Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.9 LAccepted-AOC | L1 | Accepted-AOC Lowest Tenderer | |
| 2 | L2₹4.0 L+₹13,655 (3.53%)Rejected-Finance | L2 | Rejected-Finance Higher Bid |
Tender Value
Refer Docs
Closing Date
13 Sept 2021, 6:00 pmClosed
EE(E) Dharamshala
HPO Complex, BSNL CSC Building, Dharamshala-HP
Providing Electrical Installation in Conference hall of Regional Health and Family Welfare Training Centre at Chheb Kangra HP
2021_BSNL_86747_1
03/EE/E/BSNL/ED/DMA/2021-22
Open Tender
Electrical Works
Item Rate
30 days
Kangra
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
AO(Claim), O/o CGMT HP Circle Shimla
Exempted
31 Jan 2022
1 Sept 2021
16 Sept 2021
1 Sept 2021
13 Sept 2021
1 Sept 2021
1 Sept 2021 - 13 Sept 2021
Amount
SUB HEAD-I (Wiring)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group- C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
4 X 1.5 sq. mm + 2 X 1.5 sq. mm earth wire
4 X 6 sq. mm + 2 X 6sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2x1.5sqmm
3x1.5sqmm
4x1.5sqmm
5x1.5sqmm
6x1.5sqmm
3x4sqmm
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
6 Module (200mm X 75mm)
8 Module (125mmX125mm)
12 Module (200mmX150mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 amps switch
15/16 A switch
3 pin 5/6 amp socket outlet
6 pin 15/16 amp socket outlet
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.
1 run of cable
2 run of cable
3 run of cable
Supplying and fixing of 25mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing of 25 mm sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
SUB HEAD-II (Distribution Boards & MCBs)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way (8 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole.
63 amps, 415 volts Four pole.
Supplying and fixing 63amp rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Sub Head-III ( Fans & Fitings)
SITC of following type prewired surface / recess mounted (minimum colour code 840) LED light fixture & integrated electronic driver including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
1200mm x 300mm (Nominal dimension) Metallic CRCA Powder Coated Housing High efficiency Diffuser Cover with accessories as required Recess Type LED of nominal wattage 40W ± 15% (Philips) or SS Make)
600mm x 600mm (Nominal dimension) Recess Type Metallic CRCA Powder Coated Housing High efficiency Diffuser Cover with accessories as required ( (Philips) or SS Make)
a) 6" (Minimum Dia.) recess Type LED ) Round Panel of nominal wattage 15W ± 15% (Philips)or SS Make)
SITC of 400 mm sweep wall fan i/c fixing the same on wall complete all as required at site.
SUB HEAD-IV (Misc Items )
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
Supplying & laying speaker cable Single pair, 2-core, 1.5 sqmm compleye as reqd
KUMAR ELECTRIC
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .