Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 LAccepted-AOC VILL P O KALINAGAR SOUTH 24 PARGANAS PIN 743610 | KALINAGAR | SOUTH 24 PARGANAS | WEST BENGAL | 743610 | L1 | Accepted-AOC Work order issued | |
| 2 | L2₹2.2 L+₹614 (0.28%)Rejected-Finance NARAYANGARH DOLTALA GHOLA CANNING PIN 743376 | CANNING | SOUTH 24 PARGANAS | WEST BENGAL | 743376 | L2 | Rejected-Finance L2 | |
| 3 | L3₹2.2 L+₹1,310 (0.60%)Rejected-Finance P O DHAP DHAPI MALLICKPUR P S BARUIPUR 24PGS S PIN 743387 | 24 PARAGANAS SOUTH | WEST BENGAL | 743387 | L3 | Rejected-Finance L3 |
Tender Value
₹2.2 L
EMD Value
₹4,371
Closing Date
26 Sept 2024, 12:00 pmClosed
Assistant Engineer
Baruipur Electrical Sub Division PWD
Installation of aircondition machine cable some wiring point and supply of Tube light at Shree Ramkrishna Rural Hospital Jaynagar II
2024_WBPWD_749987_1
WBPWD/AE/BESD/eNIT02/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Jaynagar II
Please refer Tender documents.
4 documents required · 4 mandatory
₹4,371
Baruipur Electrical Sub Division PWD
4 Oct 2024
19 Sept 2024
30 Sept 2024
19 Sept 2024
26 Sept 2024
20 Sept 2024
19 Sept 2024
Amount
Supply & Delivery of High-wall Split-type Air-Conditioner having following specification: Cooling Capacity - 5.2 kW (Minimum) Minimum ISEER - 3.8, BEE level - 3-Star (min) IS Compliance - IS-1391(Part-I & Part-II) with all amendment Refrigerant - R410A/R32 Compressor - Rotary/Scroll Evaporator & Condenser Coil - Copper Operating outdoor temperature - 50ºC and above Power supply -230V, 50Hz (±tolerance asper applicable standard),as directed by EIC.. The scope of work is also includes supply of following (i) Necessary refrigeration copper line with nitrile rubber insulation and wrapping tape - 3 mtr incl.25 A plug Top (ii) Necessary 3/4 core copper cable (FRLS type - make : Finolex/RR Kable/Polycab/Havells) - 3mtr. [Make: Mitsubishi Electric( C. General/ Zamil)
Installation, Testing & Commissioning of Indoor & Outdoor unit of above Hi wall split AC machine after making hole in wall etc as per direction of EIC including Supply of required Refrigerant, S&F of necessary fixing arrangement for indoor and 40 x 40 x 5 mm MS angle iron frame for outdoor unit (or arrangement recomended by Manufacturer), duly painted, laying and making connection of refrigeration pipe, power cable, drain pipe etc as per direction of the EIC.
S&F of additional following items for length exceeding 3 mtr for complete installation and commissioning of aboove AC machines. (i) Supply & Fixing of extra refrigerant pipe (as requisite dia) with nitrile rubber insulation and wrapping tape [each mtr Refrigerent pipe will include cost of 1 metre liquid pipe line and 1 mtr gas pipe line of required dia and other accesories as required].
S&F of additional following items for length exceeding 3 mtr for complete installation and commissioning of above AC machines. i) 3 core 4 sq.mm. and 4 core 1.5 sq.mm. FRLS type PVC/XLPE insulated, multi-stranded copper unarmoured cables. (Make : Finolex/RR Kable/Polycab/Havells)
Supply & laying Soft Drawn PVC Drain Pipe 19 mm dia with proper supports & brackets as per direction E.I.C.. (Make: Suprime/Oriplast)
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex/ RR Kable/ Polycab/ Havells) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 2.5 sq.mm.
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand/ L&T/ Siemens) 16 A. SP MCB
Supply & Fixing of 240 V., 20-25 A. Modular type starter (Legrand/ Cabtree) with 16 A. Modular switch type SP MCB ("C" Curve), 1 no. Blank Plate and 4 Module PVC Modular type switch board with 4 Module top cover plate on wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing of 240 V., 25 A. 3 pin Modular type plug socket (Legrand/ Cabtree) without plug top and switch with 2 Module PVC Modular type switch board with top cover plate on wall and making necy. connections with PVC Cu wire and earth continuity wire etc.
Distribution wiring in 2 x 22/0.3 (1.5 sq.mm.) single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex/ Polycab/ Havells) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1 x 22/0.3 (1.5 sq.mm.) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Brand approved by EIC) fixed on Modular PVC switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish. Average run 8 mtr.
Distribution wiring in 1.1 KV grade 22/0.3 (1.5 sq.mm.) single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex/ Polycab/ Havells) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 6 A. 3 pin Modular type plug socket & switch (Anchor-Penta) on 4 Module switch board with 3/4 Module top cover plate on wall incl. necy. connection making earthing attachment, painting and mending good damages to building works. On Board
S&D of 4' long single LED Tube light fitting with complete accessories & 1 no. 230V. 18 W. PC body T-LED Tube. (Philips - TMC 501 P 1xT-LED 22W P3241 and 1 no. Mas LEDTube 1200mm 18W865 T8 I – 2100lm/ CG - IGP161LT8-16 1 x T8 and 1 no. LTB-20-865-(2)/ Bajaj)) with 3 years warranty.
Fixing only single/twin Tube light fitting complete with all accessories Directly on wall/ceiling with suitable size MS fastener, Ceiling plate, nipples etc. as required.
Fixing only single/twin Tube light fitting suspended 25 cm below the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts as per GS. incl. necy. connection by 2 x 1.5sqmm. flexible copper wire of 1.10 mt. length.
S&F of 4' long 230V. 18 W. PC body T-LED Tube on existing Tube fitting incl. necessary changing of connections of existing Tube fitting (if required) by own tools & tackles as per direction of E.I.C.. (Philips/Bajaj/Havells)
S&F of suitable size of timer box, consisting with 1 no. 230 V. 16 A. DP MCB, 1 no. 20 A. 2 pole Power contactor, 1 no. 230 V., 6 A. SP MCB, 1 no. 10 A. toggle switch, 1 no. Digital timer clock, 1 no. 20 A. push on/ off type starter for manual operation, 2 nos. Inditating lamps etc. incl. suitable size of interconnecting wires (power line drawn by 4 sq.mm. copper wire & control & indicating circuit drawn by 1.5 sq.mm. copper wire with copper sockets) as reqd. as per direction of E.I.C.. (For Compound lighting)
S&D of the following size 1.1 KV voltage grade XLPE/PVC insulated Al. Armoured Cable. (Make: Havells/ Polycab/ Finolex). 4 core x 35 sq.mm.
Laying of following cables on wall/surface incl. S & F MS saddles & earthing attachments, making holes etc. as necy. mending good damages and painting. 4 core x 35 sq.mm.
Laying of following cable, after cutting wall and making holes incl., embedding the cable at an average depth of 75 mm in wall etc. and mending good the damages to original finish incl. removing the rubbish. 4 core x 35 sq.mm.
Laying of following cable in UG trench 460 mm wide x 760 mm average depth, with proper brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed 4 core x 35 sq.mm.
Laying only following Cable through existing GI Pipe. 4 core x 35 sq.mm.
S&F of following size medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. 40 mm dia
S&F of compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC insulated Al. armoured cables as below. 4 core x 35 sq.mm.
Finishing the end of following XLPE/PVC insulated Al. armoured cables by crimping method incl. S&F of solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials: 4 core x 35 sq.mm.
Note: 1) All the above rates should be quoted inclusive of all taxes & duties, District charges and LWC as applicable, with cost of maintenance, servicing, supply & replacement of spares for 1 (One) year from the date of commissioning. 2) Total is rounded off to the nearest rupees.
M/s MONDAL ELECTRIC (BID ID -5627043)
PUSPA ELECTRIC (BID ID -5624352)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .