COMDT(ENGR)
SHQ(DDN) ITBP SEEMADWAR DEHRADUN(UKD)
Annual repair and maintenance of Sub station installed in main and SFA campus of 23rd Bn ITB Police, Seemadwar Dehradun(UKD) for the year 2023 24
2023_ITBP_770557_1
No.-ITBP/SHQ(DDN)/23RD/2023-28 Dtd-08.09.23
Open Tender
Electrical Works
Item Rate
90 days
23rd bn itbp seemadwar dehradun
as per tender docs
2 documents required · 2 mandatory
₹0
₹13,990
1 Apr 2024
8 Sept 2023
18 Sept 2023
8 Sept 2023
15 Sept 2023
8 Sept 2023
Amount
Testing of earth resistance and Testing of earth pit including checking resistance etc and repair/ replace if required.
Dehydration and Filtration of Transformer oil of 11 KV Transformer, Remove the Moisture, sludge, Acidity and mainly to improve the BDV and Resistivity of transformers oil. After Dehydration and filtration of oil the BDV (Breakdown Voltage Test) of oil should be 60 KV and above .
Top up of Transformer oil in transformer 1 & 2 complete as per direction of Engineer-in charge.
Servicing and Overhauling of 11 KV OCB (Oil Circuit Breakers) of GEC make and testing & calibration of relays, Earth fault over current etc. including small material complete as per direction of Engineer-in charge.
Servicing and Maintenance of LT ACB (Air Circuit Breakers) including cleaning of breaker with CRC-226,removal of old grease and re-greasing the same with recommended grease., Check condition of arcing contact and gap between fixed and moving arcing contacts shall be checked. Checking presence of all circlips, checking condition of ACB wiring and replace if required.etc complete as per direction of Engineer-in charge.
Providing and Replacement of Pannel Spout complete GEC Make OCB
Complete testing of Transformer including minor repair like Repairing of T/F leakage of oil including replacement of oil seal, gasket ,HT/LT bushing , Nut bolts packing of top cover sheet, Inspection sheet, conservator tank Complete as per direction of Engineer-in charge.
Providing and Replacement of 11 KV C.T 30/15/5 Amp double ratio protection & metering GEC Make.
Servicing and Overhauling of 11 KV V.C.B (Vacuum Circuit Breaker) of Kirloskar make and Testing & calibration of relays ,Earth fault over current etc. including small material.
Re-Insulation of Non-Moisturized paint V.C.B and O.C.B.
Servicing and Maintenance of 11 kv (CSS) compact transformer RMU (near Pump room) and testing LT ACB Work complete as per direction of Engineer-in charge.
Servicing and Maintenance of 11 kva RMU at Main Sub Station and testing LT ACB Work complete as per direction of Engineer-in charge.
Providing and Replacement of Power Fector KVR (20/ 25 KVR) complete as per direction of Engineer-in charge.
Testing, Servicing and Maintenance of Power Fector Really complete as per direction of Engineer-in charge.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories and providing masnory enclosed with cover plate having lockingarrangement and watering pipe of 2.7 meter long etc. With charcol/ coke and salt as required
Providing and fixing 25mm X 5 mm copperstrip in 40 mm dia G.I. Pipe from earthing electrode including connection with bress nut, bolt, spring, washer excavation and re-filling etc as required
RAM CHANDER GUPTA
R.V. ELECTRICAL ENTERPRISES PVT. LTD.
DS Constructions Deepanshu Agarwal
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .