Diversion & modification of HT (33KV & 11KV) and LT line across and along the railway track at different locations between Aluabari Road Junction & Thakurganj railway station, Thakurganj & Siliguri Junction railway station & Siliguri Junction & New Jalpaiguri railway station for clearing electrical infringement with proposed double line.
E-C-N-S-02-26-27-DL
E-C-N-S-02-26-27-DL
Open
12 Months
Jalpaiguri, West Bengal
₹0
₹15.0 L
30 Jun 2026
30 Jun 2026
8 Jul 2026
To conduct survey of the locations of HT (33KV Kilometre & 11KV) infringement and submit drawings showing plan, elevation, CSD & BOQ of present HT track crossing & modified/diverted HT line etc prepared in AutoCad or similar platforms. Approval to be obtained from concerned SEB officials after approval of Railways (open line/Construction/RailTel). All coordination with NBPDCL for approval of drawings shall be done by the contractor. Two set drawings of every location shall be submitted to Railways after final approval.
"Supply of Galvanized steel swaged tubular pole Numbers 14.5 mtr long, type 410 SP-76 with step length 6.5-4.00-4.00 mtr., sectional dia 219.1 x 193.7 x 165.1 mm, sectional thickness 5.9 x 4.85 x 4.5 mm as per IS 2713 - 1980 including suitable size of CI base plate & it's fastener and GI cap on the top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH."
Supply of galvanized steel tubular pole 12 mtr Numbers long type 410SP-66 with step length 5.80-3.10- 3.10 mtr sectional dia 219.1x193.7x165.1 mm sectional thickness 5.9x4.85x4.5mm as per IS 2713-1980 including suitable size of CI base plate & it's fastener and GI cap on top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH.
Erection of tubular pole 12/14.5/16 Mtr.long Numbers including digging the pit 1/5th. of total length.
Supply and execution of CC foundation work in cum ratio 1:3:6 by cement,sand and chips of size 19mm & down. The size of the CC block will be 30cm dia with height upto the pole depth below GL and 30Cm above GL including tie muffing of DP.
Supply & erection of 2P composite polymer 33 Numbers KV ball & socket type Disc insulator ( 90 KN) with minimum creepage distance 900mm & sectional length 510mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rodand sealed to the hot dipped galvanised carbon steelend fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or asper IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/NBPDCL approved
Supply & erection of 2P composite polymer 33 Numbers KV Pin insulator (10 KN) with minimum creepage distance 980mm & sectional length 415 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731(1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/NBPDCL approved NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & erection of 2P composite polymer 11 Set KV ball & socket type Disc insulator ( 70 KN) with minimum creepage distance 320 mm & sectional length 300 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rodand sealed to the hot dipped galvanised carbon steelend fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or asper IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/NBPDCL approved
Supply & erection of 2P composite polymer 11 Numbers KV Pin insulator (10 KN) with minimum creepage distance 340mm & sectional length 235 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731(1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/NBPDCL approved
Supply & erection of 11 KV Gang Operated Air Set breakoff load disconnecting switch - 400 Amp 3 pole rocking type each pole consist of galvanised steel base, HT insulators as per BSS/ISS non ferrous knife and spring loaded contacts, arcing horns of adequate sections to break magnetising current of the transformer horizontal GI pipe of adequate length for phase separation and 25mm dia, 3.65mm thickness GI pipe of adequate length for operation from ground level and operating handle complete in both ON & OFF positions. Make: Rly/NBPDCL approved
Supply and erection of 11KV DO fuse double Set stack channel type 200 Amps capacity. Make: Rly/NBPDCL approved
Suply and erection of Zinc Oxide Station Class-I Set lightning arrestor suitable for 3 wire 33KV with rated voltage 30KV(RMS) and a normal discharge current rating of 10KA as per IS:4004 (1985), complete with galvanised clamping arrangement, GI bolts, nuts, washer etc. (3 Nos in a set). Make: Raychem/Oblum/Lamco/Elpro
Supply and erection of 3 Nos station class - 1 Set Zinc oxide Lightening arrestor suitable for 3 wire 11 KV OH with rated voltage 9 KV (RMS) with normal discharge current rating of 10 KA and complete with galvanized clamping arrangement, GI bolts, nuts, washer as required conforming to IS 3070-III-1993. Make: OBLUM/REYCHEM/LAMCO/Elpro
Supply, stringing & binding of ACSR conductor Metre Wolf of size 30/7/2.59 mm conforming to IS : 398-Pt.II-1976
Supply, stringing & binding of ACSR conductor Metre Dog of size 6/4.72+7/1.57 mm conforming to IS : 398-Pt.II-1976
Supply & stringing, binding of GI wire 8 SWG for Metre guarding
Supply & stringing, binding of GI wire 10 SWG Metre for lacing NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & erection of Galvanised stay set for HT Set (33KV & 11KV) OH line comprising of 20 mm dia with 1.8 mtr long stay rod, anchor plate of size 30x30cmx6mm/45x45x7.5mm, turn buckle (20mmx600 mm), 20mm thimble , stay clamp, 7/10mm dia GI stay wire, Guy strain insulator of size 85 x140 mm as per ref. IS 5300/1969, and cc foundation with ratio 1:3:6 including excavation, refilling etc.
Supply & erection of danger board size 8"x6" on Numbers GI clamp made of 20x3mm for 33/11 KV showing the voltage grade, skull symbol etc.
Supply & erection of barbed wire upto height Numbers 2.5m to be fixed on pole with 2 nos. of clamps of suitable size and as per direction of Engineer Incharge at site.
Dismantling of over head alignment like Each conductor, insulator, bracket etc and handing Span over to concerned Rly/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Uprooting of existing pole without damaging the Numbers bottom of the pole etc and handing over to concerned Rly/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Supply & laying of class LA type CI/DI pipe 150 Metre mm dia of measureable length 5.5 mtr each length for passing of cable conforming to ISS : 1536-1989 or latest amendment of IS/ISS/IEC 1.5 m below ground level as per direction of Engineer In charge at site
Supply & laying of class LA type CI/DI pipe 300 Metre mm dia of measureable length 5.5 mtr each length for passing of cable conforming to ISS : 1536-1989 or latest amendment of IS/ISS/IEC 1.5 m below ground level as per direction of Engineer In charge at site
Horizontal boring of size 100/150/200/250/300 Metre mm dia hole across railway embankment / Road at a depth of 1.5Mtr below GL by HDD Machine at Contractor's own arrangement as per direction of Engineer in charge at site.
Horizontal boring of 250/400mm dia hole across Metre Railway embankment/Road at a depth of 1.5 mtr below GL by turning a pointed instrument at contractor's own arrangement as per direction of Engineer In Charge at site.
Supply and erection of earthing by 50 mm GI Numbers pipe IS:1239/1990 (Pt-I) of 3.60mm thickness 3mtr long including construction of earth pit, RCC earth cover slab with filling/mixing of salt, charcoal etc of required quantity and earth continuty by 25x3mm GI strip with GI nuts bolts washer etc. including welding, earth resistance flag etc.
Supply and laying of additionalGI Strip including Metre suitable size hole, GI nuts & bolts, washer or welded in joints wherever required as per direction of Engineer in charge at site of size 25 mm x 6 mm
Supply and laying of HDPE pipe of size 4 inch Metre (110mm outside dia), 6kgf/cm2, 6.0 mtr each length, PE-100 Grade conforming to IS : 4984/1995. Make:SWASTIK/SUPREME/NATRAJ PIPES/SKIPPER/SINTEX/SUDHAKAR/AJA Plus NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply 100x50x50x6mm bracket of suitable length clamped with above pole made by GI flat 50x5mm with 50x16mm GI bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting. As required as per direction of Engineer in charge/NBPDCL.
Supply 75x40x40x6mm bracket of suitable size clamped with pole made by GI flat of size 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting as per direction of Engineer in charge/NBPDCL
Supply & fixing of GI angle size 65x65x6mm Metre bracket of suitable sizes clamped with above pole made by GI flat 50x5mm with 50x16mm GI bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting. As per direction of Engineer in charge/NBPDCL
Construction of cable trench of desired depth cum below the ground level for laying cable/pipes as per direct laying method and direction of site Engineer and filling & compacting of trench with soil with watering and ramming after laying of cable and disposal of garbage form site within a distance of 50 mtr.
Supply and laying of standard Bricks as per cum procedure for cable protection
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 33 KV (E) grade 3 core 400 sqmm size cable conforming to IS : 7098-II-2011 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables.
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire aluminium armoured , over all PVC sheathed (A2XWaY) 33 KV (E) grade Single core 630 sqmm size cable conforming to IS : 7098-II-1985 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with creeping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 11 KV (E) grade 3 core 300 sqmm size cable conforming to IS : 7098-II-1985 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables.
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 11KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 300 Sqmm sizes as per Raychem model no EPKT-3372 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 33KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 400 Sqmm sizes as per Raychem model no EPKT-6374 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 33KV XLPE cable with required sockets/studs etc as per standard procedure of 1 core 630 Sqmm sizes as per Yamuna cable accessories Pvt Ltd model no XSOS-34 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar Total 20329368.00 Item- 2 Part- II (LT) S No. Item Description of Item Unit Qty Rate Amount No
To conduct survey of the locations of LT Kilometre infringement and submit drawings showing plan, elevation, CSD & BOQ for proposed LT line & diversion and modification of LT line etc prepared in AutoCad or similar platforms. Approval to be obtained from concerned SEB officials after approval of Railways (open line/Construction/RailTel). All coordination with NBPDCL for approval of drawings shall be done by the contractor. Two set drawings of every location shall be submitted to Railways after final approval.
Supply of galvanized steel tubular pole 9 mtr Numbers long type 410SP-33 with step length 5.00-2.00- 2.00 mtr sectional dia 165.1x139.7x114.3 mtr sectional thickness 5.4x4.5x3.65 mm as per IS 2713-1980 including suitable size of CI base plate & it's fastener and GI cap on the top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH.
Erection of tubular pole 9-12 Mtr.long including Numbers digging the pit 1/5th. of total length.
Supply and execution of CC foundation work in cum ratio 1:3:6 by cement,sand and chips of size 19mm & down. The size of the CC block will be 30cm dia with height upto the pole depth below GL and 30Cm above GL including tie muffing of DP. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & erection of Galvanised stay set for LT Set OH line comprising of 20 mm dia. 1.8 mtr long stay rod, anchor plate of size 23x23cmx 6mm dia thick, thimble,stay clamp, 7/12SWG GI stay wire strain insulator etc.in cc foundation with ratio 1:3:6 including excavation, refilling etc
Supply and fixing of LT pin insulator of size Numbers 80x105 mm made of high grade porcelain complete with mounting threaded GI pin, GI pin, nut & bolt etc confront to IS- 1445-1977
Supply& erection of LT shackle insulator of size Numbers 75x90 mm along with GI "D" clamp and full threaded 8"long 1/2" dia GI bolt and nut with all accessories for tensioning.
Supply and installation of HDPE pipe 63 mm dia Metre (PN-6.0 grade) for cable protection.Make:SWASTIK/SUPREME/NATRAJ PIPES/SKIPPER/SINTEX/SUDHAKAR/AJA Plus
Supply, stringing & binding of ACSR conductor Metre Rabbit of size 6/1/ 3.35 mm conforming to IS : 398-Pt.II-1976
Supply & stringing, binding of GI wire 8 SWG for Metre guarding
Supply & stringing, binding of GI wire 10 SWG Metre for guarding
Supply & fixing of GI angle size 50x50x6mm Metre bracket of following size clamped with above pole made by GI flat 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting .
Supply and erection of earthing by 50 mm GI Numbers pipe IS:1239/1990 (Pt-I) of 3.60mm thickness 3mtr long including construction of earth pit, RCC earth cover slab with filling/mixing of salt, charcoal etc of required quantity and earth continuty by 25x3mm GI strip with GI nuts bolts washer etc. including welding, earth resistance flag etc.
Supply and laying of additional GI Strip including Metre suitable size hole, GI nuts & bolts, washer or welded in joints wherever required as per direction of Engineer in charge at site of size 25 mm x 6 mm
Supply, erection & commissioning of earth spike Numbers made of 20 mm dia, 1.8 mtr long GI rod including earth continuity with 6 SWG GI wire complete with GI nut, bolt, washer etc
Supply, fixing, erection & stringing of LT Aerial Metre bunched cable of 1.1 KV 3Cx50+1Cx16+1Cx35 sq mm
Supply, fixing, erection & stringing of LT AB Numbers cable anchoring clamp (galvanised)
Supply, fixing, erection & stringing of LT AB Numbers cable suspension clamp (galvanised)
Supply, fixing, erection & stringing deadend clamp for LT AB cable
Supply, fixing, erection & stringing of Insulation Numbers piercing connector (AB cable)
Supply, fixing, erection & stringing of Piercing Numbers insulation straight through joint (AB cable) 50 sq mm cable NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Dismantling of over head alignment like Each conductor, insulator, bracket etc etc and Span handing over to concerned Rly/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Uprooting of existing pole without damaging the Numbers bottom of the pole etc and handing over to concerned Rly/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
"Supply, installation, testing and commissioning Numbers of integrated solar street light with 6 Mtr GI Pole, 30W LED fitting having system efficiency on min 100lumen per watt, integrated with lithium battery, solar PV Module (120W), MPPT solar charge controller aluminium pressure die cast body 3 days autonomy, auto ON/OFF, Dusk to dawn operation, sensor switch for auto diming complete with all accessories conforming to MNRE Specification and CC (1:3:6) foundation ." Total 1167304.00 Schedule Schedule 2-Schedule-B (TKG-SGUJ) Item- 1 Part- I (HT) S No. Item Description of Item Unit Qty Rate Amount No
To conduct survey of the locations of HT (33KV Kilometre & 11KV) infringement and submit drawings showing plan, elevation, CSD & BOQ of present HT track crossing & modified/diverted HT line etc prepared in AutoCad or similar platforms. Approval to be obtained from concerned SEB officials after approval of Railways (open line/Construction/RailTel). All coordination with WBSEDCL/NBPDCL for approval of drawings shall be done by the contractor. Two set drawings of every location shall be submitted to Railways after final approval.
"Supply of Galvanized steel swaged tubular pole Numbers 14.5 mtr long, type 410 SP-76 with step length 6.5-4.00-4.00 mtr., sectional dia 219.1 x 193.7 x 165.1 mm, sectional thickness 5.9 x 4.85 x 4.5 mm as per IS 2713 - 1980 including suitable size of CI base plate & it's fastener and GI cap on the top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH."
"Supply of galvanized steel tubular pole 12 mtr Numbers long type 410SP-66 with step length 5.80-3.10- 3.10 mtr sectional dia 219.1x193.7x165.1 mm sectional thickness 5.9x4.85x4.5mm as per IS 2713-1980 including suitable size of CI base plate & it's fastener and GI cap on top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH."
Erection of tubular pole 12/14.5/16 Mtr.long Numbers including digging the pit 1/5th. of total length.
Supply and execution of CC foundation work in cum ratio 1:3:6 by cement,sand and chips of size 19mm & down. The size of the CC block will be 30cm dia with height upto the pole depth below GL and 30Cm above GL including tie muffing of DP. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & erection of 2P composite polymer 33 Numbers KV ball & socket type Disc insulator ( 90 KN) with minimum creepage distance 900mm & sectional length 510mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rodand sealed to the hot dipped galvanised carbon steelend fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or asper IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL approved
Supply & erection of 2P composite polymer 33 Numbers KV Pin insulator (10 KN) with minimum creepage distance 980mm & sectional length 415 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731(1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL/NBPDCL approved
Supply & erection of 2P composite polymer 11 Set KV ball & socket type Disc insulator ( 70 KN) with minimum creepage distance 320 mm & sectional length 300 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rodand sealed to the hot dipped galvanised carbon steelend fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or asper IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL/NBPDCL approved
Supply & erection of 2P composite polymer 11 Numbers KV Pin insulator (10 KN) with minimum creepage distance 340mm & sectional length 235 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731(1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL/NBPDCL approved
Supply & erection of 11 KV Gang Operated Air Set breakoff load disconnecting switch - 400 Amp 3 pole rocking type each pole consist of galvanised steel base, HT insulators as per BSS/ISS non ferrous knife and spring loaded contacts, arcing horns of adequate sections to break magnetising current of the transformer horizontal GI pipe of adequate length for phase separation and 25mm dia, 3.65mm thickness GI pipe of adequate length for operation from ground level and operating handle complete in both ON & OFF positions. Make: Rly/WBSEDCL/NBPDCL approved
Supply and erection of 11KV DO fuse double Set stack channel type 200 Amps capacity. Make: Rly/WBSEDCL/NBPDCL approved NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Suply and erection of Zinc Oxide Station Class-I Set lightning arrestor suitable for 3 wire 33KV with rated voltage 30KV(RMS) and a normal discharge current rating of 10KA as per IS:4004 (1985), complete with galvanised clamping arrangement, GI bolts, nuts, washer etc. (3 Nos in a set). Make: Raychem/Oblum/Lamco/Elpro
"Supply and erection of 3 Nos station class - 1 Set Zinc oxide Lightening arrestor suitable for 3 wire 11 KV OH with rated voltage 9 KV (RMS) with normal discharge current rating of 10 KA and complete with galvanized clamping arrangement, GI bolts, nuts, washer as required conforming to IS 3070-III-1993. Make: OBLUM/REYCHEM/LAMCO/Elpro"
Supply, stringing & binding of ACSR conductor Metre Wolf of size 30/7/2.59 mm conforming to IS : 398-Pt.II-1976
Supply, stringing & binding of ACSR conductor Metre Dog of size 6/4.72+7/1.57 mm conforming to IS : 398-Pt.II-1976
Supply & stringing, binding of GI wire 8 SWG for Metre guarding
Supply & stringing, binding of GI wire 10 SWG Metre for lacing
Supply & stringing, binding of GI wire 10 SWG Set for lacing
Supply & erection of danger board size 8"x6" on Numbers GI clamp made of 20x3mm for 33/11 KV showing the voltage grade, skull symbol etc.
Supply & erection of barbed wire upto height Numbers 2.5m to be fixed on pole with 2 nos. of clamps of suitable size and as per direction of Engineer Incharge at site.
Dismantling of over head alignment like Each conductor, insulator, bracket etc and handing Span over to concerned Rly/WBSEDCL/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Uprooting of existing pole without damaging the Numbers bottom of the pole etc and handing over to concerned Rly/WBSEDCL/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Supply & laying of class LA type CI/DI pipe 150 Metre mm dia of measureable length 5.5 mtr each length for passing of cable conforming to ISS : 1536-1989 or latest amendment of IS/ISS/IEC 1.5 m below ground level as per direction of Engineer In charge at site
Supply & laying of class LA type CI/DI pipe 300 Metre mm dia of measureable length 5.5 mtr each length for passing of cable conforming to ISS : 1536-1989 or latest amendment of IS/ISS/IEC 1.5 m below ground level as per direction of Engineer In charge at site
Horizontal boring of size 100/150/200/250/300 Metre mm dia hole across railway embankment / Road at a depth of 1.5Mtr below GL by HDD Machine at Contractor's own arrangement as per direction of Engineer in charge at site.
Horizontal boring of 250/400mm dia hole across Metre Railway embankment/Road at a depth of 1.5 mtr below GL by turning a pointed instrument at contractor's own arrangement as per direction of Engineer In Charge at site. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply and erection of earthing by 50 mm GI Numbers pipe IS:1239/1990 (Pt-I) of 3.60mm thickness 3mtr long including construction of earth pit, RCC earth cover slab with filling/mixing of salt, charcoal etc of required quantity and earth continuty by 25x3mm GI strip with GI nuts bolts washer etc. including welding, earth resistance flag etc.
Supply and laying of additionalGI Strip including Metre suitable size hole, GI nuts & bolts, washer or welded in joints wherever required as per direction of Engineer in charge at site of size 25 mm x 6 mm
Supply and laying of HDPE pipe of size 4 inch Metre (110mm outside dia), 6kgf/cm2, 6.0 mtr each length, PE-100 Grade conforming to IS : 4984/1995. Make:SWASTIK/SUPREME/NATRAJ PIPES/SKIPPER/SINTEX/SUDHAKAR/AJA Plus
Supply 100x50x50x6mm bracket of suitable length clamped with above pole made by GI flat 50x5mm with 50x16mm GI bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting. As required as per direction of Engineer in charge/WBSEDCL/NBPDCL
Supply 75x40x40x6mm bracket of suitable size clamped with pole made by GI flat of size 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting as per direction of Engineer in charge/WBSEDCL/NBPDCL
Supply & fixing of GI angle size 65x65x6mm Metre bracket of suitable sizes clamped with above pole made by GI flat 50x5mm with 50x16mm GI bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting. As per direction of Engineer in charge/WBSEDCL/NBPDCL
Construction of cable trench of desired depth cum below the ground level for laying cable/pipes as per direct laying method and direction of site Engineer and filling & compacting of trench with soil with watering and ramming after laying of cable and disposal of garbage form site within a distance of 50 mtr.
Supply and laying of standard Bricks as per cum procedure for cable protection
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 33 KV (E) grade 3 core 400 sqmm size cable conforming to IS : 7098-II-2011 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire aluminium armoured , over all PVC sheathed (A2XWaY) 33 KV (E) grade Single core 630 sqmm size cable conforming to IS : 7098-II-1985 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with creeping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables.
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 11 KV (E) grade 3 core 300 sqmm size cable conforming to IS : 7098-II-1985 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables.
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 11KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 300 Sqmm sizes as per Raychem model no EPKT-3372 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 33KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 400 Sqmm sizes as per Raychem model no EPKT-6374 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 33KV XLPE cable with required sockets/studs etc as per standard procedure of 1 core 630 Sqmm sizes as per Yamuna cable accessories Pvt Ltd model no XSOS-34 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar Total 28035999.00 Item- 2 Part- II (LT) S No. Item Description of Item Unit Qty Rate Amount No
To conduct survey of the locations of LT Kilometre infringement and submit drawings showing plan, elevation, CSD & BOQ for proposed LT line & diversion and modification of LT line etc prepared in AutoCad or similar platforms. Approval to be obtained from concerned SEB officials after approval of Railways (open line/Construction/RailTel). All coordination with WBSEDCL/NBPDCL for approval of drawings shall be done by the contractor. Two set drawings of every location shall be submitted to Railways after final approval. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply of galvanized steel tubular pole 9 mtr Numbers long type 410SP-33 with step length 5.00-2.00- 2.00 mtr sectional dia 165.1x139.7x114.3 mtr sectional thickness 5.4x4.5x3.65 mm as per IS 2713-1980 including suitable size of CI base plate & it's fastener and GI cap on the top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH.
Erection of tubular pole 9-12 Mtr.long including Numbers digging the pit 1/5th. of total length.
Supply and execution of CC foundation work in cum ratio 1:3:6 by cement,sand and chips of size 19mm & down. The size of the CC block will be 30cm dia with height upto the pole depth below GL and 30Cm above GL including tie muffing of DP.
Supply & erection of Galvanised stay set for LT Set OH line comprising of 20 mm dia. 1.8 mtr long stay rod, anchor plate of size 23x23cmx 6mm dia thick, thimble,stay clamp, 7/12SWG GI stay wire strain insulator etc.in cc foundation with ratio 1:3:6 including excavation, refilling etc
Horizontal boring of size 100/150/200/250/300 Metre mm dia hole across railway embankment / Road at a depth of 1.5Mtr below GL by HDD Machine at Contractor's own arrangement as per direction of Engineer in charge at site.
Supply and fixing of LT pin insulator of size Numbers 80x105 mm made of high grade porcelain complete with mounting threaded GI pin, GI pin, nut & bolt etc confront to IS- 1445-1977
Supply& erection of LT shackle insulator of size Numbers 75x90 mm along with GI "D" clamp and full threaded 8"long 1/2" dia GI bolt and nut with all accessories for tensioning.
Supply and installation of HDPE pipe 63 mm dia Metre (PN-6.0 grade) for cable protection.Make:SWASTIK/SUPREME/NATRAJ PIPES/SKIPPER/SINTEX/SUDHAKAR/AJA Plus
Supply, stringing & binding of ACSR conductor Metre Rabbit of size 6/1/ 3.35 mm conforming to IS : 398-Pt.II-1976
Supply & stringing, binding of GI wire 8 SWG for Metre guarding
Supply & stringing, binding of GI wire 10 SWG Metre for guarding
Supply & fixing of GI angle size 50x50x6mm Metre bracket of following size clamped with above pole made by GI flat 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting .
Supply and erection of earthing by 50 mm GI Numbers pipe IS:1239/1990 (Pt-I) of 3.60mm thickness 3mtr long including construction of earth pit, RCC earth cover slab with filling/mixing of salt, charcoal etc of required quantity and earth continuty by 25x3mm GI strip with GI nuts bolts washer etc. including welding, earth resistance flag etc.
Supply and laying of additional GI Strip including Metre suitable size hole, GI nuts & bolts, washer or welded in joints wherever required as per direction of Engineer in charge at site of size 25 mm x 6 mm NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply, erection & commissioning of earth spike Numbers made of 20 mm dia, 1.8 mtr long GI rod including earth continuity with 6 SWG GI wire complete with GI nut, bolt, washer etc
Supply, installing, testing & commissioning of LT Numbers distribution kiosk for distribution transformer. It is the liability of the contractor to submit the specification & drawing according to WBSEDCL's design & specification against the material code number as mentioned & to obtain the approval from WBSEDCL/NBPDCL/Rly. LT distribution kiosk for 100 KVA transformer (WBSEDCL material code no 0407010541)
Supply, installing, testing & commissioning of LT Numbers distribution kiosk for distribution transformer. It is the liability of the contractor to submit the specification & drawing according to WBSEDCL's design & specification against the material code number as mentioned & to obtain the approval from WBSEDCL/NBPDCL/Rly. LT distribution kiosk for 315 KVA transformer (WBSEDCL material code no 0407010841)
Supply, fixing, erection & stringing of LT Aerial Metre bunched cable of 1.1 KV 3Cx50+1Cx16+1Cx35 sq mm
Supply, fixing, erection & stringing of LT AB Numbers cable anchoring clamp (galvanised)
Supply, fixing, erection & stringing of LT AB Numbers cable suspension clamp (galvanised)
Supply, fixing, erection & stringing deadend clamp for LT AB cable
Supply, fixing, erection & stringing of Insulation Numbers piercing connector (AB cable)
Supply, fixing, erection & stringing of Piercing Numbers insulation straight through joint (AB cable) 50 sq mm cable
Dismantling of over head alignment like Each conductor, insulator, bracket etc etc and Span handing over to concerned Rly/WBSEDCL/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Uprooting of existing pole without damaging the Numbers bottom of the pole etc and handing over to concerned Rly/WBSEDCL/NBPDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
"Supply, installation, testing and commissioning Numbers of integrated solar street light with 6 Mtr GI Pole, 30W LED fitting having system efficiency on min 100lumen per watt, integrated with lithium battery, solar PV Module (120W), MPPT solar charge controller aluminium pressure die cast body 3 days autonomy, auto ON/OFF, Dusk to dawn operation, sensor switch for auto diming complete with all accessories conforming to MNRE Specification and CC (1:3:6) foundation ." Total 3302213.00 Schedule Schedule 3-Schedule-C (SGUJ-NJP) Item- 1 Part- I (HT) S No. Item Description of Item Unit Qty Rate Amount No NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
To conduct survey of the locations of HT (33KV Kilometre & 11KV) infringement and submit drawings showing plan, elevation, CSD & BOQ of present HT track crossing & modified/diverted HT line etc prepared in AutoCad or similar platforms. Approval to be obtained from concerned SEB officials after approval of Railways (open line/Construction/RailTel). All coordination with WBSEDCL for approval of drawings shall be done by the contractor. Two set drawings of every location shall be submitted to Railways after final approval.
Supply of Galvanized steel swaged tubular pole Numbers 14.5 mtr long, type 410 SP-76 with step length 6.5-4.00-4.00 mtr., sectional dia 219.1 x 193.7 x 165.1 mm, sectional thickness 5.9 x 4.85 x 4.5 mm as per IS 2713 - 1980 including suitable size of CI base plate & it's fastener and GI cap on the top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH.
Supply of galvanized steel tubular pole 12 mtr Numbers long type 410SP-66 with step length 5.80-3.10- 3.10 mtr sectional dia 219.1x193.7x165.1 mm sectional thickness 5.9x4.85x4.5mm as per IS 2713-1980 including suitable size of CI base plate & it's fastener and GI cap on top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH.
Erection of tubular pole 12/14.5/16 Mtr.long Numbers including digging the pit 1/5th. of total length.
Supply and execution of CC foundation work in cum ratio 1:3:6 by cement,sand and chips of size 19mm & down. The size of the CC block will be 30cm dia with height upto the pole depth below GL and 30Cm above GL including tie muffing of DP.
Supply & erection of 2P composite polymer 33 Numbers KV ball & socket type Disc insulator ( 90 KN) with minimum creepage distance 900mm & sectional length 510mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rodand sealed to the hot dipped galvanised carbon steelend fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or asper IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL approved
Supply & erection of 2P composite polymer 33 Numbers KV Pin insulator (10 KN) with minimum creepage distance 980mm & sectional length 415 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731(1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL approved NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & erection of 2P composite polymer 11 Set KV ball & socket type Disc insulator ( 70 KN) with minimum creepage distance 320 mm & sectional length 300 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rodand sealed to the hot dipped galvanised carbon steelend fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or asper IS : 731 (1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL approved
Supply & erection of 2P composite polymer 11 Numbers KV Pin insulator (10 KN) with minimum creepage distance 340mm & sectional length 235 mm made of one piece injection molded directly to high quality, corrosion resistant, fibre glass discharge rod and sealed to the hot dipped galvanised carbon steel end fittings by bead of silicon rubber complete with all accessories conforming to IEC : 1109 standard or as per IS : 731(1971) & 2488 (Pt-II) 1974 complete with hardware fitting. Make: Rly/WBSEDCL approved
Supply & erection of 11 KV Gang Operated Air Set breakoff load disconnecting switch - 400 Amp 3 pole rocking type each pole consist of galvanised steel base, HT insulators as per BSS/ISS non ferrous knife and spring loaded contacts, arcing horns of adequate sections to break magnetising current of the transformer horizontal GI pipe of adequate length for phase separation and 25mm dia, 3.65mm thickness GI pipe of adequate length for operation from ground level and operating handle complete in both ON & OFF positions. Make: Rly/WBSEDCL approved
Supply and erection of 11KV DO fuse double Set stack channel type 200 Amps capacity. Make: Rly/WBSEDCL approved
Suply and erection of Zinc Oxide Station Class-I Set lightning arrestor suitable for 3 wire 33KV with rated voltage 30KV(RMS) and a normal discharge current rating of 10KA as per IS:4004 (1985), complete with galvanised clamping arrangement, GI bolts, nuts, washer etc. (3 Nos in a set). Make: Raychem/Oblum/Lamco/Elpro
"Supply and erection of 3 Nos station class - 1 Set Zinc oxide Lightening arrestor suitable for 3 wire 11 KV OH with rated voltage 9 KV (RMS) with normal discharge current rating of 10 KA and complete with galvanized clamping arrangement, GI bolts, nuts, washer as required conforming to IS 3070-III-1993. Make: OBLUM/REYCHEM/LAMCO/Elpro"
Supply & erection of 33 KV Gang Operated Air Set breakoff load disconnecting switch - 400Amp 3 Pole Rcking type each pole consist of galvanised steel base, HT insulators as per BSS/ISS non ferrous knife and spring loaded contacts, arcing horns. Make: Rly/WBSEDCL approved
Supply and erection of 33KV DO fuse double Set stack channel type 200 Amps. Capacity. Make: Rly/WBSEDCL approved
Supply, stringing & binding of ACSR conductor Metre Wolf of size 30/7/2.59 mm conforming to IS : 398-Pt.II-1976
Supply, stringing & binding of ACSR conductor Metre Dog of size 6/4.72+7/1.57 mm conforming to IS : 398-Pt.II-1976 NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & stringing, binding of GI wire 8 SWG for Metre guarding
Supply & stringing, binding of GI wire 10 SWG Metre for lacing
Supply & erection of Galvanised stay set for HT Set (33KV & 11KV) OH line comprising of 20 mm dia with 1.8 mtr long stay rod, anchor plate of size 30x30cmx6mm/45x45x7.5mm, turn buckle (20mmx600 mm), 20mm thimble , stay clamp, 7/10mm dia GI stay wire, Guy strain insulator of size 85 x140 mm as per ref. IS 5300/1969, and cc foundation with ratio 1:3:6 including excavation, refilling etc.
Supply & erection of danger board size 8"x6" on Numbers GI clamp made of 20x3mm for 33/11 KV showing the voltage grade, skull symbol etc.
Supply & erection of barbed wire upto height Numbers 2.5m to be fixed on pole with 2 nos. of clamps of suitable size and as per direction of Engineer Incharge at site.
Dismantling of over head alignment like Each conductor, insulator, bracket etc and handing Span over to concerned Rly/WBSEDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Uprooting of existing pole without damaging the Numbers bottom of the pole etc and handing over to concerned Rly/WBSEDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Supply & laying of class LA type CI/DI pipe 150 Metre mm dia of measureable length 5.5 mtr each length for passing of cable conforming to ISS : 1536-1989 or latest amendment of IS/ISS/IEC 1.5 m below ground level as per direction of Engineer In charge at site
"Cutting of existing erected pole (Rail/Steel Numbers tubular/Joist)."
Horizontal boring of size 100/150/200/250/300 Metre mm dia hole across railway embankment / Road at a depth of 1.5Mtr below GL by HDD Machine at Contractor's own arrangement as per direction of Engineer in charge at site.
Horizontal boring of 250/400mm dia hole across Metre Railway embankment/Road at a depth of 1.5 mtr below GL by turning a pointed instrument at contractor's own arrangement as per direction of Engineer In Charge at site.
Supply and erection of earthing by 50 mm GI Numbers pipe IS:1239/1990 (Pt-I) of 3.60mm thickness 3mtr long including construction of earth pit, RCC earth cover slab with filling/mixing of salt, charcoal etc of required quantity and earth continuty by 25x3mm GI strip with GI nuts bolts washer etc. including welding, earth resistance flag etc.
Supply and laying of additional GI Strip including Metre suitable size hole, GI nuts & bolts, washer or welded in joints wherever required as per direction of Engineer in charge at site of size 25 mm x 6 mm
Supply and laying of HDPE pipe of size 4 inch Metre (110mm outside dia), 6kgf/cm2, 6.0 mtr each length, PE-100 Grade conforming to IS : 4984/1995. Make:SWASTIK/SUPREME/NATRAJ PIPES/SKIPPER/SINTEX/SUDHAKAR/AJA Plus NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply 100x50x50x6mm bracket of suitable length clamped with above pole made by GI flat 50x5mm with 50x16mm GI bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting. As required as per direction of Engineer in charge/WBSEDCL.
Supply 75x40x40x6mm bracket of suitable size clamped with pole made by GI flat of size 50x5mm with 50x16mm bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting as per direction of Engineer in charge/WBSEDCL.
Supply & fixing of GI angle size 65x65x6mm Metre bracket of suitable sizes clamped with above pole made by GI flat 50x5mm with 50x16mm GI bolts, nuts for holding insulators, lightning arrester with necessary hole by drill including painting. As per direction of Engineer in charge/WBSEDCL.
Construction of cable trench of desired depth cum below the ground level for laying cable/pipes as per direct laying method and direction of site Engineer and filling & compacting of trench with soil with watering and ramming after laying of cable and disposal of garbage form site within a distance of 50 mtr.
Supply and laying of standard Bricks as per cum procedure for cable protection
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 33 KV (E) grade 3 core 400 sqmm size cable conforming to IS : 7098-II-2011 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables.
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 11 KV (E) grade 3 core 120 sqmm size cable conforming to IS : 7098-II-1985 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables.
Supply and laying of stranded circular Metre aluminium conductor , conductor screened with excluded semiconducting compound, XLPE insulated , installation screened with excluded semi conduction compound in combination with copper tape (0.3 KA for 1 sec), round wire steel armoured , over all PVC sheathed (A2XWY) 11 KV (E) grade 3 core 300 sqmm size cable conforming to IS : 7098-II-1985 with latest amendment. for laying below GL as per direction of Engineer incharge at site complete with crimping socket grommet etc. make: Havells/ polycab/finolex/RPG cables/RR kables. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 11KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 300 Sqmm sizes as per Raychem model no EPKT-3372 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 11KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 120 Sqmm sizes as per Raychem model no EPKT-3362 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar
Supply, fixing, fitting and testing of heat shrink Numbers outdoor termination kit for HT 33KV XLPE cable with required sockets/studs etc as per standard procedure of 3 core 400 Sqmm sizes as per Raychem model no EPKT-6374 or similar Make: MS SEAL/ Multi Pressing/ Reychem or Similar Total 21573757.00 Item- 2 Part- II (LT) S No. Item Description of Item Unit Qty Rate Amount No
To conduct survey of the locations of LT Kilometre infringement and submit drawings showing plan, elevation, CSD & BOQ for proposed LT line & diversion and modification of LT line etc prepared in AutoCad or similar platforms. Approval to be obtained from concerned SEB officials after approval of Railways (open line/Construction/RailTel). All coordination with WBSEDCL for approval of drawings shall be done by the contractor. Two set drawings of every location shall be submitted to Railways after final approval.
Supply of galvanized steel tubular pole 9 mtr Numbers long type 410SP-33 with step length 5.00-2.00- 2.00 mtr sectional dia 165.1x139.7x114.3 mtr sectional thickness 5.4x4.5x3.65 mm as per IS 2713-1980 including suitable size of CI base plate & it's fastener and GI cap on the top (Pole should be galvanized through hot dip galvanization process as per IS). Make: Skipper/BPP/JK/UTKARSH.
Erection of tubular pole 9-12 Mtr.long including Numbers digging the pit 1/5th. of total length.
Supply and execution of CC foundation work in cum ratio 1:3:6 by cement,sand and chips of size 19mm & down. The size of the CC block will be 30cm dia with height upto the pole depth below GL and 30Cm above GL including tie muffing of DP. NEW JALPAIGURI-ELECTRICAL/N F RLY CONSTRUCTION
Supply & erection of Galvanised stay set for LT Set OH line comprising of 20 mm dia. 1.8 mtr long stay rod, anchor plate of size 23x23cmx 6mm dia thick, thimble,stay clamp, 7/12SWG GI stay wire strain insulator etc.in cc foundation with ratio 1:3:6 including excavation, refilling etc
Supply, erection & commissioning of earth spike Numbers made of 20 mm dia, 1.8 mtr long GI rod including earth continuity with 6 SWG GI wire complete with GI nut, bolt, washer etc
Supply, fixing, erection & stringing of LT Aerial Metre bunched cable of 1.1 KV 3Cx50+1Cx16+1Cx35 sq mm
Supply, fixing, erection & stringing of LT AB Numbers cable anchoring clamp (galvanised)
Supply, fixing, erection & stringing of LT AB Numbers cable suspension clamp (galvanised)
Supply, fixing, erection & stringing deadend clamp for LT AB cable
Supply, fixing, erection & stringing of Insulation Numbers piercing connector (AB cable)
Supply, fixing, erection & stringing of Piercing Numbers insulation straight through joint (AB cable) 50 sq mm cable
Dismantling of over head alignment like Each conductor, insulator, bracket etc etc and Span handing over to concerned Rly/WBSEDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
Uprooting of existing pole without damaging the Numbers bottom of the pole etc and handing over to concerned Rly/WBSEDCL authority including loading, unloading, transportation etc with contrctor's own liability & cost.
"Supply, installation, testing and commissioning Numbers of integrated solar street light with 6 Mtr GI Pole, 30W LED fitting having system efficiency on min 100lumen per watt, integrated with lithium battery, solar PV Module (120W), MPPT solar charge controller aluminium pressure die cast body 3 days autonomy, auto ON/OFF, Dusk to dawn operation, sensor switch for auto diming complete with all accessories conforming to MNRE Specification and CC (1:3:6) foundation ." Total 637758.00
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Tender doc
ATTACHMENT
SPECIAL TERMS AND CONDITIONS
ATTACHMENT
PV.pdf
ATTACHMENT
GCC-2022_.pdf
ATTACHMENT
TenderDocumentHT-LT-AUB-TKG-SGUJ-NJP.pdf
ATTACHMENT
SpecialTermsandconditionHT-LTAUB-TKG-SGUJ-NJP.pdf
ATTACHMENT
ACS1to10.pdf
ATTACHMENT
ACS11.pdf
ATTACHMENT
Download all tender documents and submit your bid