Expenditure
Capital (Works)
SRDEEG/SEE
16 conditions · 5 needing a document upload
Contractor should have to be registered with Employee ProvidentFundOrganization (EPFO). It is mandatory for contractor to submit PFcodeprovided by EPFO with their tender offer. Also each contractor hastosubmit "UAN" of their worker with their offer and have to mentionintender document. It is mandatory. Otherwise offer will not beconsideredfor further action and your offer will summarily be rejected.
Financial Eligibility Criteria: The tenderer must have minimumaverageannual contractual turnover of 'V/N'or 'V' whichever is less;where V=Advertised value of the tender in crores of Rupees N= Numberof yearsprescribed for completion of work for which bids have beeninvited. Theaverage annual contractual turnover shall be calculated as anaverage of"total contractual payments" in the previous three financialyears, as perthe audited balance sheet. However, in case balance sheetof theprevious year is yet to be prepared/ audited, the audited balancesheetof the fourth previous year shall be considered for calculatingaverageannual contractual turnover. The tenderers shall submitrequisiteinformation as per Annexure-VIB, along with copies of AuditedBalanceSheets duly certified by the Chartered Accountant/ CertificatefromChartered Accountant duly supported by Audited Balance Sheet.
As per CE/Works/HJP's letter no. ECR- HQ0ENGG(CONT)/0009/2025,dated18.11.2025 "The balance sheet and all other financialdocumentsattested/certified by the Chartered Accountant (CA) tosubstantiatefulfillment of Financial Eligibility Criteria should be withUDIN, failingwhich the offer shall be considered as incomplete and will besummarilyrejected without any further reference."
The tenderer shall posses the valid Electrical Contractor's licenseandSupervisory License issued by any State/Central Govt. licensingboard forthe required voltage level or above with their tender paper.Tenderswithout valid electrical contractor's license & Supervisory licensewillsummarily be rejected.
"ELIGIBILITY CRITERIA:- Document required to be submitted in support of Technical Eligibility Criteria: Tenderer should have completed at least one similar single work. The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, or One similar work costing not less than the amount equal to 60% of advertised value of the tender. Similar nature of works (as defined and approved by competent authority) for " (i) Electrical work in connection with provision of power supply in new constructed CNC pit wheel lathe at BJU. (ii) At CSR:- Electrical work in connection with augmentation of Intermediate Overhauling (IOH) and Periodic Overhauling (POH) facilities for track machine." is (i) Erection of LT or above voltage level distribution panels. (ii) Erection and commissioning of LT or above voltage level line (over head or underground). (iii) Electrification/Rewiring service buildings, bungalow and quarters. (iv) Supply and erection of tower light. (v) Lighting of station/ Administrative building / circulating area."
17 conditions · 2 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The tenderers whether sole proprietor , a limited company or a partnership firm he/they should submit authentic proof in terms of partnership deed, proprietorship documents etc. along with the tender. If he/they want to act through agent or individual partners should submit a power of attorney duly stamped and authenticated by Notary Public or by Magistrate in favour of specific person whether he/she/they are partners of the firm or any other person specifically authorizing him/her name to submit the tender, sign the agreement , receive money, witness measurements, sign measurement books , compromise, settie, relinquish any claims, preferred by firm and also sign No Claim Certificate and refer all or any disputes arbitration.
Rates are inclusive of all taxes/GST, license fee, royalty charges etc. legally leviable by State, Central Govt. and/or any other local authority.
Railway Administration reserves the right to change/Alter/Cancel the tender without any notice.
(i) Electrical work in connection with provision of power supply in new constructed CNC pit wheel lathe at BJU. (ii) At CSR:- Electrical work in connection with augmentation of Intermediate Overhauling (IOH) and Periodic Overhauling (POH) facilities for track machine.
L-Open-26-27-17Dt24-09-26~ECR
L-Open-26-27-17Dt24-09-26
Open
Works - General
180 Days
Saran, Bihar
₹0
₹1.4 L
24 Sept 2026
24 Sept 2026
2 Oct 2026
70 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 58,37,117.78 | ||
| — | 2.00 | — | — | ||
| Making foundation of 500 KVA transformer with ramp as per site in-charge. | — | — | — | 27,888 | |
| — | 2.00 | — | — | ||
| Provision, Fabrication and commissioning of 11 KV 3 phase Gang Operated Switch on the top portion of pre-erected H- pole/4 pole structure capacity 400 Amp conforming to IS: 1818 complete with drop out fuse conforming to ISS-9835 (Pt.II) of 1980 along with mounting channel/angle iron insulator etc. all respect including supply of all required material. | — | — | — | 16,884 | |
| — | 2.00 | — | — | ||
| Erection and fabrication of H-pole structure exceeding 10 mtrs. but not exceeding 13 mtrs. with angle iron 50mm x 50mm x 6mm & 75mm x 40mm x 6mm channel nut bolt etc. Direct in ground including excavation refilling with cement concrete 1 : 3: 6 (Cement, Course sand, 40 mm graded stone nominal size) made foundation with foundation of size 2000 mm x 1000 mm x1000 mm depth and muffing of base foundation of 500 mm x 500 mm x 500 mm with cement concrete as per ration 1:3:6 above the ground level including transportation of rail pole from different location to the site. (only rail pole will be supplied by the railway). | — | — | — | 10,890 | |
| — | 400.00 | — | — | ||
| Supply & laying of 11 KV 3 core 50 mm² XLPE alluminium armoured cable on cable tray with suitable clamping arrangement. Make - Polycab, RR Cables, Havells, & KEI. | — | — | — | 2,63,600 | |
| — | 400.00 | — | — | ||
| Laying of cable depth of 3' partly under ground through suitable trench partly on wall, rail post through suitable clamp including Excavation of cable trench either in rock/soil/concrete and covering. | — | — | — | 42,204 | |
| — | 6.00 | — | — | ||
| Earthing with copper Plate earthing 600x600x3mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. | — | — | — | 75,732 | |
| — | 6.00 | — | — | ||
| Supply and making of heat shrinkable outdoor end termination Kit for 11 KV 'E' XLPE 3 core 16-50 mm² cable. Make -Mahindra, Yamuna Densons & Chemicals, Cabseal, Frontec, & Raychem. | — | — | — | 55,164 | |
| — | 6.00 | — | — | ||
| Earthing with perforated G.I. earth pipe 4.5 mtrs. Longx40mm dia with minimum 3.25mm thick including accessories and providing masonry enclosure on top with cover plate having locking arrangement and watering pipe including supply & using salt and charcoal for pipe earth electrode complete as per Genl. Spec. of elect. Work & drawing etc. as required. so that the earth resistance value should be within 2 Ohms. Make of GI pipe TATA/Jindal or equivalent superior make. | — | — | — | 10,352.58 | |
| — | 60.00 | — | — | ||
| Supply and laying 25mm X 5mm G.I. Strip at 0.5 metre below ground level/surface as strip earth electrode including jointing etc. as required. | — | — | — | 6,387 | |
| — | 995.00 | — | — | ||
| Supply & delivery of four core circular armored cross linked polyethylene XLPE (LT) insulated cable PVC outer sheathed armored with galvanized round steel wire or steel strip and with aluminums conductor suitable for rated voltage 1100 volts grade conforming to IS:7098 (Part-I)- 1988 with amdt. No. 1,2 and 3 (reaffirmed 2005) size - 4x400 sq.mm. The firms will have to submit type test report as per IS from NABL accredited lab along with the tender. Type test report should not be more than 10 years old on the date of bid opening. Make - RR KABEL, NATIONAL CABLES, HAVELL's, POLYCAB & KEI | — | — | — | 22,63,625 | |
| — | 500.00 | — | — | ||
| Supply & delivery of four core circular armored cross linked polyethylene XLPE (LT) insulated cable PVC outer sheathed armored with galvanized round steel wire or steel strip and with aluminums conductor suitable for rated voltage 1100 volts grade conforming to IS:7098 (Part-I)- 1988 with amdt. No. 1,2 and 3 (reaffirmed 2005) size - 4x120 sq.mm. The firms will have to submit type test report as per IS from NABL accredited lab along with the tender. Type test report should not be more than 10 years old on the date of bid opening. Make - RR KABEL, NATIONAL CABLES, HAVELL's, POLYCAB & KEI | — | — | — | 2,91,500 | |
| — | 500.00 | — | — | ||
| Supply & delivery of four core circular armored cross linked polyethylene XLPE (LT) insulated cable PVC outer sheathed armored with galvanized round steel wire or steel strip and with aluminums conductor suitable for rated voltage 1100 volts grade conforming to IS:7098 (Part-I)- 1988 with amdt. No. 1,2 and 3 (reaffirmed 2005) size - 4x50 sq.mm. The firms will have to submit type test report as per IS from NABL accredited lab along with the tender. Type test report should not be more than 10 years old on the date of bid opening. Make - RR KABEL, NATIONAL CABLES, HAVELL's, POLYCAB & KEI | — | — | — | 1,37,500 | |
| — | 1880.00 | — | — | ||
| Laying of the cable partly through trench at a depth of one meter and filling with suitable cushioning materials or under the road by laying through G.I pipe at a depth of one meter or at a platform /road/wall where excavation of one meter is not possible only cutting of the surface to the size of cable with at least two inch covering by concrete is required and refilling with earth and partly of the rail /lamp post/PF color /wall with supply of clamp made of MS flat 35x6 mm with nut - bolts adequate number with maximum space of one meter /wherever feasible etc. required . In case due to space constraints more than one cable is required to lay in one trench, payment will be released in form of length of trench and not in length of underground cable. | — | — | — | 2,01,799.2 | |
| — | 2.00 | — | — | ||
| Supply & fixing of bus bar chamber with 4 strips bus bar of length 300 mm made of copper strips suitable for 200 Amp. capacity complete with all accessories including connection, earthing the body complete etc. as reqd. Make - Standard/Havells/C&S. | — | — | — | 16,770 | |
| — | 2.00 | — | — | ||
| Supply fixing testing & commissioning of MCCB 200 Amp, Breaking capacity 35 KA, four pole (04), with thermal magnetic release with suitable MCCB enclosure. Fixing is to be done as per the site requirement under supervision of site in-charge including correction with crimping of the cable ends with aluminnium lugs of required sizes. Make- Siemens, ABB, Legrand , L&T, Schneider, C&S. | — | — | — | 46,010 | |
| — | 2.00 | — | — | ||
| "Supplying, installation, testing & commissioning of cubicle type LT panel suitable for 415V, 3 Phase, 4 Wire 50 Hz Ac supply system, fabricated with CRCA sheet steel of 1.6mm thick for frame work and co vers, 2mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, A 5 Set 812321.00 At Par 4061605.00 having suitable Amp capacity extensible type TPN bus bars of high conductivity, DMC/SMC bus bar supports. entire panel shall have a common copper earth bar of size 25mm x 5mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Copper bus bars i/c providing following switch gears Incomer - 800A, Four Pole ACB, (Breaking capacity: Icw = Ics = Icu = 50 kA for 1 sec), MDO with MTX 1.5G, having Overload, Short -circuit & instantaneous protection with adjustable current & time delay settings, In-built neutral & earth fault protection, current metering through O-LED display, local fault annunciation through LED indication & pre-trip alarm - 1 No, 3 Phase LED Voltmeter, Cl 1 (50 - 520 Vac) - 1 Nos 3 Phase LED Ammeter, Cl 1 - 1 Nos. CT Class 1 (800/5) - 3 Nos Voltmeter Selector Switch(VSS) - 1 No, Ammeter Selector Switch (A SS) - 1 No , RYB LED indicating Lamp - 1 Set On-off Indicating lamp - 1 Set 2A, 10 kA SP MCB for Protection - 4 Nos TPN Copper bus bars of minimum of 800Amps capacity 800A, 4Pole On-load Changeover switch (Manual)- 01 No Outgoing: 1) MCCB: 400A 4Pole, (TM), 36kA breaking capacity (Ics=100% Icu), with with factory made Silver plated Copper spreading links & Rotary handle - 3 Nos. 2) MCCB: 250A 4Pole,(TM), 25kA breaking capacit y (Ics=100% Icu), with with factory made Silver plated Copper spreading links & Rotary handle - 1 No 3) MCCB: 200A 4Pole, (TM), 25kA breaking capacity (Ics=100% Icu), with with factory made Silver plated Copper spreading links & Rotary handle - 3 Nos. 4) MCCB: 100A 4Pole, (TM), 25kA breaking capacity (Ics=100% Icu), with with factory made Silver plated Copper spreading links & Rotary handle - 6 Nos. All MCCBs should ha ve variable thermal setting of 80-100% for overload protection. Make of all switchgear items L&T, Havells, ABB, Schneider, Siemens, C&S. | — | — | — | 15,07,506 | |
| — | 1.00 | — | — | ||
| Supply, Installation, Testing and Commissioning of 12.5 Mt. Hot dip Galvanized suitable for wind velocity of 44 M/Sec as per IS 875 Part 3 1987 latest version High Mast system along with head frame, steel wire rope, double drum winch , galvanized lantern carriage suitable for 6 luminaries & its CG boxes & lightning finial, integral type high powered reversible power tool for raising and lowering of lantern carriage, gear box coupled with the winch & torque limiter , foundation bolt of special steel with nuts washers, anchor plates , templates , LED beam flood light luminaries 200 W , shallow foundation considering the . Double drum/350 Kg winch having gear 53:1 , oil bath (SAE90/140) arrangement . (4) 02 nos. stainless steel wire ropes 5 mm dia (7/19) breaking load capacity 1450 kg x 2 Integral power tool 3- phase , 0.75 HP 2mm/min single speed winch, galvanized antern carnage suitable for B luminaries & its CG boxes & Sighting finiat integral type high powered red reversible reveres power tool for raising and lowering of lantern carriage, gear box coupled with the winch & torque miter foundations bolt of special steel with ruts washers, anchor plates, templates, LED beam fought luminaries 200 W, shallow Foundation considering the safe soil bearing capacity at site as 10 T/Sq Mtr at 2 mtr depth , twin dome aviation obstruction light heavy gauge hot Dipped galvanized lighting finals, Feeder Panel comprising main Incoming switch MCB', time switch, contactor reversing starter and protective system etc . as required and maintenance free Earthing etc. Make-Bajaj, Transrail, Phillips, Crompton, Surya & Valmount. | — | — | — | 2,29,205 | |
| — | 1.00 | — | — | ||
| Provision of panel room of size 15 FtX12 Ft = 16.72 Sq. Mtrs. | — | — | — | 5,28,161 | |
| — | 5.00 | — | — | ||
| Supply, delivery & Fixing of octagonal pole hot Dip Galvanized in single dip average 70 micron DFT, designed for maximum wind speed of 169KM/Hr.,BOP-7030 type pole of 6 m long, top dia 70mm, bottom dia. 130mm sheet thickness 3mm, in single section with Base plate (220x220x12)mm (LxBxT) with 4x20mm dia. 700mm long with 100mm projection foundation bolt complete with smart pack junction box with bakelite sheet, 6A MCB & stud terminals (for mounting inside base component of pole) and internal wiring for terminal to fitting with 2x2.5 sq.mm cable including single arm 1 mtr. long suitable for 3 to 10 mtr. pole of reputed make. Make - Bajaj, Transrail, Bansal, Jindal, Gammon Group & Surya. | — | — | — | 59,405 | |
| — | 5.00 | — | — | ||
| Making of foundation suitable for 3 to 8 mtrs. octagonal pole as per site in- charge/4'X4'X4'manufacturer dimension & as per site requirement. | — | — | — | 24,525 | |
| — | 5.00 | — | — | ||
| Supply of (out door) 45 W LED street light luminaire made of pressure die cast aluminium housing LED street light luminaires with IP66, with five year warranty Surya Product Code- SLE UL 45 W IP66 LXN. Make of luminaire & Tube- Philips, Surya, Bajaj, Crompton Greaves & Havells. Warranty/Guarantee 05 Years from date of installation. | — | — | — | 20,660 | |
| — | 5.00 | — | — | ||
| Installation, testing & Commissioning of LED street light fitting complete with all accessories on wall/ on rail pole/tubular pole including connection with 1.5 sq. mm Cu. conductor S/C stranded cable with heavy duty conduit pipe PVC insulated weather proof earthing the body complete etc. as required. | — | — | — | 1,350 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
I_CT_GCC-
ATTACHMENT
GCCACS1-9.pdf
ATTACHMENT
Advancecorrectionslipno.10.pdf
ATTACHMENT
GCCACS11.pdf
ATTACHMENT
TenderdocumentCNCpitBJUCSR.pdf Tender document
ATTACHMENT
GCC_April-2022_2022_CE-I_CT_GCC-2022_POLICY_27_04_22.pdf
ATTACHMENT
TenderdocumentCNCpitBJUCSR.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .