| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹60.8 LAccepted-AOC R N COLONY PO BIRPARA DIST ALIPURDUAR W B PIN 735204 | ALIPURDUAR | WEST BENGAL | 735204 | L1 | Accepted-AOC Quoted amount being reasonable | |
| 2 | L2₹78.1 L+₹15.1 L (24.0%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹78.1 L+₹15.1 L (24.0%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 4 | L4₹79.8 L+₹16.8 L (26.8%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 5 | Rejected-Technical C O SHRI DIPAK SHYAM PO BINNAGURI DIPOPARA DIST JALPAIGURI W B PIN 735203 | JALPAIGURI | WEST BENGAL | 735203 | - | Rejected-Technical NOT HAVING ELIGIBLE CLASS AND CATEGORY/SIMILAR NATURE OF WORKS EXPERIENCE |
Tender Value
₹65 L
EMD Value
₹1.2 L
Closing Date
13 May 2022, 6:00 pmClosed
CWE BINNAGURI
HQ CWE BINNAGURI
REPAIR REPLACEMENT AND MAINTENANCE OF 66 11KV SWITCH YARD TRANSFORMER VCB RMU CENTRAL POWER HOUSE CABLES AND ALLIED HT WORKS AT BINNAGURI MIL STN UNDER GE (N) BINNAGURI
2022_MES_518009_1
8010/BIN(N) 01 OF 2022-23
Open Tender
Civil Works
Item Rate
180 days
BINNAGURI MIL STN
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
GE (N) BINNAGURI
₹1.2 L
Yes
9 Sept 2022
18 Apr 2022
14 May 2022
18 Apr 2022
13 May 2022
9 May 2022
Amount
Schedule 'A'
Dehydration, hot filtration de sludging of transformer oil of any type / capacity of transformer at site including all arrangement of tools plants etc to achieve dielectric strength not less than 60 KV(rms) with 2.5 mm testing gap complete all as specified and as directed.
Dehydration, hot filtration de sludging of transformer oil of any type / capacity of transformer at site including all arrangement of tools plants etc to achieve dielectric strength not less than 40 KV(rms) with 2.5 mm testing gap complete all as specified and as directed.
Supplying, filling dehydration and filtration of new transformer oil for toping up / replacement of transformer oil having dielectric strength not less than 40 KV (rms) with gap of 2.5 mm all as conforming to IS 335 of 1993 complete all as specified and as directed.
Disconnecting transformer outdoor / indoor type 11 KV /433 Volt supply system electrically both side, earth terminal and taking down carefully from pole / platform mounted on PCC foundation etc and carrying to work shop for repair of following capacities complete all as specified and as directed.:- (a) 63 KVA to 250 KVA
(b) 300 KVA to 750 KVA complete all as specified and as directed.
Supply and replacing Surge counter Monitor suitable Lightning Arrestor (Surge Arrestor) for a rated voltage of 72.5 KV, Model No SC-07-1 Make Crompton Greaves or equivalent make approved by GE complete all as specified and as directed.
M & L for rewinding of transformer HT coil with super enamelled / paper coated copper wire of existing gauge including all associated insulating material such as separator etc complete varnishing, heating including dismantling of top cover, decanting transformer oil, storing the same in suitable container, disconnection live part, dismantling of bushing, lifting of core Assay, checking the windings, cleaning of cooling tube, conservator and all internal connection after all necessary repair work and rewinding, assemble the complete transformer and refilling after necessary filtration including all internal connection etc of any type / capacity transformer complete all as specified and as directed. Note : Filtration of oil shall be measured and paid separately.
All as per item No 7.00 here-in-above but LT winding complete all as specified and as directed.
M & L for painting of transformer with two coats of synthetic enamel paints including surface preparation and painting / making SM MES No Capacity etc complete all as specified and as directed. :- (a) 200 KVA to 300 KVA
(b) 400 KVA to 750 KVA
(c) 5000 KVA (5 MVA) complete all as specified and as directed.
Supply & fixing in replacement of Silica gel breather assembly complete unit including Silica gel and taking out the old unserviceable one and providing proper gasket including replacement of corroded pipe connections to breather assembly suitable for transformer of capacity 100 - 200 KVA complete all as specified and as directed.
All as per item No 12.00 her-in-above but for transformer of capacity 250-300 KVA -ditto- complete all as specified and as directed.
All as per item No 12.00 her-in-above but for transformer of capacity 400-500 KVA -ditto- complete all as specified and as directed.
All as per item No 12.00 her-in-above but for transformer of capacity 750 KVA -ditto- complete all as specified and as directed.
All as per item No 12.00 her-in-above but for transformer of capacity 5MVA -ditto- complete all as specified and as directed.
M & L for repairing to Outdoor/Indoor transformer HT / LT bushing assembly including all worn out / damaged parts by replacing the following parts without disturbing the other parts as under complete all as specified and as directed.:- (a) Brass spindle with 05 Nos nuts, check nuts and washer of dia 12 mm.
(b) Brass spindle with 05 Nos nuts, check nuts and washer of dia 16 mm complete all as specified and as directed.
(c ) Brass spindle with 05 Nos nuts, check nuts and washer of dia 20 mm complete all as specified and as directed.
(d) Rubber bush round type of any size complete all as specified and as directed.
(e) Porcelain insulator for LT bushing of any size complete all as specified and as directed.
(f) Porcelain insulator for HT bushing of any size complete all as specified and as directed.
M & L for transformer gasket for top cover 4mm thick rubber seal cork sheet complete all as per site requirement complete all as specified and as directed.
Shifting of transformer of any capacity from 2 pole structure / PCC foundation / sub station after disconnecting HT / LT connections, earthing leads etc and reinstallation the same at new location complete all as specified and as directed.
Supply and fixing and testing of externally operated tap changer switch off load type after dismantling of transformer conservation / top cover and reassembling the same after replacing complete suitable for 63 to 200 KVA Transformer complete all as specified and as directed.
Supply fixing and testing of externally operated tap changer switch off load type after dismantling of transformer conservation / top cover and reassembling the same after repairs complete suitable for 250 to 750 KVA Transformer complete all as specified and as directed.
Supply and fixing of new temperature gauge ( 0 degree to 120 degree C ) range dial temperature as directed including taking down old unserviceable gauge.
M & L for transformer oil level indicator assembly complete with iron frame, glass, rubber packing sheet, nuts, bolts and washers etc as per existing complete all as specified and as directed.
Transporting, lifting and positioning repaired transformer from workshop to the desired place complete all as specified and as directed :- (a) 63 KVA to 250 KVA
(b) 300 KVA to 700 KVA complete all as specified and as directed.
M & L for PCC work providing PCC type B2 (1 : 2 : 4) with 20 mm graded aggregate in foundation for panel and finishing the surface even and smooth without using extra cement including breaking of old PCC complete all as specified and as directed.
M & L for rough excavation not exceeding 1.5m deep and getting out hard/dense soil for 66 KV/11KV switch yard/Sub Station complete all as specified and as directed. by the Engr-in-Charge.
M & L for screening metal, chipping etc on the site of the work, when specially order including removing screened material clear screen and stacking in separate heaps for measuring( Material from both sides of screen measured) complete all as specified and as directed.
M&L for loose filling with stone aggregate of gauge 80mm to 150mm deposited, spread and leveled in layers n.exc 30 cm thick complete all as specified and as directed.
All as per item No 34.00 here-in-before but with stone aggregate of gauge 40mm to 80mm deposited , spreas and leveled in layer n.exc 15 cm thick complete all as specified and as directed.
Supply & fixing in replacement of fabricated Duct covers made out of MS Sheet with carring handle complete of size 60cmx45cmx10mm thick complete all as specified and as directed.
M&L for opening the cover of RMU 11 KV servicing of fixed and moving contacts, repair and replacement of fixed copper terminal/contacts (Male/Female), insulation tubes including other connected items for function of RMU, lamp indicators, meters triping coil etc. Cleaning the fixed and moving contact inside the RMUs properly, checking of spring changing mechanism, servicing and greasing all movable mechanism, replacement of defective fuse, wiring, spares and resembling and testing and service capability check from remote operation upto satisfaction complete all as per the direction of the Engr-in-Charge and the manufacture instruction.Note:-(i) The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of minor unserviceable parts with new parts .
M&L for opening the cover of VCBs/Bus coupler 11 KV ,630 Amp and servicing of fixed and moving contacts, repair and replacement of fixed copper terminal/contact (Male/Female), insulation tubes including other connected items to functional of pannel board, lamp indicators, meters triping coil etc.Cleaning the fixed and moving contact inside the VCB properly, checking of spring changing mechanism, servicing and greasing all movable mechanism, replacement of defective fuse, wiring, spares and resembling and testing and service capability check from remote operation upto satisfaction complete all as per the direction of the Engr-in-Charge and the manufacture instruction. Note:-(i) The quoted rate of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts . The new replaced parts shall be measured and paid separately under appropriate item of Sch 'A' (ii) For Sl No 40 to 57 : The make of spare parts, vaccum interrupter, switches, LED indicators should be of existing make of VCB's installed at Main Recieving Station.
Supply only spring charging motor & gear assembly 110V AC/DC complete all as specified and as directed.
Supply only push button bracket assembly complete all as specified and as directed.
Supply only gear assembly with motor shaft ,11 KV breakercomplete all as specified and as directed.
Supply only closing coil assembly 24 Volt complete all as specified and as directed.
Supply only tripping coil assembly, 24 volt complete all as directed.
Supply only closing coil assembly, 110 Volt complete all as directed.
Supply only tripping coil assembly, 110 volt complete all as directed.
Supply only TNC Switch complete all as directed.
Supply only lower connector complete all as directed.
Supply only isolating contacts complete all as directed.
Supply only auxiliary switch (7 NO + 7NC) model 33 PO24 complete all as directed.
Supply only vacuum interputer for HT11 KV VCBs, 630 Amps, type- B-21-M4 (M-500), breaking capacity 13.1 KA complete all as specified and as directed.
Supply only Indicating lamps LED,24V,2 Watt with holder, any type ( Red/ Green/ White/ Amber /blue)
Supply only phase indicating lamps 110V AC with holder (Red/ Yellow / Blue) complete all as directed.
Supply only push button actuator 1 No element, 22.5mm dia (TCH) complete all as directed.
Supply only thermostat range 30-90 deg Celsius complete all as directed.
Supply and fixing Heater 230 volts AC 60 watt for 11 KV HT VCB complete all as specifed and as directed. Make :Heatco/Vileco Electrical. complete all as specified and as directed.
Supply only High insulating varnish of superior quality ISI Marked complete all as directed.
M&L for servicing/testing /callibration of HT 11 KV relays ensuring of breaker tripping through relay by simulation CDG CDD completed for one VCB panel such as Mster trip relay,auxilary relay etc complete all as specified and as per WBSEB setting parameters as directed by Engr-in-Charge
M & L for repair of HT 11 KV vaccum circuit breaker complete set including replacement of complete internal AC/DC circuit wiring with existing size of wire, internal and external painting as per exsting colour, reinsulation of HT busbar and calibration of relays and tripping mechanism and installation of VCB with existing system after coupling with VCB panel by suitable size copper busbar and testing complete all as specified and as directed.
M & L for paint of HT VCB 11 KV Panel consisting of 14 Nos VCB at common busbar with two coats of hammer tone paint after preparation of existing surface without damaging any part of VCB complete all as specified and as directed.
Supply and fixing high speed master trip relay (3 element) of operating limits 50 to 120% if rated coil voltage, operational time 10-15ms normal rated voltage, coil rating 24V/30V/110V/220V DC or AC, burden @ 30VDC/24VDC:7VA, 110 VDC : 10 Va, 220 VDC:7 VA, mechanical flag (red to alarm and white for normal) in window HR type operational indicator 3No+1NC contacts, as per IS 3232-1981 including setting of relay and testing complete all as specifed and as directed. Make : Ashida Type : AVAJH33 /Crompton Greaves/Areva.
M&L for Earthing complete with Copper earth plate electrode 600x600x3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to Copper earth strip 20x3 mm by means of bolts, nuts, check nuts and washers of brass/copper all as shown in electrical plate No 3 of SSR part-I 2009 connected to lightening conductor all as specified and testing on completion including. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20mm dia GI pipe medium grade, funnel with wire mesh and lugs and GI pipe 40 mm dia of light grade, for protection of earth strip complete all as specified and directed. Note: Excavation/PCC/Earth work/Charcoal/ Salt shall be deemed to be include in this unit rate. complete all as specified and as directed
M&L for Earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to GI earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of brass/copper all as shown in electrical plate No 3 of SSR part-I 2009 connected to lightening conductor all as specified and testing on completion including. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20mm dia GI pipe medium grade, funnel with wire mesh and lugs and GI pipe 40 mm dia of light grade, for protection of earth strip complete all as specified and directed. Note: Excavation/PCC/Earth work/Charcoal/ Salt shall be deemed to be include in this unit rate.complete all as specified and as directed.
M&L inreplacement for GI pipe 40 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.Make: Tata/Jindal/Bansal complete all as specified and as directed.
Supply and fixing aluminium strip of size 25x3.15 mm for earth continuity conductor fixed on PCC block complete all as specified and as directed.
Supply and fixing Copper strip of size 20x3.15 mm for earth continuity conductor fixed on PCC block complete all as specified as directed.
Dismantling of existing unsv loose/disturbed Aluminum strip/GI Strip/Termination rod of any sizes on roof/down conductor fixed on wooden guities /directly on roof including screws etc complete all as specified and as directed.
Supply & fixing in repairs for 32 x 6 mm galvanised iron strip,earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or burried in ground or fixed to poles or roof with saddel and screw current complete all as specified and directed.
Supply and fixing porcelain insulator of size 65x31 mm and height 30mm with three nos hole including GI bolts and nuts of required size and two nos washer on incl PCC block, fixing strip complete all as specified and as directed.
Supply and fixing air termination single pointed aluminium rod 12mm dia and 300 mm dia complete all as specified and as directed.
M&L for taking out old unserviceable cable of any size from trenches , GI pipe protection, with and including separating serviceable bricks & set aside and removing un-serviceable bricks from site complete all as specified and as directed. ( Note : (i) The Excavation and earth work shall be mesured and paid separately under relevant item of Sch). complete all as specified and as directed.
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11/6.35 KV grade suitable for earthed system cross sectional area 120 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as specified & as directed . Make: Havells/Plaza/Polycab/KEI/Universal/Glue Star. complete all as specified and as directed.
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bended galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11/6.35 KV grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as specified & as directed. Make: Havells/Plaza/Polycab/KEI/Universal/Glue Star. complete all as specified and as directed
Relaying only cable of sizes 70-185sq mm 3 core retreived from item No- 71 , after rectifing defects complete as specified and as directed. NOTE: (i) Earth work & Excavation, GI pipe brick protection etc shall be measured and paid separately under relevant items of this schedule.l complete all as specified and as directed.
Excavation in trenches in soft/loose soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for taking up / laying under ground electric cable/errection of pole complete all as specified and as directed.
Returning, filling in, including spreading levelling watering and well rammming in layers not exceeding 25 cms in depth complete all as specified and as directed.
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and as directed.
Laying only serviceable bricks obtained from item No 71 here in before complete all as specified and as directed.
Supply and lay dry river sand filling for under ground cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed.
Supplying and Laying Reinforced Precast Concrete Cable Cover, class HVP, type – 1, flat size 300 mm x 180 mm x 40 mm complete all as specified and as directed
M&L 100 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.Make: Tata/Jindal/Bansal complete all as specified and as directed
M & L for horizontal boring across the existing road without disturbing the road surface for inserting 100 mm bore GI pipe all complete all as specified and as directed. ( Note :- GI pipe will be measured and paid respective item of sch'A'). complete all as specified and as directed
Supply and installtion (above ground) including testing HT joint box 2 way outdoor type of size 1500 x 1000 x 900 mm (overall) made out of 3.15 mm thick CRCA sheet with support of angle iron frame of size 40 x 40 x 6 mm with KIOSK BOX and comprising of 03 Nos HT porcelain bushing and copper round bus bar 12 mm dia rigidly mounted on bakelite sheet 12 mm thick to support insulators of suitable size and shape including providing necessary electric connection and applied two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces (internally & externally) including PCC foundation base of size 1700 mm x 400 mm x 1400 mm height (700 mm above GL & 500 mm below GL) with PCC 1:3:6 type C1 usisng 20 mm graded aggregate complete including necessary excavation and earth work for foundation and necessary electric connection complete and including dismantling of unserviceable joint box complete all as specified and as directed by Engineer-in-Charge. complete all as specified and as directed
Supply and installtion (above ground) including testing HT joint box 3 way outdoor type of size 1700 x 1200 x 1000 mm (overall) made out of 3.15 mm thick CRCA sheet with support of angle iron frame of size 40 x 40 x 6 mm with KIOSK BOX and comprising of 03 Nos HT porcelain bushing and copper round bus bar 12 mm dia rigidly mounted on bakelite sheet 12 mm thick to support insulators of suitable size and shape including providing necessary electric connection and applied two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces (internally & externally) including PCC foundation base of size 1700 mm x 400 mm x 1400 mm height (700 mm above GL & 500 mm below GL) with PCC 1:3:6 type C1 usisng 20 mm graded aggregate complete including necessary excavation and earth work for foundation and necessary electric connection complete and including dismantling of unserviceable joint box complete all as specified and as directed by Engineer-in-Charge.. complete all as specified and as directed
M & L repairs to 66 KV SF-6 Breaker Switch auto charging electical system by replacing damaged spares,suitable for Outdoor SF6 Circuit Braker type 70-SFM-32B, 72.5 KV rated Amps 1250 A, Make : Crompton Greaves NOTE : Replacement of unserviceable spares/accessories shall be measured & paid separately under relevant items of this Schedule ‘A complete all as specified and as directed.
Supply and fixing Closing coil 110 volts DC, 52C for 66 KV SF-6 circuit breaker for remote/manual operation complete all as specifed and as directed. Make: Kirloskar/CG.
Supply and fixing trip coil 110 volts DC, 52 T1 T2 for 66 KV SF-6 circuit breaker for remote/manual operation complete all as specifed and as directed. Make : Kirloskar/CG.
Supply and fixing Heater 230 volts AC 100 watt for 66 KV SF-6 circuit breaker for remote/manual operation complete all as specifed and as directed. Make :Heatco/Vileco Electrical.
M& L for filling of Gas in SF-6 Circuit breaker 66 KV/RMU upto required levelcomplete all as specified and directed at site.
Supply and fixing Analogue Amp-meter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 15/30 Amp complete all as specified and as directed. Make: AE/Siemens/CG
Supply and fixing Analogue Amp-meter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 60/30 Amp complete all as specified and as directed. Make: AE/Siemens/CG
Supply and fixing Analogue Amp-meter CT operated of size 144 mm x 144mm, suitable for HV panel board 11000 V ranging 0 to 100/50 Amp complete all as specified and as directed. Make: AE/Siemens/CG
Supply and fixing Analogue Volt meter of size 144 mm x 144 mm, suitable for HV panel board 11000 V, ranging 0 to 15 KV (excluding PT) complete all as specified and as directed.Make: AE/Siemens/CG.
Supply and fixing replacement of dry type epoxy resin cost totaly enclosed Single Phase PT (Potential Transformer) 11000 /110 V range, 50 Hz, voltage factor 1.2/1.9, Burden-100 VA insulation level 12/28/75 KVas per IS-3156/1992.complete all as specified and as directed. Make: Instrans Engg & Mfg Pvt Ltd /Kirloskar/Crompton Greves.
Supply and replacement of Fuse Links of PT (Potential Transfoemer) 11000/110 V range with HRC fuse complete Make: Instrans Engg & Mfg Pvt Ltd /Kirloskar/Crompton Greves.
Supply and fixing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for potection of system having ratio of 100/50 : 5 A , Burden-15VA, class-I, insulation level 12/28/75 KV as per ISS-2705 and IEC-60044. complete all as specified. Make:Instrans Engg & Mfg Pvt Ltd/Areva(Alstom)/Crompton Greves.
Supply and fixing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for potection of system having ratio of 60/30 : 5 A ,Burden-10VA, Class-I insulation level 12/28/75 KVas per ISS-2705 and IEC-60044. complete all as specified. Make:Instrans Engg & Mfg Pvt Ltd/Areva(Alstom)/Crompton Greves.
Supply and fixing Epoxy resin cost totaly enclosed dual core type Current transfomer (CT) for potection of system having ratio of 150/75 : 5 A ,Burden-10 VA, Class-I insulation level 12/28/75 KVas per ISS-2705 and IEC-60044. complete all as specified. Make:Instrans Engg & Mfg Pvt Ltd/Areva(Alstom)/Crompton Greves.
Material & labour for straight through joints, outdoor, cold shrinkable type (Earthed) suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable with jointing materials and accessories complete including testing after jointing complete all as specified and as directed. Make: Denson .
Material & labour for straight through joints, outdoor, heat shrinkable type (Earthed) suitable for 3 core 120 Sqmm to 185 sq mm 11000 Volts grade XLPE cable with jointing materials and accessories complete including testing after jointing complete all as specified and as directed. Make: Denson
Material & labour outdoor cable end termination joint cold shrinkable type suitable for 3 core 120/185 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing.complete all as specified and as directed
Material & labour Indoor cable end termination joint heat shrinkable type suitable for 3 core 70/95 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing. complete all as specified and directed.
Material & labour outdoor cable end termination joint cold shrinkable type suitable for 3 core 120/185 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing. complete all as specified and directed.
Material & labour of Indoor cable end termination joint cold shrinkable type suitable for 3 core 120/185 Sqmm 11000 Volts grade XLPE cable complete including testing after jointing. complete all as specified and directed.
Material & labour of Indoor Red Polyethylene Heat Shrinkable Bus Bar Tubes/slives of thikness 3 mm suitable for 11000 Volts complete all as specified and as directed.
Material & labour of Indoor cable termination protection Boot make right angle connection for RMU of size 95 to 185 sqmm, heavy duty insulating barrier device ,provide phase to phase insulation to the power cable terminals suitable for 11000 volts grade XLPE cable complete all as specified and as directed.
M&L for Servicing to outdoor type Potential Transformer suitable 72.5 KV oil immersed including replacing of old transformer insulation oil and all gaskets,Painting the metallic part and providing greasing/lubrication to other jointing/rusting components, reconditioning electric connections complete all as specified and as directed.
M&L for Servicing to outdoor type Current Transformer suitable 72.5 KV oil immersed including replacing of old transformer insulation oil and all gaskets,Painting the metallic part and providing greasing/lubrication to other jointing/rusting components, reconditioning electric connections complete all as specified and as directed.
Supply and replacing of metallic clamps/connections inclusive of fixing accessories for 66 KV expansion joint connection between tubular bus to equipment insulators flexible conductor to equipment/insulators tabular bus to other tubular bus for vertical connection/horizontal extension or connection all as required complete all as specified and as directed. Make :- As per IS.
Supply, fixing and testing post top insulator in 3 series including necessary connection with 66 KV distribution system complete all as specified and as directed. Note : Each insulator of the 3 series shall be of 33 KV rating. Make :PACTIL/NATIONAL/CEC/ECE/ JAIPURIA. complete all as specified and as directed.
M & L for switch air break gang operated tripplle pole out door type with V type insulator drop out switch fuze unit on HT 11 KV 50 cycle AC suitable for current rating upto 200 amps mechanically operated mounted on insulators and frame with operating mechanism worked from ground level with and including locking arrangement and dismantling old one all as directed by Engr-in-charge Make PACTIL/NATIONAL/CEC/ECE/JAIPURIA
M & L for HT lightening arrester expulsion type complete with all fittings discharging capacity 65 KA 11000 volts grade including taking down old one.complete all as specified and as directed. Make :- Alstom/Oblum/Crompton Greaves
Supply and fixing HT rubber matting of superior quality ISI marked of size 2Mx1Mx19 mm thick complete all as specified and as directed.
M&L for preparation of the old decorated existing external steel surface of feeder HT JBs of any size and description in any position including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopponf required and applying two coats of Asian aspa paint (Mahindra Grade) by using spray painting machine on old prepared surface including marking of Feeder No and feeding area with applying synthetic enamel paint (1st grade) complete all as specified.
Material and labour for applying two coats of aluminium paint to GI structure of dirrerent size channel/angle/flat strip/pipe/Busbar etc at 66 KV distribution structure after preparation of existing surface complete all as specified and directed
Material and labour for applying two coats of aluminium paint to steel tubular HT pole 9.0 mtr long including cross arms after preparation of existing surface complete all as specified and directed.
Material and labour for applying two coats of aluminium paint to steel tubular HT pole 11 mtr long including cross arms after preparation of existing surface complete all as specified and directed
Material and labour for applying two coats of aluminium paint to steel tubular HT pole 16 mtr long including cross arms after preparation of existing surface complete all as specified and directed.
S & F wall mounted flex sign board size not less than 2 x1 x.15 mtr made out of high quality GI sheet thickness not less lthan 2 mm and suitable size of Aluminium bedding with flex for marking of schematic diagram of external electric supply scheme/Name of sub station with suitable fixing arrangement as directed by Engr-in-Charge and incl 4 x 18W batten type LED fitting and wiring inside the board with suitable size of cables and the board fixed on wall with suitable size of cables and the board fixed onwall with suitable size of GI nut bolts,clamps, complete including taking down old existing, all as specified and directed by Engr-in-Charge.
M&L for one run of 1.5 Sqmm 3 Core (Nominal Area) PVC Sheathed multi stranded unarmed copper conductor cable LT 1100 volt grade Conforming to IS 7098 FRLS (inner sheet) in existing position from pole junction box to light fitting all complete as specified and directed. Make : Plaza/MESCAB/Polycab/HAVELLS
S&F in replacement of low density polyethylene (LDPE) pipes of pressure rating 16 kg/cm2 of 20 mm bore complete with connected accessories including dismantling of old unserviceable any size and type pipe complete all as specified and directed.
Supply & Fixing of LED type single dome aviation obstruction light complete with all connected accessories including dismantling of old unserviceable light from 16mtr pole any type complete all as specified and directed.Bajaj or equivalent make of Philips/Havells ..
M&L for LED decorative gate light made up of high grade unbreakable polycarbonate material suitable for retrofit 10 W LED bulb with 22 B base including dismantling of old unserviceable light,complete all as specified & directed . Cat No LHFHASE1TL4K015 (Grace Big) of Havells or equivalent make of Philips/Bajaj.
M&L for PVC insulated unarmoured aluminium conductor cable 6 sq mm 2 core including dismantling of old unserviceable cable complete all as specified & directed
M&L GI pipe light grade 40 mm dia for med grade installation of light as per reqd size inscuding bends or other fitting reqd at site , welding works ,etc including dismantling of old unserviceable pipe complete all as specified & directed.
M&L for PVC conduit pipe heavy duty 25 mm dia incl exdcavation work for laying cable in conduit complete all as specified & directed..
M&L for PCC 1;3;6 of 20 mm graded type C1 aggregate complete all as speifiec & directed
M&L for precast cable route indicator of size 100x30x10 Cms by using 20 mm graded aggregate type B1 1;2;4 for cable indicator and engraving as "HT CABLE" slightly round from one side incl Red painting with two coat of synthetci enamel paint of a coat of primer complete all as specified & directed
M&L for Earth pit cover of size 54x54x50 mm made by 1;2;4 type B1 using 20 mm graded crushed stone aggregate reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with mild steel handle 12 mm dia in including white wash complete all as specified and directed.
Material and labour for earthing result testing for any type of earthing such as GI plate/copper plate/chemical/bore earthing connected with and for HT panel , LT panel,Equipments, Lightening arrestor, DG sets,Transformer etc in any position and any place under GE (N) Binnaguri Mil station using Digital Earth meter in 3M method and E-N voltage at main DBs and register the result as per performa provided in earth test register duly signed by JE and Engr in charge complete all as specified and directed by Engr-in charge
Cutting unaxious green growth and wild grass by manual labour or by machine at Electrical Installation Permises around pole, around panel board along boundaries fencing, removing runnish material from work site and depositing where directed not exc. 100 meter from the starting point complete all as directed. Note : The item shall be operated maximum 2 (Two) times in the entire period of the Contract period and measurement will be taken every time independently for payment.
KD SAHA and CO.INDIA
S.N. GHOSH AND CO.
CHAKRABORTY AND SONS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .