| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.4 LAccepted-Finance | ₹14.4 L | L1 | Accepted-Finance Quoted lowest Price |
| 2 | L2₹14.6 LRejected-Finance JAGAHARMURA AGARTALA TRIPURA W | AGARTALA | TRIPURA | ₹14.6 L | L2 | Rejected-Finance Quoted price is higher than L1 bidder |
| Sl No | Description | Qty | Unit | M/S GHOSH ELECTRICAL ENGINEERING L1 | Swapan Das L2 |
|---|---|---|---|---|---|
| 2.00SCHEDULE A : SUPPLY AND ERECTION | |||||
| 3.00 | Supply, loading, transportation, unloading, insurance, delivery at site, handling, storage of 3- Phase, 3-core, 6.35/11 KV, 95 sqmm, FRLS type, XLPE insulated, Armoured , Aluminium Conductor Power Cable as per IS 7098/II/1985 with upto date amendments. | 0.34 | Km | 11,90,000 ₹4,84,449 Lowest | 14,00,000 ₹5,69,940 |
| 4.00 | Supply, loading, transportation, unloading, insurance, delivery at site, handling, storage of HDPE Pipe, PE - 100 Grade, PN 8 (SDR 17) , 110 mm Outer Dia, Wall thickness : minimum- 6.5 mm, maximum: 7.3 mm. | 315 | m | 650 ₹2,41,605 | 350 ₹1,30,095 Lowest |
| 5.00 | Supply of GI Strip 50x6 mm for DTR earthing | 35 | m | 150 ₹6,195 | 100 ₹4,130 Lowest |
| 6.00 | Supply of Centrifugal Cast iron Earthing Electrode 50mm Diameter, 3.5 mm Thickness with clamp ( 32x6 mm) and furne with long GI nuts & bolts in middle, perforated holes,trapper and cuts. | 5 | No. | 2,000 ₹11,800 Lowest | 2,500 ₹14,750 |
| 7.00 | Supply of 25 KG Bag of Earth enhancing compound / Back fill compound. | 5 | No. | 500 ₹2,950 Lowest | 3,000 ₹17,700 |
| 8.00 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering-
Above 95 sq. mm up to 185sqmm. | 30 | m | 400 ₹14,160 | 200 ₹7,080 Lowest |
| 9.00 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Trench Size: Width-350mm, Hieght-1200mm Sand(couhioning): Hieght-250mm, Width-350mm/ Protection: Double layer Bricks. Upto 120 sq. mm | 6.66 | m | 650 ₹5,108.22 | 300 ₹2,357.64 Lowest |
| 10.00 | Laying of 11 KV ,XLPE insulated power cable of size 3C X 95 sqmm by manually digging /machine driIIing horizontally or diagonally direction for road crossing / Water supply line/Telcomunication line/Gas Pipe line etc. including Laying of 64 to 200mm dia GI pipe direct into the earth at a depth of minimum 1100 mm below the ground surface with out effecting the existing road including excavation earth for entry pit as per site condition and direction of Engineering In Charge. | 315 | m | 750 ₹2,78,775 | 550 ₹2,04,435 Lowest |
| 11.00 | Coiling of excess Single/3core/3.5 Core, upto to 400sqmm, HV/MV, XLPE insulated, armoured power Cable direct into earth including excavation of earth upto a depth of 1500mm (Size pit should be 2250mmX2250mm or as per site requirement.) including 1st class brick protection of two layer flat brick soling , 300 mm. Fine sand (Local quary) for cushioning/bed and refilling and ramming the excavated soil as per direction of Engineer in charge. | 4 | No. | 1,000 ₹4,720 Lowest | 1,000 ₹4,720 Lowest |
Tender Value
₹14.1 L
EMD Value
₹28,213
Closing Date
19 May 2026, 5:00 pmClosed
DGM,ED-I,Banamalipur,TSECL
O/O The DGM,ED-I,Banamalipur,TSECL
Extension of HT line by 3 core 6.35/11 KV 95 sqmm XLPE insulated Power Cable and installation of 1X200 KVA 11/0.433 KV Sub-station for facilitating service connections to Residential cum Commercial building Motorstand under ESD-I Banamalipur
2026_POWER_72245_1
DGM/ED-I/TSECL/2026-27/03
Open Tender
Electrical Works
Works
Agartala West Tripura
Please refer Tender documents.
8 documents required · 8 mandatory
₹5,000
₹28,213
O/O The AGM,EC-I,TSECL,Agartala
16 Jul 2026
29 Apr 2026
20 May 2026
29 Apr 2026
19 May 2026
12 May 2026
30 Apr 2026 - 5 May 2026
7 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | GST % |
|---|---|---|---|---|---|---|
| 2 | SCHEDULE A : SUPPLY AND ERECTION | - | - | - | - | - |
| 3 | Supply, loading, transportation, unloading, insurance, delivery at site, handling, storage of 3- Phase, 3-core, 6.35/11 KV, 95 sqmm, FRLS type, XLPE insulated, Armoured , Aluminium Conductor Power Cable as per IS 7098/II/1985 with upto date amendments. | 1 | Km | - | - | 0.18% |
| 4 | Supply, loading, transportation, unloading, insurance, delivery at site, handling, storage of HDPE Pipe, PE - 100 Grade, PN 8 (SDR 17) , 110 mm Outer Dia, Wall thickness : minimum- 6.5 mm, maximum: 7.3 mm. | 315 | m | - | - | 0.18% |
| 5 | Supply of GI Strip 50x6 mm for DTR earthing | 35 | m | - | - | 0.18% |
| 6 | Supply of Centrifugal Cast iron Earthing Electrode 50mm Diameter, 3.5 mm Thickness with clamp ( 32x6 mm) and furne with long GI nuts & bolts in middle, perforated holes,trapper and cuts. | 5 | No. | - | - | 0.18% |
| 7 | Supply of 25 KG Bag of Earth enhancing compound / Back fill compound. | 5 | No. | - | - | 0.18% |
| 8 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering-
Above 95 sq. mm up to 185sqmm. | 30 | m | - | - | 0.18% |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Trench Size: Width-350mm, Hieght-1200mm Sand(couhioning): Hieght-250mm, Width-350mm/ Protection: Double layer Bricks. Upto 120 sq. mm | 6.66 | m | - | - | 0.18% |
| 10 | Laying of 11 KV ,XLPE insulated power cable of size 3C X 95 sqmm by manually digging /machine driIIing horizontally or diagonally direction for road crossing / Water supply line/Telcomunication line/Gas Pipe line etc. including Laying of 64 to 200mm dia GI pipe direct into the earth at a depth of minimum 1100 mm below the ground surface with out effecting the existing road including excavation earth for entry pit as per site condition and direction of Engineering In Charge. | 315 | m | - | - | 0.18% |
| 11 | Coiling of excess Single/3core/3.5 Core, upto to 400sqmm, HV/MV, XLPE insulated, armoured power Cable direct into earth including excavation of earth upto a depth of 1500mm (Size pit should be 2250mmX2250mm or as per site requirement.) including 1st class brick protection of two layer flat brick soling , 300 mm. Fine sand (Local quary) for cushioning/bed and refilling and ramming the excavated soil as per direction of Engineer in charge. | 4 | No. | - | - | 0.18% |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.44 MB
Tendernotice_2.pdf
PDF • 1.41 MB
BOQ_73527.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].