wiring with panel Refrigerant to be used shall be - R 410 A only. Approved Makes: Voltas / Daikin/ Blue star Limited / Carrier/ Toshiba | |||||
| 3.10 | 0.0M LEVEL - UPS Room at 0 M level 5.5 TR | 1 | No | 94,530 ₹94,530 | 1,19,000 ₹1.2 L |
| 4.00LOW SIDE WORKS | |||||
| 4.10Supply of chemical resistance coating for Condenser coil/ fins for corrosion/errosion protection | |||||
| 4.11 | 5.5 TR | 1 | Nos | 6,210 ₹6,210 | 25,500 ₹25,500 |
| 4.20Supply of Electrical sub panel wall/ floor mounted with 1no. Incoming power feeder provision and single/ mulitple outgoing feeders for DX condensing units including Switch Disconnecting Fuse(SDF), DOL starter for AHU motor , isolators, contactors, overload relays single phasing preventor etc. | |||||
Tender Value
Refer Docs
Closing Date
20 Dec 2025, 3:00 pmClosed
GM (PROJECTS)
TNPL UNIT-I, KAGITHAPURAM, KARUR DISTRICT
Supply of chilled water Pipes and other Accessories for AHUs in TM5
2025_TNPL_630700_1
TNPL/Unit-II/TM#5/252623003625
Open Tender
Electrical Goods/Equipments
35 days
TNPL Unit II, Trichy
As per Part 1 of bid document
7 documents required · 7 mandatory
₹0
Exempted
16 Jan 2026
10 Dec 2025
22 Dec 2025
10 Dec 2025
20 Dec 2025
11 Dec 2025
10 Dec 2025 - 20 Dec 2025
Amount
Supply
DX-Air Handling Units
Supply of DX Double skin draw thru type Vertical Air handling unit (as per the drawing) of 28mm panel thick duly sandwich insulated with PUF having 0.7mm Preplasticised steel complete with backward curved centrifugal fan having efficiency more than 60% , IE3 motor belt drive package, coil section with 6 Row deep copper tube aluminium fins DX cooling coil having fins 5 fins per cm, cooling coil shall be half inch OD copper tube of thickness not less than 0.4mm. Flat Filters section with Flat filters with efficiency of 80% down to 20 micron Approved Makes: Airprism/Luftek/ Thermoflex The AHU cost shall include 1set of commissioning filters, outlet Al. VCD etc.
0.0M LEVEL - UPS Room at 0 M level Vertical Floor Mounted AHU having 3740 M³ per hour against 40 mm static with capacity of 5.5TR with six row DX cooling coil connected to 1no. 5.5TR DX Condensing unit
DX CONDENSING UNIT Supply of air cooled DX outdoor condensing unit with high efficient scroll compressor, condenser coil etc. Each unit connected to and, interconnected refrigerant piping, full charge of refrigerant gas including additional top up and oil, control cabling etc. as per detail given in specifications and having following items. . with fan & motor,Integral refrigerant piping, safety controls & cutouts,drier with compressor service shut off valves, control panel housing the starters for the compressors /condenser fan motors,single phase preventor,compressor crank case heater, HP / LP cutouts, Oil safety switch overload thermal overload protectioncontrol wiring with panel Refrigerant to be used shall be - R 410 A only. Approved Makes: Voltas / Daikin/ Blue star Limited / Carrier/ Toshiba
0.0M LEVEL - UPS Room at 0 M level 5.5 TR
LOW SIDE WORKS
Supply of chemical resistance coating for Condenser coil/ fins for corrosion/errosion protection
Supply of Electrical sub panel wall/ floor mounted with 1no. Incoming power feeder provision and single/ mulitple outgoing feeders for DX condensing units including Switch Disconnecting Fuse(SDF), DOL starter for AHU motor , isolators, contactors, overload relays single phasing preventor etc.
UPS room- 3740CMH AHU-1no. + 5.5TR Condensing unit- 1no.
Supply of Power cabling and double earthing between the above panel to motors and control cabling/ double earthing from panel starter to the local on /off switch etc. with in AHU room/near AHU UPS room at 0.0Mtr Level
Armoured copper Power cabling for 1no. 3750CMH AHU
Armoured copper Power cabling for 1no. 5.5TR Cond. Unit
Copper control cabling and GI double earthing for above system
Supply of Expansion Vlave, drier etc. Make: Sporlan/ Danfoss
Additional Refrigerant gas R410a
Supply of 20G Copper tubing for connecting the AHUs and VRF Outdoor units with Supply and application of Elastomeric nitrile rubber type tubular insulation of fire retardent grade of conductivity less than 0.22 Btu.in./(h.ft² °F) and density 50 Kg/CMT with 19 mm thickness for suction line. Indoor & Outdoor insulation shall be mechanically protected with two layers (07 mil thick each layer) of adhesive and Glass Cloth / CSM and Outdoor insulation shall have two coats of special UV resistant paint.insulation 0.0M LEVEL Note: The Vendor to quote the rate for copper piping - suction line and liquid line suitable for their Equipments UPS Room at 0 M level
Suction line 1/2"
Liquid line 7/8"
Drain piping Supply of PVC pipes for drain cut to required lengths and installed complete with all necessary fittings like elbows tees & reducers with 9mm Nitrile insulation
40 mm dia
Supply of Temperature & RH Display with Temperature controller including control cabling etc. (UPS room, Rewinder Panel room, I/O Rack room, Switch gear room -1)
Supply of Thermostat with sensor and control cabling for individual unit
Any other items required for satisfactory for the Project the same to be included and to specify the items and rates clearly
PRE-INSULATED CHILLED WATER PIPING: PRE-INSULATED CHILLED WATER PIPING Supply of Heavy quality Class "C" MS Pipes (Conforming to IS 1239) with necessary fittings like Elbows, Reducers, DIN Flanges, insulated with PUF insulation covered with GI spiral ducts in factory. Wherever, pre-insulated pipes are not possible such as AHU brach piping, equivalent thickness of PUF sections with GI cladding shall be considered.Wherever, pipe racks are not made available by clients, vendor shall provide structural supports from floor & wall which can be claimed in BOQ item dedicated for MS supports . However, please include the cost of required high density PUF saddles, U clamps, etc here. For all pipes to be supported in ceiling, the cost of factory facricated pipes supports with necessary rubber beadings shall be included here.The piping flange connection bolts and nuts should be of hot dipped galvanised.
80 mm dia
50 mm dia
BUTTERFLY VALVES (CHW PIPING) WITH FLANGES : Supply of Butterfly valves with 1000kPa working pressure,100 Deg C maximum operating temperature, Cast iron body for DN 50 to 300, Ductile iron body for DN 350 plus, EPDM Seal, Stainless Steel 416 Shaft material, Nylon coated ductile iron, extended stem, lever lock handle, and wafer style for installation between flanges and confirming to IS:13095. Use DIN Flanges for connections with GI bolt nuts.Insulation of valves shall be similar to Chilled water pipes. The scope shall includes 2 nos. of Flanges alongwith required GI Bolt nut to be supplied for each valves.
80 mm dia
50 mm dia
DX-Air Handling Units
Installation, testing & commissioning of DX Double skin draw thru type Vertical Air handling unit (as per the drawing) of 28mm panel thick duly sandwich insulated with PUF having 0.7mm Preplasticised steel complete with backward curved centrifugal fan having efficiency more than 60% , IE3 motor belt drive package, coil section with 6 Row deep copper tube aluminium fins DX cooling coil having fins 5 fins per cm, cooling coil shall be half inch OD copper tube of thickness not less than 0.4mm. Flat Filters section with Flat filters with efficiency of 80% down to 20 micron Approved Makes: Airprism/Luftek/ Thermoflex The AHU cost shall include 1set of commissioning filters, outlet Al. VCD etc.
0.0M LEVEL - UPS Room at 0 M level Vertical Floor Mounted AHU having 3740 M³ per hour against 40 mm static with capacity of 5.5TR with six row DX cooling coil connected to 1no. 5.5TR DX Condensing unit
DX CONDENSING UNIT Installation, testing and commissioning of air cooled DX outdoor condensing unit with high efficient scroll compressor, condenser coil etc. Each unit connected to and, interconnected refrigerant piping, full charge of refrigerant gas including additional top up and oil, control cabling etc. as per detail given in specifications and having following items. . with fan & motor,Integral refrigerant piping, safety controls & cutouts,drier with compressor service shut off valves, control panel housing the starters for the compressors /condenser fan motors,single phase preventor,compressor crank case heater, HP / LP cutouts, Oil safety switch overload thermal overload protectioncontrol wiring with panel Refrigerant to be used shall be - R 410 A only. Approved Makes: Voltas / Daikin/ Blue star Limited / Carrier/ Toshiba
0.0M LEVEL - UPS Room at 0 M level 5.5 TR
LOW SIDE WORKS
Application of chemical resistance coating for Condenser coil/ fins for corrosion/errosion protection
Installation of Electrical sub panel wall/ floor mounted with 1no. Incoming power feeder provision and single/ mulitple outgoing feeders for DX condensing units including Switch Disconnecting Fuse(SDF), DOL starter for AHU motor , isolators, contactors, overload relays single phasing preventor etc.
UPS room- 3740CMH AHU-1no. + 5.5TR Condensing unit- 1no.
Installation of Power cabling and double earthing between the above panel to motors and control cabling/ double earthing from panel starter to the local on /off switch etc. with in AHU room/near AHU UPS room at 0.0Mtr Level
Armoured copper Power cabling for 1no. 3750CMH AHU
Armoured copper Power cabling for 1no. 5.5TR Cond. Unit
Copper control cabling and GI double earthing for above system
Installation of Expansion Valve, drier etc. Make: Sporlan/ Danfoss
Additional Refrigerant gas R410a
Installation and Testing & Commissioning of 20G Copper tubing for connecting the AHUs and VRF Outdoor units with Supply and application of Elastomeric nitrile rubber type tubular insulation of fire retardent grade of conductivity less than 0.22 Btu.in./(h.ft² °F) and density 50 Kg/CMT with 19 mm thickness for suction line. Indoor & Outdoor insulation shall be mechanically protected with two layers (07 mil thick each layer) of adhesive and Glass Cloth / CSM and Outdoor insulation shall have two coats of special UV resistant paint.insulation 0.0M LEVEL Note: The Vendor to quote the rate for copper piping - suction line and liquid line suitable for their Equipments UPS Room at 0 M level
Suction line 1/2"
Liquid line 7/8"
Drain piping Fxing in position the following PVC pipes for drain cut to required lengths and installed complete with all necessary fittings like elbows tees & reducers with 9mm Nitrile insulation
40 mm dia
Fixing of Temperature & RH Display with Temperature controller including control cabling etc. (UPS rrom, Rewinder Panel room, I/O Rack room, Switch gear room -1)
Fixing of Thermostat with sensor and control cabling for individual unit
Any other items required for satisfactory for the Project the same to be included and to specify the items and rates clearly
Bidder Name
Amount in Words
Blue Star Ltd (BID ID -1537699)
Unimech systems private limited (BID ID -1537066)
Unimech systems private limited (BID ID -1537066)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
BidDocumentSigned.pdf
Tender Documents • 4.98 MB
BOQ_754203.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid