Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹7.0 LAccepted-AOC EDAYUR PO VALANCHERY MALAPPURAM | MALAPPURAM | KERALA | 676552 | ₹7.0 L | 1 | Accepted-AOC AEE/LIDEW-DIV/MPM/141/24-25 |
| 2 | 2₹7.0 L+₹344 (0.05%)Rejected-Finance COMET ELECTRICAL ENGINEERING CO KOTTAKKAL MALAPPURAM | ₹7.0 L+₹344 (0.05%) | 2 | Rejected-Finance L2 |
| 3 | Rejected-Technical PALAJIKA VALLUHER VEEDU KOSHTAN ALAKKAD NANNAMUKKU 679591 | MALAPPURAM | MALAPPURAM | KERALA | 679591 | - | - | Rejected-Technical L3 |
Tender Value
₹8.3 L
EMD Value
₹20,731
Closing Date
10 Dec 2024, 6:55 pmClosed
ASSISTANT EXECUTIVE ENGIEER
Office of the Executive Engineer, LID and EW Division, Malappuram, civil station, Malappuram District Panchayath Building, Malappuram, 676505
Annual Plan- Malappuram DistrictPanchayath Electrification works for Kuttippuram GHS for IT Lab Smart class room and Toilet block at Kuttippuram-S0112/25-General Electrical Work
2024_LSGD_711920_1
DB1/TN/ELE/AEE/17/24-25
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
CIVIL STATION MALAPPURAM
Please refer Tender documents.
11 documents required · 11 mandatory
₹2,006
₹20,731
Yes
5 Feb 2025
3 Dec 2024
12 Dec 2024
3 Dec 2024
10 Dec 2024
3 Dec 2024
Amount
Electrical
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.7:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
1.14.3:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.14.8:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 4 sq. mm + 2 X 4 sq. mm earth wire
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.3.20.4:Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 2X20W LED Lamp with box type fixture
OD273777/2024-2025:Supply Conveyance, installation, testing and commissioning of 30 W LED Flood light with IP 65 protection LED Chip make acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use
OD273943/2024-2025:upply Conveyance, installation, testing and commissioning of 100 W LED Flood light with IP 65 protection LED Chip e with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenanc including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire etc as required.
OD273770/2024-2025:Supply and fixing 12W LED bulk head fitting heat resistant prismatic glass cover to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required.
OD273775/2024-2025:Supply, installation testing and commissioning exhaust fan of size 150 mm sweep Light duty in plastic body with self opening lowers in the existing opening or making hole , fixing necessary anchor bolts/bolt and nut neatly plastered in the existing exhaust fan hole, making good the damages, color washing etc as required and giving connection with required length of 4/0.20mm PVC insulted and PVC Sheathed 650/1100V grade 3 core round copper conductor flexible wire
OD275719/2024-2025:Supply, installation testing and commissioning exhaust fan of size 225 mm sweep Light duty in metal body in the existing opening or making hole , fixing necessary anchor bolts/bolt and nut neatly plastered in the existing exhaust fan hole, making good the damages, color washing etc as required and giving connection with required length of PVC insulted and PVC Sheathed 650/1100V grade 3 core round copper conductor flexible wire etc as reuired at site
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
90.5.1.8:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Gong bell 150mm-without MS box
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.2:Supply and installation of suitable size MS belt type fan clamp fabricated from flat iron 40 x 6 mm, 150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD273782/2024-2025:Supply, Conveyance, installation, testing and commissioning of 400mm sweep High speed wall mounting fan with metallic blades, blade covers,body,mounting brackets etc with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS (Havells Girik Neo 400 mm, Orient Tornado Wall II Black 450 mm, atomberg Renesa 400mm BLDC with remot, Crompton torpedo High Speed or equivalent make)
OD273780/2024-2025:Supply and fixing Recess mounted 12 W or nearest LED down lighter ABS plastic with diffuser luminaire LED light source Operating temperature: -0&deg; C to +40&deg; C Operating voltage range: 100-300 V cosumption 12W +_5 , power factor 0.95, rated (Havells/Phillips/Bajaj/Osram/K Lite/Lucker/Dewton or similler make) on false ceiling and giving connection etc as required .
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
OD275731/2024-2025:Supplying and fixing 9 W LED Bulb including connection etc. as required
1.31:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.56:Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
90.10.1.4:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )4 module moulded plastic box on surface
90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.4:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.7:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.7 x 1.5 sq. mm
1.17.8:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.8 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.20:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
90.14.10.1:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 3 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.12.2:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.3:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD273783/2024-2025:Supplying and fixing following rating, Triple pole, 415 volts, MCB in the existing Panel. complete with connections, testing and commissioning etc. as required. 63A TP MCB
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD273771/2024-2025:Supplying and Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate
OD273778/2024-2025:Supply, providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD273774/2024-2025:Supply and providing 25x6mm brass nut and bolt etc. as required.
OD273781/2024-2025:12x3mm brass nut and bolt Supply and providing 12x3mm brass nut and bolt etc. as required.
90.12.5.3:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 10 sq mm
90.12.7.3:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 10 sq mm with factory made clamp
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
90.4.3:Conveyance installation testing and commissioning ceiling fan of all sizes using standard accessories excluding resistance type regulator wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or extending the original wiring etc. as required.
1.59:Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins reinstalling the same as required.
OD273784/2024-2025:Dismantling the existing EI with switch boards, plug boards all fitting DB MB etc complete with out damages to wall and making good the damages colour wasing etc as required and handed over to occupancy with reciepts.
OD275913/2024-2025:Supply, conveyance, installation ,testing and commissining of Rating 7.5KVA Phase Single Phase in - Single phase Output Type Online Backup Time 3 Hr Battery Type Tubular Battery Input Input Voltage Range 230V AC SINGLE PHASE &N Input Frequency Range(Hz) 45-55Hz. Power Factor >0.85 Input THD <5% Output Voltage 230 VAC SINGLE PHASE P-N Voltage Regulation +/-1% Frequency(Synchronized Range) 50 Hz+/-0.1 Hz. Output Waveform Pure sine wave Crest Factor 3:1 Efficiency 85% Power Factor 0.8 Overloadcapacity 110% for 1Minute,120%for 30 SEC Transfer Time(MainstoBattery) 0 ms THD <5% IsolationTransformer Inbuilt Galvanic Isolation Transformer Bypass MANUAL LCD Display Output voltage,Output current,Output requency,InputVoltage,Bat Protection Automatic discharge protection with self test Features, Over Load, Surge protection, Input fault, Cold start, Low Battery, Battery over charge Output short circuit, Charging Current Circuit Inverter over temperature ISO Certification ISO9001:2008&ISO14001:2004 Certifications BIS,OHSAS,ROHS and CE 7.5KVA TRUE ONLINE UPS SINGLE PHASE ,WITH INBUILT ISOLATION TRANSFORMER WITH TUBULAR BATTERY FOR BACKUP 21600VAH ( UPS Model Hykon/Schneider Electric SE/ Mitsubishi Electric Corporation , Battery MODEL- 150AH TUBULAR BATTERY with rack ( EXIDE/HYKON/Amaron) etc as required at site
OD275914/2024-2025:Supply, conveyance Installation testing and commissioning of 3500va/ sine wave inverter/Home UPS with 7200VAH Battery backup Rating DSP based intelligent controlled 3.5kva Warranty 2years Phase Single Phase Type Inverter /ups Backup Time 7200 vah, Battery Type 12v Tubular Battery Input Input Voltage Range NORMAL -90-270 VAC ,UPS MODE- 195-260VAC Input Frequency Range(Hz) 50 Hz.+/- 5% Output Voltage 215V-5 to +1% Frequency(Synchronized Range) 50 Hz+/-0.5 Hz. Output Waveform Pure sine wave Protections OVER LOAD,SHORT CIRCUIT ,BATTERY LOW BATTERY 48VDC Charging current 0-10 A Type 12v TUBULAR BATTERY Battery warranty 3 years ( UPS Model Hykon/Schneider Electric SE/ Mitsubishi Electric Corporation , Battery MODEL- 150AH TUBULAR BATTERY with rack ( EXIDE/HYKON/Amaron) etc as required at site
OD276216/2024-2025:Supply, threading ,laying and jointing of the 32 mm "B' class GI pipe with all required accessories in ground in he existing trench as protective covering to UG Cable
ANSARI KUNDIL (BID ID -2011969)
Rafeeq P V (BID ID -2012516)
Bidder Name
ANSARI KUNDIL
Rafeeq P V
MOIDEENKUTTY KOLAMBAN
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1119674.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .