Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical | Accepted-Technical Technically Qualified |
| 2 | Accepted-Technical B 13 109 NIMTALA BUS STAND P O P S KALYANI NADIA PIN 741235 | KALYANI | NADIA | WEST BENGAL | 741235 | Accepted-Technical Technically Qualified |
| 3 | Accepted-Technical | Accepted-Technical Technically Qualified |
| 4 | Rejected-Technical | Rejected-Technical Technically Not Qualified |
Tender Value
₹2.3 L
EMD Value
₹4,677
Closing Date
28 Mar 2026, 3:00 pmClosed
The University Engineer, University of Kalyani
The University Engineer, Works Department, University of Kalyani, Kalyani - 741235, Nadia, West Bengal
RENOVATION OF ELECTRICAL WIRING AT SEMINAR ROOM DODL DEPARTMENT UNDER UNIVERSITY OF KALYANI.
2026_UOK_1023216_1
WD/2025-26/3T-1/1070
Open Tender
ELECTRICAL WORKS ORG
Percentage
30 days
UNIVERSITY OF KALYANI
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹4,677
Yes
28 Apr 2026
16 Mar 2026
30 Mar 2026
16 Mar 2026
28 Mar 2026
16 Mar 2026
Renovation of Electrical Wiring at Seminar Room DODL department under University of Kalyani.
Supply & fixing 4 way double door horizontal TPN MCB DB with SS enclosure ( Cat no.8GB32202RC04 )(Siemns) concealed in wall after cutting the wall & mending good the damages to original finish with earthing attachment comprising with the following. a) 63 A Four Pole MCB isolator (Siemens) b) 6 to 32 A range SP MCB. (Siemens) ---12 Nos. [Ref:PWD SOR :-Page No-D-6(Item No-7)Page No-D-5,(Item No-6)Page No-D-10(Item No-14) ]
Supply & fixing SPN MCB DB (2+8) Way (Make Siemens) with S.S. Enclosure (8GB32102RC10) concealed in wall after cutting wall & mending good the damages & earthing attachment comprising with the following: a) 40 A DP isolator - 1 No. (Siemens) b) 6 to 32 A range SP MCB - 8 Nos.(Siemens) [Ref:PWD SOR Page No-D-5(Item No-6)Page No-D-6,(Item No-7)Page No-D-10(Item No-13)]
Supplying and fixing Four Pole 415 V MCB 40 A of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection with 4 way MCB SS enclosure having IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment mending good for damages. [Make: Siemens] [Ref:PWD SOR Page No-D-9(Item No-11)Page No-D-6,(Item No-7)]
Supplying and fixing 20 mm size PVC Rigid Conduit 'FR' [Precision Make]on wall, ceiling with saddles and other accessories as required and mending good damages to building works. [Ref:PWD Page No-E-16,Item No-7(a)] NB - Should be use Precision make shaddle & the saddles should be fixed at 325mm interval .
Supplying and fixing 25 mm size PVC Rigid Conduit 'FR' [Precision Make]on wall, ceiling with saddles and other accessories as required and mending good damages to building works. [Ref:PWD SOR Page No-E-16,Item No-7(b) ] NB - Should be use Precision make shaddle & the saddles should be fixed at 325mm interval .
Cutting Channel of sizes (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge as per office supply pipe sample 19 mm bore, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG including supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles for the following sizes Pipes - **a)19 mm dia 3 mm thick polythene pipe without earth continuity wire (For circuit drawing & Point wiring / as per requirement of Job / as per instruction of EIC) NB - All rubbishes should be removed from work site & also Tee & Elbow should not be use in the conceal pipe,continuity wire. [Ref:PWD SOR Page No : E - 3 Item No : 6(a)]
Cutting Channel of sizes (43 mm x 43 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge as per office supply pipe sample 25 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG including supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles for the following sizes Pipes - **a) 25 mm dia 3 mm thick polythene pipe without earth continuity wire (For circuit drawing & Point wiring / as per requirement of Job / as per instruction of EIC) [E-3/6a & 7a)] NB - All rubbishes should be removed from work site & also Tee & Elbow should not be use in the conceal pipe,continuity wire.
Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaid polythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages A) 4×16 sq mm + 2× 10 sq mm as ECC ( VTPNDB to TPNDB) **NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No:g1 )
Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaid polythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages B)2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC(TPNDB to SPNDB) **NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No: 1(z )
Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaid polythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages (v)2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC ( for AC) **NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No: 1(v )
Supply & drawing 1.1 KV single core stranded 'FR'/'FRLSH PVC insulated & unsheathed copper wire (Make Gloster or Brand approved by EIC) through prelaid polythene pipe and by the prelaid GI fish wire/PVC rigid conduit 'FR' (Precision make) pipe on wall incl. making necy. connection as required & mending good the damages t)2× 2.5 sqmm + 1× 1.5 sqmm.(For Computer Board ) **NB- Should be maintain colour combination of Circuit Wire (Ref:PWD SOR Page No-E-9 Item No: 1(s )
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) For 2.5 sq mm Copper Wire. [Ref:PWD SOR Page No : F - 5 Item No : 9(i)]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) For 4 sq mm Copper Wire. [Ref:PWD SOR Page No : F - 5 Item No : 9(ii)]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) For 6 sq mm Copper Wire. [Ref:PWD SOR Page No : F - 5 Item No : 9(iii)]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) For 10 sq mm Copper Wire. [Ref:PWD SOR Page No : F - 5 Item No : 9(iv)]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. i) For 16 sq mm Copper Wire. [Ref:PWD SOR Page No : F - 5 Item No : 9(v)]
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' /FRLSH PVC insulated & unsheathed copper wire [ Make:Gloster / Polycab / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes] **NB- Should be maintain colour combination of Circuit Wire, partly in 20 mm/25 mm size PVC rigid conduit 'FR' (Precision make) and in 19mm bore, 3 mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Make Legrand Myrius or equivalent Brand approved by EIC) fixed on Modular GI switch board (should be use same brand as swithces ) having 60 mm to 65 mm avg depth of the box complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed] Average Run : 6 mtr (Ref:PWD SOR Page No-E-25 Item No:5)
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' /FRLSH PVC insulated & unsheathed copper wire [ Make:Gloster / Polycab / Finolex (Gold) or as equivalent approved by EIC] After Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes] **NB- Should be maintain colour combination of Circuit Wire, partly in 20 mm/25 mm size PVC rigid conduit 'FR' (Precision make) and in 19mm bore, 3 mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Make Legrand Myrius or equivalent Brand approved by EIC) fixed on Modular GI switch board (should be use same brand as swithces ) having 60 mm to 65 mm avg depth of the box complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed] Average Run : 8 mtr (Ref:PWD SOR Page No-E-25 Item No:5)
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire [ Make:Gloster / Polycab / Finolex (Gold) or as equivalent approved by EIC] in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Make Legrand Myrius or equivalent Brand approved by EIC)incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish *On board (Ref.PWD SOR Page No-E-20 Item No:3(i)
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire [ Make:Gloster / Polycab / Finolex (Gold) or as equivalent approved by EIC] in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Make Legrand Myrius or equivalent Brand approved by EIC)incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish Average run 3 mtr (Ref.PWD SOR Page No-E-20 Item No:3(iii)
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length. [Ref: PWD SOR Page No-C-4 Item no. 29]
Supply & fixing Combo plug board modular type of 6 module GI box with cover plate recessed in wall comprising with the following (Legrand/Cabtree /Brand approved by EIC): (PWD Page No-E-17 ) ----- a) 16A socket --1 No b) 16 A switch --1 NoS c) 6A socket --1 NoS d) 6 A switch --- 1 Nos (PWD Page No-E-17 Item no. 4(b),4(a),3(b),3(a),1(b))
Supply & fixing of Modular type Computer plug board of 12 module GI box with cover plate recessed in wall comprising of the following (Legrand/Cabtree /Brand approved by EIC): a) 16A Switch & 16A Socket ---1 set [3(b)+4(b)]x1 b) 6A Switch - 3 nos & 6A Socket - 3 nos --- 1 set [3(a)+,4(a)]x3 ( Computer Board) [PWD SOR :-Page No E-17(Item No-1(d),3(a),3(b),4(a),4(b)]
Supply & Fixing 240 V, 25 A, Modular type starter (Make North West or equivalent Brand approved by EIC) with 25A Modular switch type DP MCB (C Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (Ref:PWD SOR Page No-E-19 Item no.17)
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Legrand Myrius/Brand approved by EIC), without plug top and switch, with supply and fixing 2 module GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (For AC) (PWD Page No-E-17 Item no. 2(a),4(c))
Supply of recessed mounted LED 36 W 4000K dimension (mm) l |b | h =600 | 600 |60 low glare diffuser light on ceilling complete set. [Make:K-Lite Cat No:-KL-2281 or quivalent make approve by EIC ) ( Ref:Non Schedule Item )
Supply and delivery of 4 Metal Blade 450 mm sweep, single phase, 240 Volt, 85 W 50 Hz Ac Wall Fan including all accessories . (Noise Free) (Make- EPC or equivalent Approve by EIC) ( Ref:Non Schedule Item )
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
BOQ_2514952.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .