Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.6 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Lowest and reasonable bidder | |
| 2 | L2₹93.7 L+₹4.1 L (4.56%)Rejected-Finance | L2 | Rejected-Finance Not lowest bidder | |
| 3 | L3₹95.0 L+₹5.4 L (6.02%)Rejected-Finance | L3 | Rejected-Finance Not lowest bidder | |
| 4 | L4₹95.9 L+₹6.3 L (7.06%)Rejected-Finance 1ST FLOOR GURJEET MARKET DHANGU ROAD | L4 | Rejected-Finance Not lowest bidder | |
| 5 | L5₹1.1 Cr+₹16.8 L (18.8%)Rejected-Finance 1630 SECTOR 7 C CHANDIGARH 160019 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160019 | L5 | Rejected-Finance Not lowest bidder |
Tender Value
₹1.1 Cr
EMD Value
₹1.8 L
Closing Date
22 Mar 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF AMBALA
HQ CWE AF Ambala Ambala cantt 133001
PROVN OF INDEPENDENT FEEDER LINE FOR CERTAIN LOCATION IN TECH AREA AT AFS HALWARA UNDER GE(AF) HALWARA
2023_MES_581011_1
CWE/AF AMB/HAL-43/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HALWARA
For MES enlisted contractor Class B Category b ii and for un-enlisted contractor refer NIT
7 documents required · 7 mandatory
₹1,000
GE AF HALWARA
₹1.8 L
Yes
17 Jul 2023
14 Feb 2023
24 Mar 2023
14 Feb 2023
22 Mar 2023
8 Mar 2023
14 Feb 2023 - 28 Feb 2023
Amount
Supply, laying, jointing, testing and commissioning HT XLPE cable (heavy duty), 11000 volts (earthed), cross sectional area 185 Sqmm, 3 core, insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with upto date amendments, laid in trenches /pipes /ducts /along poles/ walls/ equipment etc complete all as specified & directed. Notes: (i) Cable shall be of manufacturing date not earlier than Jan 2023. All the cable shall be embossed with year of manufacturing, meterage at every metre, in addition to its own standard markings as per IS i.e. Size, voltage etc. The contractor shall produce original purchase vouchers duly machine numbered alongwith excise duty gate pass of factory for verification and record. (ii) Excavation & earth work, sand cushioning, end termination joints, protection pipes & protection covers shall be measured and paid separately. (iii) No straight through joint shall be permitted in less than single drum length. (iv) Cable shall be tested in the presence of rep of Accepting Officer at the factory as well as at site after laying in the trenches & before returning filling in the trenches as & when requested by contractor and same is deemed to be included in quoted rates.
M&L boring of holes under road, pavement, hardstanding for passing/crossing pipes/cables upto size 150mm dia/bore at suitable depth (not below than 1mtr) by trenchless technology using ultra sounding technique and using necessary machinery / equipments complete without damaging the surface and removing excavated soil to a distance not exceeding 50mtr including S&F of HDPE pipe of 150mm bore, 0.4Mpa working pressure complete all as specified & directed. Notes : (i) Location of boring holes shall be decided by the Engineer-in-charge as per requirement, nothing extra shall be payable on account of variation in length of crossing of road etc. (ii) During boring soil strata may be changed, hence nothing extra shall be paid to the contractor for boring of holes through different strata/different type of soil. (iii) The one RM of boring holes & HDPE pipe shall measured as one unit for payment purpose.
S&F cable jointing kit for 11000 volt earthed grade, outdoor, end termination heat shrinkable type joints complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185sqmm complete all as specified & directed.
M&L PCC 1:3:6, type C2, using 40mm graded mechanically crushed stone aggregate as in foundation, filling and mass concrete complete all as specified & directed.
Supply, installation, testing & commissioning of factory made HT Feeder Pillar box(conforming to IP-54 protection), size 150cm x 65cm x 90cm with 03 Nos. copper busbar(size 100cm x 6cm x 6mm) mounted on HT porcelain insulator, outdoor & double door type, dust, weather & vermin proof, having front & rear openable shutter(two leaf) by keys from both side having chromium plated fancy lock (2 Nos. in each compartment) with high quality rubber beading on door and locking arrangement. Feeder pillar box shall be made out of CRCA steel sheet 3.15mm thick duly powder coated painted by using 7 tank process. The top of the CRCA sheet shall be bent in slope/tapper with projection of 100mm on all sides. Including cable entry arrangements at bottom and earthing terminals 2 Nos. at both side. The feeder pillar box should be mounted on frame base of MS angle iron of size 100mm x 100mm x 8mm duly zinc metal coated and legs 90cm long grouted/fixed in PCC blocks of 1:3:6, type C-1 of size 30cm x 30cm x 15cm complete all as specified & directed:- Notes: (i) The cost of Earthwork in any type of soil, fair finished formwork (if any) & PCC blocks/foundation of size as directed by Engineer-in-charge deemed to be included in quoted rates. (ii) Layout diagram of HT Feeder Pillar shall be produced by contractor for approval of Accepting Officer through GE before placing order to manufacturer and panel shall be brought at site as per approved drawing. The cost of same is deemed to be included quoted rates.
Supply, installation, testing & commissioning of Ring Main Unit(RMU) outdoor type, 11 KV, 630Amps, 20 KA outdoor extensible SF6 gas insulated 5 way floor mounted compact switchgear with copper busbar consisting of 01 No. incoming VCB, 04 Nos. outgoing VCB and 01 No. air insulated BUS PT panel. The coupling should be at the top of RMU through bolted connection & sleeved busbars covered with insulating boots. All live parts, busbars, VCB will be closed in robotically welded 2.5mm thick non ferrite non-magnetic stainless steel tank filled with SF6 with IP class IP-67, leak rate not less than 0.1% and tested for internal arc 21KA/second as per latest IEC 62271-200. The unit shall include the following with all necessary standard fittings complete all as specified & directed:- (a) Incoming VCB-01 No./Outgoing VCB-04 Nos. consisting of following:- (i) Manual operated 630Amps Vacuum circuit breaker having two position double spring mechanism. (ii) Three position disconnector/earthing switch down stream vacuum circuit breaker. (iii) Three position single spring mechanism for disconnector/earthing switch. (iv) Live cable LED indicators thru capacitor voltage dividers mounted on the bushings. (v) Green (ON)/Red(OFF) push buttons to operate load break switch locally. (vi) 4 Nos. (O/C + E/F) self powered numerical protection relay with low and high set for over current and earth fault, relay should have facility to display the maximum loaded phase current also.
Notes: - (i) The rate for making foundation for RMU of size as per recommendation by manufacturer and the cost of excavation, brick work, concrete, steel etc. (if any) shall be included in the quoted rate. The drawing for foundation as per manufacturer design & shall be approved by GE. (ii) The drawings in respect of RMU shall be approved by Accepting Officer through GE and as & when requested by contractor before placing order to manufacturer. (iii) RMU shall be tested by representative of Accepting Officer at factory premises before dispatch as & when requested by contractor. (iv) The testing and commissing after installation of the RMU shall be carried out in presence of Senior Electrical Inspector as & when requested by contractor. (v) The cost of all above factors deemed to be included in quoted rates.
M&L earthing complete with galvanized steel earth plate electrode 60cm X 60cm X 6mm thick buried directly vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of earth plate not less than 1.5 mtr below ground level surrounded from all sides by 15cm thick packed layer of Charcoal dust & common salt filled in alternate layers and electrode connected to GI earth lead strip 32mm x 6mm upto 7.5mtr long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly and including watering pipe medium grade GI 20mm bore & protection pipe light grade GI 40mm bore, including wire mesh, funnel, lugs, salt, charcoal dust, excavation in soft/losse soil, returning filling & removal of surplus soil upto 50mtr, pit chamber shall be of PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates and pit cover slab 80mm thick shall be of Precast RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates reinforced with XPM weighing not less than 4Kg/sqm including necessary form work complete all as shown in electrical plate No 3 of SSR part-I, including testing on completion at site complete all as specified & directed. Notes:- (i) Any variation in length of earth lead and protection pipe of earth lead shall be adjusted through DO. (ii) On testing if the desired earth resistance is not obtained, earthing will be generated at no extra cost , till the desired earth resistance is obtained. (iii) The chamber shall be constructed atleast 1.5 mtr away from the earth electrode.
M&L 32mm x 6mm galvanised iron strip as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other situation for loop earthing etc. complete all as specified & directed.
Supply, installation, commissioning and testing of HT 11KV, 3 phase 50 hertz, 3 wire, indoor type, floor mounted, horizontal drawout, vertical isolation type totally enclosed metal clad, prewired, independent type Vaccum Circuit Breaker(VCB), capacity 630 Amp rating, incommer VCB connecting with copper busbar of appropriate capacity duly insulated, motor operated, spring charged having rupturing capacity of 350 MVA, comprising of the following undermentioned asscessories including providing suitable foundation for VCB as per manufacturer's instructions complete all as specified & directed:- (a) Housing for circuit breaker carriage -01 No. (b) Mechanical interlock and automatic safety shutter gear including padlocking arrangement - 01 No. (c) Isolating plugs - 06 Nos. (d) 18.4KA at 11KV, 630Amp VCB comprising of the following:- (i) Assembly of 3 vaccum interrupters complete with epoxy support insulators and self aligning finger type isolating contacts. (ii) Hand & motor operated (220 volt AC) spring charged, independent starting crossing /tripping trip free operating mechanism with manual closing and tripping push buttons and mechanical break closed / open spring charged/discharged indication. (iii) Mechanical operation counter.
(q) Inbuilt arrangement for continuous DC supply as per manufacturer's recommendation for the system. (r) Common busbar having inbuilt alarm/hooter/barrer system. (s) Battery bank of suitable capacity for 11 KV VCB -02 Nos. Notes:- (i) Rate of cutting in existing VCB, modification of existing busbar for matching with new busbar will be included in the quoted rates. (ii) The drawings in respect of VCB shall be approved by Accepting Officer through GE and as & when requested by contractor before placing order to manufacturer (iii) VCB shall be tested by representative of Accepting Officer at factory premises before dispatch as & when requested by contractor. (iv) The testing and commissing of the VCB shall be carried out in presence of Electrical Inspector as & when requested by contractor. (v) The cost of all above factors deemed to be included in quoted rates.
Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5mtr in depth for foundation etc or for walls, shafts, manholes not exceeding 10 Sqm on plan or for laying pipes/cables etc and getting out, in soft/loose soil complete all as specified & directed.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm thick each in soft/loose soil complete all as specified & directed.
Removal of excavated soil to a distance not exceeding 50 mtr & depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified & directed.
M&L sand cushioning to electric cable with a layer of dry fine sand 8 cm deep before laying the cable and 15 cm deep after laying the cable (punned down to 18 cm depth after laying and stretching of cable ) complete all as specified & directed.
M&L un-reinforced precast concrete cable cover, Class HV type-1, flat, size 300mm x 180mm x 40mm, ISI marked, laid flat for protection of cable, adjacent to each other, perpendicular to central axis of cable complete all as specified & directed.
BEHL AND COMPANY
M/s Kataria Construction Company
Vijay Kumar Contractor and Engineers
SAGGI ELECTRIC COMPANY
M/s Rohit Construction Co.
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .