Shri Nitesh K Singh, IDSE AEE AGE (I) R and D NSTL
AGE (I) R and D, NSTL Complex, Visakhapatnam 530027
8427 REPAIR/ MAINTENANCE AND REPLACEMENT OF DEFECTIVE PARTS OF STANDBY DG SETS OF VARIOUS CAPACITIES AND ALLIED WORKS AT DRDL KALINGA UNDER AGE(I) R n D NSTL, VISHAKHAPATNAM
2022_MES_563026_2
AGE I R AND D NSTL VIZAG 8427
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Visakhapatnam
class E, cat b(i)
7 documents required · 7 mandatory
₹500
AGE I R and D NSTL Visakhapatnam
₹15,000
Yes
19 Jan 2023
14 Dec 2022
9 Jan 2023
14 Dec 2022
7 Jan 2023
19 Dec 2022
Amount
M&L for carrying out general servicing and repairs to Engine of DG set of capacity 725 KVA of Make: Caterpillar (Model : 3412 DITA GP 3) including servicing of water pump, replacement of unserviceable spares, carrying out 'B' Check as per manufacturer's recommendations including replacement of oil filters, diesel filters with 'O' rings, Engine Oil and toping up of coolant up to required level complete all as specified and as directted. Notes : (a) Supply only Engine Oil and coolant shall be measured and paid separetely. (b) Rate quoted is inclusive of Secondary Diesel fillter Cat Part No 1R0749 - 02 Nos, Primary Diesel fillter Cat Part No 81531064 - 01 Nos, O rings (Gasket) Cat No 81526106 - 01 Nos and Oil filter Cat No 1R1808-02 Nos of Make: Caterpillar. (c) All the spares require replacement during servicing shall be measured and paid separately as 'Supply only' (d) Servicing of Radiator & self starter shall be measured and paid separately
M&L for carrying out general servicing and repairs to Engine of DG set of capacity 300 KVA of Make: Greaves Ltd (Model No TBD 2 V12 MK-1) including replacement of unserviceable spares, carrying out 'B' Check as per manufacturer's recommendations including replacement of oil filters, diesel filters with 'O' rings, Engine Oil and toping up of coolant up to required level complete all as specified and as directted. Notes : (a) Supply only Engine Oil and coolant shall be measured and paid separetely. (b) Rate quoted is inclusive of Oil filters, diesel filters with O rings. (c) All the spares require replacement during servicing shall be measured and paid separately as 'Supply only' (d) Servicing of Radiator & self starter shall be measured and paid separately
M&L for carrying out general servicing and repairs to Engine of DG set of capacity 100 KVA of Make: Greaves (Model : 4YDC MK 3 Trolly mounted) including replacement of unserviceable spares, carrying out 'B' Check as per manufacturer's recommendations including replacement of oil filters, diesel filters with 'O' rings, Engine Oil and toping up of coolant up to required level complete all as specified and as directted. Notes : (a) Supply only Engine Oil and coolant shall be measured and paid separetely. (b) Rate quoted is inclusive of Oil filters, diesel filters with O rings. (c) All the spares require replacement during servicing shall be measured and paid separately as 'Supply only' (d) Servicing of Radiator & self starter shall be measured and paid separately.
M&L for carrying out general servicing and repairs to Engine of DG set of capacity 180 KVA of Make: Cummins (Model : QSB-6.7 G14) including replacement of unserviceable spares, carrying out 'B' Check as per manufacturer's recommendations including replacement of oil filters, diesel filters with 'O' rings, Engine Oil and toping up of coolant up to required level complete all as specified and as directted. Notes : (a) Supply only Engine Oil and coolant shall be measured and paid separetely. (b) Rate quoted is inclusive of Oil filters, diesel filters with O rings. (c) All the spares require replacement during servicing shall be measured and paid separately as 'Supply only' (d) Servicing of Radiator & self starter shall be measured and paid separately.
Supply only Air cleaner of existing size suitable for 725 KVA DG Set of Make: Caterpillar. [Cat Part No 81536080].
Supply only Air cleaner of existing size (inner element and outer element) suitable for 300 KVA DG Set of Make: Greaves Ltd.
Supply only V belts for radiator fan of 725 KVA DG sets of existing size [Cat No 4N8216 of make: Caterpillar]
Supply only V belt for Alternator of 725 KVA DG sets of existing size [Cat No 9L6639 of make: Caterpillar]
Supply only V belt for Radiator/Alternator of 300/100 KVA DG sets of existing size
Supply only Engine oil 15 W 40 or as per manufacturer's recommendation.
Supply only Radiator Coolant
M&L for repair and overhauling of self starter assembly 12/24 V of DG Set of capacity up to 725 KVA, complete including replacement of pinion, bushes, solenoid, carbon brushes and springs etc. complete as per requirement and as directed
Supply only cooling temperture sensor suitable for 725 KVA DG Set [Make: Caterpillar, Part No: 2468150]
Supply only coolant level sensor suitable for 725 KVA DG Set [Make: Caterpillar, Part No: 1916587]
Supply only regulator (thermostat) including gasket suitable for 725 KVA DG Set [Make: Caterpillar, Part No: 81537094 - 02 Nos & 4N1156 - 02 Nos]
M&L for scrapping and cleaning the old painted surfaces of entire exposed parts of 300 KVA DG Set with wire brushes etc. including removing oil & grease stains using appropriate cleaning agents and applying two spray coats of heat retardant paint of approved tint all as directed by Engineer-in-charge.
All as per item above herein before but for 100 KVA DG set including trolley
Supply and installation in replacement lead acid battery 12 V 180Ah complete (Initially charged) and connected to DG sets complete all as directed [Make: Exide/ SF/ Amaron]
Supply and installation in replacement lead acid battery 12 V 150 Ah complete (Initially charged) and connected to DG sets complete all as directed [Make: Exide/ SF/ Amaron]
M&L for opening the fuel tank of 300KVA/ 725 KVA DG set, thoroughly cleaning internal surfaces, scraping the surfaces and applying two spray coats of synthetic enamel paint and reassembling the tank complete all as directed by Engineer-in-charge.
M&L for opening the fuel tank of 100 KVA DG set to 300 KVA DG Set, thoroughly cleaning internal surfaces, scraping the surfaces and applying two spray coats of synthetic enamel paint and reassembling the tank complete all as directed by Engineer-in-charge.
M&L for carrying out repairs/servicing of starter solenoid switch capacity 12/24 Volt connected to the DG set of various capacity including replacement of defective parts, rewinding of coil complete all as specified and as directed.
M&L for carrying out repairs to 12/24 volts Alternator/dynamo by replacement of carbon brushes, electronic regulator/ rectifies, bearings reassembling the same and testing complete all as directed
Supply and fixiing in replacement of demage AVR (Automatic Voltage Regulator) of DG Set capacity 725 KVA of make Caterpiller all as specified and directed by Engr - in - Charge.
Supply and laying in replacement synthetic rubber insulated mats 2 mm thick for voltage upto 3.3 KV for electrical purpose as per IS 15652 - 2006, suitable for electrical shock safety of sizes 2 m x 1 m all as specified and directed by Engr - in - Charge.
Supply and laying in replacement synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 KV for electrical purpose as per IS 15652 - 2006, suitable for electrical shock safety of sizes 2 m x 1 m all as specified and directed by Engr - in - Charge.
Dis-connecting the ACB ( Air Circuit Breaker) panel capacity ranging from 600 to 2000 Amp of Make : CG/ABB /L&T /Simens /Schnider, Over hauling of complete bearker panel by taking out the trolley of the breaker, opening the total mechanism of breaker checking its contact, baffle plates and other minor parts, cleaning the complete accessories carefully. Minor repairs shall be rectified, Parts/accessories shall be cleaned, the tank, baffle plates, rotating contact, upper supports, lower supports, drive assembies and all other spare parts all as directed by Engineer-in-Charge. Reassembled Breaker after repair/ replacement of the faulty parts, testing and calibration of ACB realy settings complete all as specified and directed by Engr - in - Charge.
Supply only spring charging motor 220 V AC/DC supply.
Supply only Shunt Release EA1 415V AC
Supply only Under-voltage Release 415V AC
Supply only Closing Preventer 415V AC
Supply only Jaw contact Assy. 630/1000A S1
Supply only Jaw contact Assy. 800/1000A C/H & 1250A S1
Supply only Jaw contact Assy. 1250/1600A C/H, 1600/2000A S1
Supply only Pole Assy. 1250/1600 C & 1600 S1 D/O
Supply only Arc Chute 800-2000 E, 800-1600 C/H, 1600/2000S1 (440V)
Supply and fixing on load change over switch 630 A, 415 Volt, AC 23 B, Isc = 70KA rms ref IS: 13947-3
Taking down/out old unserviceable burnt/punctured/faulty aluminium cable/ Cross linked poly-ethylene (XLPE) insulated, LT cable of any size from pole/ laid in trenches/through pipe in road crossings/ paths /drains /ducts /floors /along poles /walls/ceilings/ equipments etc and relaying the same after removing of defect including cutting making jointing complete all as specified and as directed by Engineer-in-Charge. (Note:- (i) Earth work and cable jointing kit will be measured and paid separetly
Supply, lay, connect, test and commissioning of LT XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 1100 volts grade of size 3.5 Core 185 Sq.mm complete all as specified and directed.
Supply, lay, connect, test and commissioning of LT XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 1100 volts grade of size 3.5 Core 25 Sq.mm complete all as specified and directed.
Excavating in trenches n. exc. 1.5m wide and n. exc. 1.5m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes etc. n. exc. 10sq.m. on plan and n. exc. 1.5m in depth and getting out in hard/ dense soil.
Returning, filling in including spreading leveling watering and well ramming in layers not exc 25cm in any type of soil.
Removing excavated materials to a distance not exc. 50m and depositing where directed at a level n.exc 1.50m above the starting point.
Supply & lay precast cable cover class LV, type 1, flat of size 250 x 150 x 40mm for cable protection all as specified
Supply and spread river sand as in cushioning for UG cable all as specified in clause 19.75 of SSR Part I. [Note: Punned down thickness shall be considered for payment]
LAKSHMI SAI CONSTRUCTIONS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .