| 1 | L1₹11.2 LAccepted-AOC GROUND FLOOR BUILDING NO 1 MORE COMPLEX ROHA KOLAD ROAD DHATAV RAIGAD MAHARASHTRA 402116 | RAIGAD | MAHARASHTRA | 402116 | ₹11.2 L | L1 | Accepted-AOC AOC |
| 2 | L2₹12.1 LRejected-Finance NEAR KHERDI GRAMPANCHAYAT OFFICE KHERDI CHIPLUN | CHIPLUN | MAHARASHTRA | ₹12.1 L | L2 | Rejected-Finance Rejected |
| 3 | L3₹12.2 LRejected-Finance SHOP NO 2 MORBEKAR JOSHI BUILDING OPP SUDHA MANJIRI SOCY TILAK ROAD NEAR OM BAKERY PANVEL DIST RAIGAD 410206 | PANVEL | RAIGAD | MAHARASHTRA | 410206 | ₹12.2 L | L3 | Rejected-Finance Rejected |
| Sl No | Description | Qty | Unit | STAR Rewinders and Electricals L1 | Thasale And Sons L2 | S P Electricals L3 |
|---|---|---|---|---|---|---|
| 1.00 | Servicing of DG set up to 50 kVA capacity with AMF panel of any make to ensure smooth running of DG set for 30 mins on load. Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any. Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator, checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes, checking of AVR, excitation diodes, its connections confirming proper output voltage. checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and submit the servicing report to engineer in charge. | 72 | JOB PER MONTH | 2,300 ₹1,65,600 Lowest | 2,500 ₹1,80,000 | 2,530 ₹1,82,160 |
| 2.00 | Servicing of DG set from 62.5 kVA to 100 kVA with/without AMF panel of any make to ensure smooth running of DG set for 30 mins on load. Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any. Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator, checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes, checking of AVR, excitation diodes, its connections confirming proper output voltage. checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge. | 72 | JOB PER MONTH | 2,900 ₹2,08,800 Lowest | 3,000 ₹2,16,000 | 3,030 ₹2,18,160 |
| 3.00 | Topping up new lubricating oil 15W/40 grade of approved make as per IS 13656 : 2014 | 344 | Litre | 450 ₹1,54,800 Lowest | 500 ₹1,72,000 | 510 ₹1,75,440 |
| 4.00 | Supplying and erecting V-Belt of all types and lengths, adjust tension as per requirements from generator manufacturer suitable for DG set upto 100kVA | 6 | Number | 3,150 ₹18,900 Lowest | 4,000 ₹24,000 | 4,050 ₹24,300 |
| 5.00 | Supplying and erecting lub oil filter element along with sealing rings, gasket etc complete suitable for DG Set from 82.5 kVA to 100 kVA. | 12 | Number | 3,800 ₹45,600 Lowest | 4,000 ₹48,000 | 4,050 ₹48,600 |
| 6.00 | Supplying and erecting fuel filter along with sealing rings, gasket, primary filter and water separator etc complete suitable for DG Set from 62.5 kVA to 100 kVA. | 12 | Number | 1,800 ₹21,600 Lowest | 2,000 ₹24,000 | 2,020 ₹24,240 |
| 7.00 | Supplying and erecting stop solenoid assembly 12V/24V single coil energized to run with or without primary etc complete suitable for DG set upto 100 kVA. | 6 | Number | 6,400 ₹38,400 Lowest | 7,000 ₹42,000 | 7,070 ₹42,420 |
| 8.00 | Supplying and erecting Air cleaner/Air filter element suitable for DG set from 30 kVA to 100 kVA | 12 | Number | 5,300 ₹63,600 Lowest | 6,000 ₹72,000 | 6,060 ₹72,720 |
| 9.00 | Supplying, erecting and testing permanent magnet generator (PMG) excited Automatic Voltage Regulator (AVR) with sensing input voltage range: 190 V AC - 264 V AC 2/3 Phase, frequency range 50- 60 Hz and output voltage max 120 V DC continuous current 3.7 A, transient current 6 A for 10 second with minimum resistance of 15 ohm, AVR response time of 10 ms etc.complete suitable for DG set as per Specification GEN-SER-AVR | 3 | Number | 70,000 ₹2,10,000 Lowest | 75,000 ₹2,25,000 | 75,750 ₹2,27,250 |
| 10.00 | Supplying and erecting SMPS based Battery Charger input voltage 230 V A.C. & output voltage 24 V DC, charging current 20A suitable to charge DG set Battery | 6 | Number | 19,300 ₹1,15,800 Lowest | 21,000 ₹1,26,000 | 21,200 ₹1,27,200 |
Tender Value
₹11.2 L
EMD Value
₹11,300
Closing Date
30 Oct 2025, 5:00 pmClosed
Executive Engineer E and M Mahad Div
Executive Engineer E and M Mahad Div
DG MAHAD INDUSTRIAL AREA...M and R to WSS and EDS in Mahad and Vile Bhagad Industrial area AMC of Diesel Generator sets for two years.
2025_MIDC_1230809_1
11,24,851.00
Open Tender
Support/Maintenance Service
Item Rate
Mahad Industrial Area...
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,900
₹11,300
4 Jul 2026
16 Oct 2025
3 Nov 2025
16 Oct 2025
30 Oct 2025
21 Oct 2025
17 Oct 2025 - 20 Oct 2025
Amount
Servicing of DG set up to 50 kVA capacity with AMF panel of any make to ensure smooth running of DG set for 30 mins on load. Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any. Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator, checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes, checking of AVR, excitation diodes, its connections confirming proper output voltage. checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and submit the servicing report to engineer in charge.
Servicing of DG set from 62.5 kVA to 100 kVA with/without AMF panel of any make to ensure smooth running of DG set for 30 mins on load. Checking for abnormal sound and leakages, carry out visual inspection of all moving parts, oil levels, oil filters, fuel filters, air filters and clean them properly, rectify the minor leakages if any. Inspect alternator, stator and rotor for normal speed & proper frequency, examine battery charging with monitoring system and recording voltages, checking battery cells gravity and topping up with distilled water, checking V belts with necessary adjustment, checking and retightening of nut bolts including coupling bolts of engine and alternator, checking & cleaning of radiator and leakage testing checking of radiator & fuel supply hose pipes, checking of AVR, excitation diodes, its connections confirming proper output voltage. checking & resetting of valve tappets, Cleaning of DG set internally using blower, cleaning radiator and Submit the servicing report to engineer in charge.
Topping up new lubricating oil 15W/40 grade of approved make as per IS 13656 : 2014
Supplying and erecting V-Belt of all types and lengths, adjust tension as per requirements from generator manufacturer suitable for DG set upto 100kVA
Supplying and erecting lub oil filter element along with sealing rings, gasket etc complete suitable for DG Set from 82.5 kVA to 100 kVA.
Supplying and erecting fuel filter along with sealing rings, gasket, primary filter and water separator etc complete suitable for DG Set from 62.5 kVA to 100 kVA.
Supplying and erecting stop solenoid assembly 12V/24V single coil energized to run with or without primary etc complete suitable for DG set upto 100 kVA.
Supplying and erecting Air cleaner/Air filter element suitable for DG set from 30 kVA to 100 kVA
Supplying, erecting and testing permanent magnet generator (PMG) excited Automatic Voltage Regulator (AVR) with sensing input voltage range: 190 V AC - 264 V AC 2/3 Phase, frequency range 50- 60 Hz and output voltage max 120 V DC continuous current 3.7 A, transient current 6 A for 10 second with minimum resistance of 15 ohm, AVR response time of 10 ms etc.complete suitable for DG set as per Specification GEN-SER-AVR
Supplying and erecting SMPS based Battery Charger input voltage 230 V A.C. & output voltage 24 V DC, charging current 20A suitable to charge DG set Battery
Supplying, erecting, testing and commissioning 4 pole power contactor 32A with coil voltage of 220/240 V suitable to operate on AV voltage for DG set.
Supplying, erecting, testing and commissioning 4 pole power contactor 80-130A with coil voltage of 220/240 V suitable to operate on AV voltage for DG set.
Batteries for Inverter & UPS - Supplying and erecting 12 V/100Ah SMF battery with battery terminal wire, duly charged complete with 24 months warranty complete.
Thasale And Sons (BID ID -6996482)
S P Electricals (BID ID -6999298)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.04 MB
BOQ_2123940.xls
BOQ • 0.29 MB
TenderDocument.pdf
Tender Documents • 0.26 MB
ItemSpecification.pdf
Other Document • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].