Executive Engineer, TLMD-IV, Jammu
Office of Executive Engineer, TLMD-IV, Jammu
Replacement of Obsolete equipments by way of SITC of 220 KV, 132 KV and 33 KV CTs, CVTs, LAs and allied equipments at various grid stations under the jurisdiction of TLMD IV
2026_PDD_326671_1
TLMD-IV/J/12 Dated 30-09-2026 of 2026-27
Open Tender
Electrical Works
Turn-key
180 days
Ambedkar Chowk
As per SBD and Nit
3 documents required · 3 mandatory
₹5,900
Executive Engineer, TLMD-IV, Jammu
₹5 L
Office of Executive Engineer, TLMD-IV, Jammu
30 Sept 2026
30 Sept 2026
23 Oct 2026
30 Sept 2026
21 Oct 2026
30 Sept 2026
5 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Design, Engineering. Manufacture,workshop testing, supply including packing and forwarding, transportation, delivery at site storage charges of;- | |||||
| 1.1 | MAIN EQUIPMENTS | - | - | - | - |
| 2Capacitor Voltage Transformer | |||||
| 2.1 | Single phase, 50 c/s 220KV Capacitor Voltage Transformers (220/√3KV /110/√3V), one minute power freq withstand 460KV rms GALVANISED TANK Acc Class 0.2 as per specific technical requirement. | 9 | Nos | - | - |
| 2.2 | Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/ (110/√3V), one minute power freq withstand 275KV rms GALVANISED TANK Acc Class 0.2 as per specific technical requirement | 6 | Nos | - | - |
| 2.3 | Voltage Transformer | - | - | - | - |
| 2.4 | Single phase, 50 c/s 220KV Voltage Transformers (220/√3KV /110/√3V), one minute power freq withstand 460KV rms GALVANISED TANK Acc Class 0.2 as per specific technical requirement. | 9 | Nos | - | - |
| 2.5 | Single phase, 50 c/s 132KV Voltage Transformers (132/√3) KV/(110/√3V), one minute power freq withstand 275KV rms GALVANISED TANK Acc Class 0.2 as per specific technical requirement | 3 | Nos | - | - |
| 2.6 | Single phase, 50 c/s 66KV Voltage Transformers (66/√3KV /110/√3V), one minute power freq withstand 140KV rms GALVANISED TANK Acc Class 0.2 as per specific technical requirement | 3 | Nos | - | - |
| 2.7 | Single phase, 50 c/s 33KV Voltage Transformers (33/√3KV /110/√3V ), one minute power freq withstand 70KV rms GALVANISED TANK Acc Class 0.2 as per specific technical requirement | 9 | Nos | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
SBD.pdf
Tender Documents • 4.84 MB
BOQ_1105057.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .