Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.0 CrAccepted-AOC | ₹37.0 Cr | L1 | Accepted-AOC Accepted being workable and reasonable rates are quoted |
| 2 | L2₹41.4 CrRejected-Finance PLOT NO HIG 7 CHUNVATI LANE GOPALGAN BALASORE 756001 | BALESHWAR | ODISHA | 756001 | ₹41.4 Cr | L2 | Rejected-Finance Being Not L1 |
| 3 | L3₹41.6 CrRejected-Finance | ₹41.6 Cr | L3 | Rejected-Finance Being Not L1 |
| 4 | L4₹41.9 CrRejected-Finance | ₹41.9 Cr | L4 | Rejected-Finance Being Not L1 |
| 5 | L5₹41.9 CrRejected-Finance K 99 LGF KALKAJI NEW DELHI 110 019 | NEW DELHI | SOUTH EAST DELHI | DELHI | 110019 | ₹41.9 Cr | L5 | Rejected-Finance Being Not L1 |
Tender Value
₹39 Cr
EMD Value
₹15 L
Closing Date
20 Jul 2023, 6:00 pmClosed
DDG and CE
DDG CE Conference Hall DGNP Near pipe line Junction Visakhapatnam Pin-530014
PROVISION OF OFFICE BUILDING AND ALLIED SERVICES UNDER WP8B AT NAVAL STATION RAMBILLI VISAKHAPATNAM
2023_MES_591750_1
DDG CE V TOKEN 14 OF 2021-2022
Open Tender
Civil Works
540 days
Rambilli
As per NIT
7 documents required · 7 mandatory
₹3,000
DGNP
₹15 L
Yes
DDG CE Conference Hall
31 Oct 2023
27 Apr 2023
22 Jul 2023
27 Apr 2023
20 Jul 2023
10 Jul 2023
27 Apr 2023 - 11 May 2023
11 May 2023
Amount
Lump sum amount worked out by the contractor for "BUILDINGS & STRUCTURES" as listed in Schedule 'A' Part-I on Serial Page No. 37(R)
Lump sum amount worked out by the contractor for "SITE CLEARANCE / AREA DEVELOPMENT / EARTH WORK EXCAVATION" as listed in Schedule 'A' Part-II on Serial Page No. 39(R)
Lump sum amount worked out by the contractor for "PILE FOUNDATION" as listed in Schedule 'A' Part-III on Serial Page No. 40(R)
Lump sum amount worked out by the contractor for "INTERNAL WATER SUPPLY" as listed in Schedule 'A' Part-IV on Serial Page No. 41(R)
Lump sum amount worked out by the contractor for "INTERNAL ELECTRIFICATION" as listed in Schedule 'A' Part-V on Serial Page No. 45(R)
Lump sum amount worked out by the contractor for "EXTERNAL WATER SUPPLY" as listed in Schedule 'A' Part-VI on Serial Page No. 46(R)
Lump sum amount worked out by the contractor for "EXTERNAL ELECTRIFICATION" as listed in Schedule 'A' Part-VII on Serial Page No. 48(R)
Lump sum amount worked out by the contractor for "ROAD /PATH/ CULVERT/HELIPAD" as listed in Schedule 'A' Part-VIII on Serial Page No. 54(R)
Lump sum amount worked out by the contractor for "AREA DRAINAGE" as listed in Schedule 'A' Part-IX on Serial Page No. 55(R)
Lump sum amount worked out by the contractor for "COMPOUND WALL / GATE / FENCING" as listed in Schedule 'A' Part-X on Serial Page No. 58(R)
Lump sum amount worked out by the contractor for "FIRE FIGHTING AND FIRE ALARM SYSTEM" as listed in Schedule 'A' Part-XI on Serial Page No. 61(R)
Lump sum amount worked out by the contractor for "LIGHTNING PROTECTION" as listed in Schedule 'A' Part-XII on Serial Page No. 62(R)
Lump sum amount worked out by the contractor for "HOT WATER / COOLING APPLIANCES" as listed in Schedule 'A' Part-XIII on Serial Page No. 63(R)
Schedule "A" Part - XIV: [Miscellaneous Items] [Internal Water Supply, Internal Electrification, External Water Supply, External Electrification, Lightning Protection, Fire Fighting and Fire alarm System, Road, DG Set, Lifts, Air Conditioning, Refrigeration and Boom Barrier]: [To be quoted by the bidder.]
M&L for Point wiring with 1.5 Sq.mm FRLSH PVC insulated unsheathed copper conductor cable, single core multi stranded 1100Volt grade confirming to IS 694: 1977, drawn in and including rigid PVC conduit not less than 20mm bore, concealed type, medium grade as per IS 9537 (Part 1-1983) with conduit accessories, junction boxes, tees, terminal boxes with and including factory made MS boxes, modular cover plates with frame for mounting modular switches, including one run of 1.5 Sq.mm single core FRLS PVC unsheathed copper conductor cable as earth continuity conductor and connected to common earth dolly, for one light / fan point controlled by one one way switch, complete all as specified and as directed. Note: Cutting chases and making good surfaces shall be included in the unit rate.
Description all as per Serial Item No. 15 here in before but for light / fan point controlled by two twoway switches complete.
Description all as per Serial Item No. 15 here-in-before but with 2.5 Sqmm copper conductor cable and 2.5 Sqmm cable as earth continuity conductor for 3 pin 5Amp switch socket point, on independent board, complete all as specified.
Description all as per Serial Item No. 15 here-in-before but for 3 pin 5Amp switch socket point, on Same board, complete all as specified.
Description all as per Serial Item No. 15 here-in-before but with 4.0Sqmm copper conductor cable and 4.0Sqmm cable as earth continuity conductor for 3 pin 5/15Amp switch socket point, on independent board, complete all as specified.
Description all as per Serial Item No. 15 here in before but for Bell / Buzzer point controlled by bell push complete.
Supply and fixing twin core copper telephone cable of size 0.5sqmm, PVC insulated PVC sheathed, complete all as specified.
S&F Modular type Telephone jack with shutter glossy white RJ 11 port with suitable gang box, complete all as specified and directed.
S&F Modular type Data socket white glossy RJ 45 and RJ 11 Port with suitable gang box and face, complete all as specified and directed.
S&F Modular type TV socket outlet, delux with suitable gang box, complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 4mm GI wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-I, including excavation / earth work in any strata, adequate quantity of charcoal and common salt, PCC chamber with with RCC 1:2:4 type B1 40mm thick cover slab with suitable handle and angle iron frame of suitable size to fix the cover, with 20mm bore GI pipe light grade for watering with funnel, wire mesh and 15mm bore GI pipe medium grade for GI wire protection and 4mm GI earth wire, including testing after completion, complete all as specified and directed. Note : Earth wire will be measured after 7.5mtr from the earth strip or earth testing terminal block whichever is lesser under relevant item.
All as per Serial Item No. 25 here in before but using galvanised iron strip 32 x 6mm earthing lead and 50mm bore GI pipe medium grade as protection pipe. .
S&F LED Building Security light fitting 40Watts, 230 volts, >100lum/W, with Suitable size GI bracket made out of 25/40mm GI pipe fixed with clamps, nuts&bolts etc., complete with IP 65/66 protection with LED lamp, driver, bracket with impact and corrosion resistant and all accessories, complete all as specified and as directed. Make Cat. CIS-300-40-57-SL-DP-NGR for batten and LT8-20-865(2) for tube of Crompton or equivalent in makes given here-in-after.
S&F Energy saving, environmentally friendly & robust High bay light LED 80 Watt energy efficient, P.F>0.95, >100 lum/watt, with and including LED light driver holder connecting of with three core flexible copper conductor cable of suitable size, complete all as directed by Engr-in-charge. Make: Cat No. LHELAAU7PG7S080 of Havells or Equivalent in makes given here-in-after.
M&L for Flame proof point wiring with 1.5 Sq.mm FRLSH PVC insulated unsheathed copper conductor cable, single core multi stranded 1100Volt grade confirming to IS 694: 1977, drawn in and including stove enamelled steel conduit not less than 20mm bore, concealed type, medium grade with conduit accessories, junction boxes, tees, terminal boxes with and including factory made MS boxes, modular cover plates with frame for mounting modular switches, including one run of 1.5 Sq.mm single core FRLS PVC unsheathed copper conductor cable as earth continuity conductor and connected to common earth dolly, for one light / fan point controlled by one one way switch, complete all as specified and as directed. Note: Cutting chases and making good surfaces shall be included in the unit rate.
Description all as per Serial Item No. 29 here-in-before but with 2.5Sqmm copper conductor cable and 2.5Sqmm cable as earth continuity conductor for 3 pin 6/16Amp switch socket point, on independent board, complete all as specified.
S&F Flame proof exhaust fan, steel body, AC single phase, 230Volt, 380mm sweep, heavy duty with blades, frame, louvers, wiremesh with all accessories and necessary PCC work, complete all as specified and as directed.
S&F Flame proof DB double door, single pole and neutral 04 Way sheet steel phospetised power coated with 200 Amps rated bus bar 240 Volts neutral link, IP-20 protection, fixed in concealed position, with and including one MCB SPN 63Amp & one MCB SP 6-32Amp, complete all as specified and as directed.
S&F Voltage stabilizer of capacity 2KVA, for automatic operation, suitable for deep freezers / refrigerator / water cooler / 2 Ton AC, single phase naturally air cooled indoor type and designed for input variation 170V to 270V, output voltage stabilized at 230Volt with accuracy of ± 2.50%, complete all as specified and as directed.
S&F Voltage stabilizer of capacity 5KVA, for automatic operation, suitable for deep freezers / refrigerator / water cooler / 2 Ton AC, single phase naturally air cooled indoor type and designed for input variation 170V to 270V, output voltage stabilized at 230Volt with accuracy of ± 2.50%, complete all as specified and as directed.
S&F Time switches 415Volts, 3 phase, 20Amp rating capacity with and including contactor and steel enclosure, complete all as specified and as directed.
Supply, installation, commissioning of Metal Top Deep Freezer of capacity 1000 liters, single phase 240 Volt, 50 Hz, complete all as specified.
S&F CO2 fire extinguishers - 4.5 Kg capacity, complete with initial charge, gun metal cap, discharge hose with nozzle, wall fixing brackets etc confirming to IS : 15683 with ISI mark, complete all as specified.
S&F Gun-metal, globe or gate valves, with iron wheel head, screwed both ends, suitable for iron pipe of 80mm bore, complete all as specified and as directed.
S&F Cast Iron Foot valve ball type suitable for 50mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slots and including necessary fixing arrangement, complete all as specified and as directed.
Design, Supply, Install, testing and commissioning of centrifugal pumping set, electrically driven, horizontal split case, conforming to IS and as per CPHEE manual with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings, suitable for continuous operation with range of operation 0% to 150% of rated capacity for 440V, 3 phase, 50Hz, 30mtr head, 900 LPM discharge, with and including Soft starter, single phase preventer, control switch gear MFM meter, with suitable foot valve with Y strainer with cored hole/slots and LT panel necessary MS frame and PCC foundation as per OEM Specification, GI sheet shed for weather protection, complete all as specified and as directed. Note: Contractor has to submit drawings for approval before manufacturing at factory and pump / motors shall be confirming to GRIHA 3 rating.
M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine with and including HDPE pipe of 150mm bore of pipe suitable for 6 kgf/Sq.cm working pressure, complete all as specified and as directed.
S&F Hot dip Galvanised perforated cable tray with cover for fixing XLPE cables at various places to accommodate the cables for MCBs, Panel etc of size not less than 100X100mm, 2mm thick with necessary bends, angles, supports for fixing etc., complete all as specified and as directed.
M&L for Loop in Loop Out Junction box of size 300mm x 300mmx 150mm of FRP made with IP 65 protection of thermoplastic circuit breaker boxes with metric knockouts for cable entry and exit, comb climate Cable Glands of IP66/IP67 for cable entry and Grommets IP 65 for conduit for cable exit with MCB 6-32 Amps, 10KA, C Curve overload and short Circuit protection, with 4 way connector, terminals as bus terminals for cable with necessary fixing arrangements and with cable glands etc., complete all as specified and as directed.
S&F Street light bracket (with two sets of clamp,nuts & bolts) made out of 40/50 mm medium grade GI pipe of length not less than 1.20m, bend to shape and with fixing arrangement duly welded & painted, complete all as specified and as directed.
M&L for PVC insulated, PVC sheathed electric control cable galvanized steel strip or wire armoured, multistranded copper conductor cable of size 2 core x 2.5 sqmm, Heavy duty, 1100 Volts, FRLS Grade, ISI marked with all accessories, complete all as specified.
Design, Supply, Installation, Testing and Commisioning of GOODS LIFT with capacity of 1000Kg Weight, Speed 0.5 metre/sec, Lift with single speed motor 415 Volts, 3 Phase, AC 50Hz supply conforming to IS-14665, suitable to serve G + 01 upper floors with AC Variable Voltage and Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (Electric motor driven mechanism), sliding stainless steel doors, Automatic Rescue Device (ARD) System, 3D infrared sensor in full height of door and built-in announcing system without hand set (03 Nos, One each in car, machine room and Near Ground floor landing door) complete all as specified.
M&L for Valve chamber of size 1000mm x 1000mm x 600mm internal dimensions, with and including excavation in any type of soil, spreading, levelling and refilling etc. PCC (1:4:8) type D2 for foundation, Fly ash brick work of one brick thick wall in CM (1:4) including internal plaster 15mm thick in CM (1:4) external plaster 15mm thick(1:4) upto 150mm below GL and providing coping in PCC (1;2:4) type B1, angular iron frame of size 50x50x6mm with 6mm thick MS plate cover complete including locking arrangements and having FRP coating of 2mm thick on both inside and outside surfaces, complete all as specified and shown in TD drawing.
Supply, laying, testing and commissioning of Ductile Iron pressure pipe of 100mm bore with socket and spigot ends with blast furnace sludge cement with Portland cement properties suitable for push -on-jointing with inside cement mortor lining with internal metallic zinc coating and external black bitumen coating duly ISI marked, confirming to IS-8329:2000, class K-9, PN-10 rating, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately.
M&L for DI Specials such as Bends , tapers any type, Tee pieces, single branch, "Y" junction, double branch, cross, collars, caps and plugs for connecting up to 150mm bore DI Pipe all as per IS:9523, complete all as specified and as directed. Note: Fittings shall be conforming to IS 9523:2000.
M&L for RCC (M25) Pipe / Cable route indicator of size 800mm x 400mm x 75mm thick, minimum 500mm height above GL, duly painted with two coats of super enamel yellow colour over a coat of primer, duly marked with red colour words such as DI Pipe / HT 11KV / LT Cable 1.1KV cables as directed with and including grouting in PCC 1:2:4 (Type B1), necessary earthwork, complete all as specified and directed.
Supply, Installation, testing & commissioning of Silent Diesel Engine driven generating set, prime mover with electronic governing 415Volt (at 0.8 PF) 320KVA, 3 phase, 50 Hz, 1500RPM with accoustic enclosure and canopy type (indoor use) made out of min 14 gauge CRCA sheet with AMF Panel with and including all excavation, PCC foundation (as per manufacturers recommendation's), anti vibration pads, tamper standard control panel as per manufacture instructions, The DG set will comprise of following: -(a) Alternator: Standard design alternator rated at 320KVA net out put at site, self excited, self regulated through an AVR, screen protected, revolving field, brushless design with permanent lubricated bearings with winding in each pole, insulation class H, voltage regulation ± 1.5 % of rated voltage 'No load to full load'. The alternator shall be in a position to generate supply with frequency regulation within ± 1 % tolerance and permissible overload of 10 % for one hour in 12 hrs continuous run and conforming to IS 13364 with latest amendments. (b) Diesel Engine adequate capacity suitable for 200 KVA Alternator water cooled to drive independently the above alternator directly coupled through flexible coupling multi cylinder Multi stroke direct injection cold starting 1500RPM as per revant IS, IS:10001/ 10002 BS 5514 with in overload capacity of 12 hrs continuous running, with standard accessories all as specified and required for site handling and operation, the scope of accessories shall be as under :- (i) Air intake system : air intake manifold air cleaner. (ii) Exhaust system : Turbo charger SS Flexible below silencer complete with MS exhaust piping of suitable size up to and outside the building covered with glass wool covered under aluminium foil of 28 gauge, adequate to exhaust without transferring vibration to building/walls as per latest CPCB Norms. (iii) Coolant system : Engine water pump, radiator with fan and fan belt. (iv) Lubricating system Oil pump of suitable capacity, lub oil pump and lub oil filter.
(v) Fuel system : Fuel injection pump 12/24 Volts (as per OEM recommendation) DC solonoid switch nozzle mechanical/electronic governor, replaceable fuel filter, fuel tank made of 14 SWG sheet with drain valve, air vent inlet and outlet connection, fuel supply piping from tank to pump & to engine including return of over flow fuel with level indicating arrangement duly marked in inches/Litres. Fuel tank should be of adequate capacity for 8 hrs running at full load. (c) Starting system: 12/24V DC self starter 12/24V DC battery charging alternator, start & stop push button, ignitor key/ switch, Battery of reputed make of suitable capacity in changed condition with its copper leads of adequate size as per OEM recommendations. (d) Base frame: common base plate with AVM pads for mounting the engine & alternator. (e) Engine mounted Instrument Panel fitted with and having digital display for following:(i) Start-stop switch with key,(ii) Water temperature indication,(iii) Lubrication oil pressure indication,(iv) Lubrication oil temperature indication,(v) Battery charging indication,(vi) RPM indication,(vii) Over speed indication,(viii) Low lub. Oil trip indication & (ix) Engine Hours indication (f) Saftey control : Lub oil pressure trip, High water temp trip & over speed trip. (g) Acoustic enclosure: Modular construction with the provision to assemble & dismantle easily at site, powder coated & stainless steel nut & bolts/external hardware, provision for filling fuel from outside the enclosure with locking arrangement, Sound proofing of enclosure with high quality rock wool /mineral wool The rock wool is further covered with fibre glass tissue & perforated sheet . A special residential silencer within the enclosure to reduce exhaust noise. Noise level 75 db (A) at 3 m distance.
S&F Air Circulator fan 450mm sweep oscillation type of approved colour and model, with complete accessories (Energy Efficient) including provision of suitable clamp, flexible cable suitable for 230volt, AC 50 HZ, complete all as specified and as directed.
Supply, Installation, testing & commissioning of boom barrier of 3.5m length x 2 in Nos set suitably for 7m wide road, complete all as directed by Engineer-in-Charge. Make: Godrej & Boyce Model : Vigiguard
S&F Construction of soakage pit of size of 1.8m diaX 1.8m deep and filled with brick bats, complete all as specified and shown on TD drawing No. DGNP/TD-202 Sheet No. 1/1.
S&F Construction of Flag Mast with SS pipe of 50mm dia, 12m height, with and including brackets, pulley, painting, complete all as specified and shown on TD drawing No. DGNP/TD-253 Sheet No. 1/1.
M&L for Cutting & Chipping of laitance concrete in piles above cut off level upto a maximum of 1m from cut off level and disposal to distance of 10KM and depositing where directed by Engineer-in-Charge.
M&L for Drilling or boring for 600mm nominal dia. bored cast-in-situ piles through any or all types of strata i.e soft/loose soil, stiff clay, gravel, cobble stone, compact moorum, soft conglomerate or loose boulders, disintegrated rock, weathered rocks/rocks etc., (except hard rock for socketing depth) upto top of socketing depth/founding depth by adopting suitable method with perennial water and disposal of drilling/bored materials outside MD land as directed, complete all as specified and as directed.
M&L for Drilling or boring for 800mm nominal dia. bored cast-in-situ piles through any or all types of strata i.e soft/loose soil, stiff clay, gravel, cobble stone, compact moorum, soft conglomerate or loose boulders, disintegrated rock, weathered rocks/rocks etc., (except hard rock for socketing depth) upto top of socketing depth/founding depth by adopting suitable method with perennial water and disposal of drilling/bored materials outside MD land as directed, complete all as specified and as directed.
All as per Serial Item No. 62 here in before but for 600mm nominal dia through hard rock for founding depth minimum 2D (Where D is dia of pile), complete all as specified.
All as per Serial Item No. 63 here in before but for 800mm nominal dia through hard rock for founding depth minimum 2D (Where D is dia of pile), complete all as specified. Notes for Item Nos. 62 to 65:- (i) The depth of boring for piles shall be measured from existing ground level to the approved founding level. (ii) It shall be ensured that the waste bentonite slurry/ drilled or bored material is pumped off from the premises to locations shown by GE to contractor at his own cost. (iii) All channels/tanks made for bentonite circulations shall be filled with approved moorum obtained by contractor at his cost after clearing all bentonite cakes. (iv) The contractor may use any approved method as approved by GE for boring without any extra cost to the Govt. The rates for boring of piles shall be inclusive of any method/ casing that may be used by the contractor for bored piles. Nothing extra shall be paid. (v) For the purpose of payment of boring/drilling, description of hard rock shall be as given in SSR Part-I specification. (vi) The rate quoted by the contractor shall be inclusive of the rates for the shifting and setting up of piling rig as many times as required.
Carrying out routine load test on 600mm dia pile (working pile) as per standard procedure given in IS-2911 (Part IV) by high strain dynamic load with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc and submission of reports for 1.5 times of the design load, complete all as specified and as directed.
Carrying out routine load test on 800mm dia pile (working pile) as per standard procedure given in IS-2911 (Part IV) by high strain dynamic load with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc and submission of reports for 1.5 times of the design load, complete all as specified and as directed.
Carrying out initial load tests on test pile of 600mm dia as per standard procedure laid down in IS-2911 by static load test method with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc. as specified and as directed by GE and submission of reports for 2.5 times of the design load in non-working areas in the vicinity of site, including the cost of new piles with specification as same as working pile with minimum depth of socketing into the hard rock 2D (Where D is dia of pile) depth, complete all as specified. Note: Load rquired for testing as per IS shall be arranged by the contractor and test pile shall be abondoned after testing.
Carrying out initial load tests on test pile of 800mm dia as per standard procedure laid down in IS-2911 by static load test method with compressive strength, including construction of test cap, dismantling the cap after the test and clearing the site and maintaining complete records of load settlements etc. as specified and as directed by GE and submission of reports for 2.5 times of the design load in non-working areas in the vicinity of site, including the cost of new piles with specification as same as working pile with minimum depth of socketing into the hard rock 2D (Where D is dia of pile) depth, complete all as specified. Note: Load rquired for testing as per IS shall be arranged by the contractor and test pile shall be abondoned after testing.
M&L for High density poly ethylene pipe 150mm dia (HDPE) of pressure rating 6 kgf/cm2, laid in trenches, complete all as specified.
Supply, Install, testing and commissioning of non woven Geotextiles of minimum 285 grams/SqM, consists of 100% poly polypropylene continuous multifilament (end-end fibbers), nonwoven needle punched type geotextile, including third - party testing, complete all as per manufacturers instructions and as directed by Engineer-in-Charge.
Earth work in excavation by mechanical means (Hydraulic excavator) over areas (exceeding 30cm in depth, 1.5m in width as well as 10Sqm on plan) not exceeding 1.50 m in depth and including getting out and disposal of excavated earth lead upto 50m and lift upto 1.5m, as in filled up earth including boulders, complete all as directed by Engineer-in-Charge.
M&L for Retro reflective Painting, centre line, apron markings etc., either continuous or broken lines to the required width and length over the new surface either on bituminous / concrete surface with solvent based road marking paint (Retro reflective paint) of approved make as specified and glass beads shall be applied at the rate of 0.25 Kg per Sqm (Reflective index 1.5) with self propelled airless spray painting equipment including preparation of surface, complete all as specified and as directed.
anjaliinfratech
LIRA CONSTRUCTIONS PVT LTD
B DURGA REDDY INFRASTRUCTURES PRIVATE LIMITED
jd constructions
SOOD ASSOCIATES PVT LTD
SLC PROJECTS Pvt Ltd
SVS PROJECTS
RAJYALAKSHMI BUILDERS
Bidder Name
Indus Projects Private Limited
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid