Loading…
Loading…
Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 4 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
Refer Docs
EMD Value
₹12,000
Closing Date
25 Mar 2026, 3:00 pmClosed
NITHIN C S
SM (P and P)-CD
Removal of Old Rubber Lining of Phosphoric Acid Strong Storage Tank C in PA Plant
2026_FACT_901862_1
4098/2025-2026/E33212
Limited
Miscellaneous Works
Item Rate
40 days
AMBALAMEDU
This tender is issued on limited tender basis from the registered bidders of FACT (CD)
4 documents required · 4 mandatory
₹0
₹12,000
Yes
26 Mar 2026
10 Mar 2026
26 Mar 2026
10 Mar 2026
25 Mar 2026
10 Mar 2026
Removal of Old Rubber Lining of Phosphoric Acid Strong Storage Tank C in PA Plant
Removal of Old Rubber Lining of Phosphoric Acid Strong Storage Tank C in PA Plant: Old rubber lining shall be removed from complete side wall / shell areas and bottom area, roof area, base plates, flanges, dummies and top covers of inside of the phosphoric acid strong storage tank C. Removal of silica/deposited matter on shell and side walls is also under the scope of this contract. Preparation of entire surface shall be done by chipping, through cleaning by using wire brush, grinding and buffing. Approx diameter of tank is 11 m and height 10 m, aprroximate area of rubber lining to be removed is 540 Sq. m.Removed rubber lining shall be collected and transported to designated area as instructed by site in charge.
Providing and Fixing Scaffolding system inside Strong Storage Tank C in PA Plant: Providing and fixing scaffolding system for all type of works using 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical joining with cup & lock/tube & clamp system including necessary working platform etc., and maintaining it in a serviceable condition for required duration till sucessful completion of the work mentioned in sl.no.1 of the schedule and removing it there after. The scaffolding system shall be stiffened with bracings, runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineer-in-charge / Safety Department. (The elevational area of the scaffolding shall be measured for payment purpose .The payment will be made once irrespective of duration of scaffolding).
Supply/unloading and Handing over of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured PVC outer sheathed cable of size 3.5 cores x 400 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply/unloading and Handing over of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured PVC outer sheathed cable of size 3.5 cores x 50 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply/unloading and Handing over of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured PVC outer sheathed cable of size 3 cores x 50 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply/unloading and Handing over of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured PVC outer sheathed cable of size 3 cores x 35 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply/unloading and Handing over of 650/1100V, Aluminium unarmoured, earthing cable of size 1 core x 70 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply/unloading and Handing over of 650/1100V, Aluminium unarmoured, earthing cable of size 1 core x 35 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply/unloading and Handing over of 650/1100V, Copper conductor PVC insulated, armoured PVC outer sheathed cable of size 5 cores x 2.5 sq.mm. The cable shall be supplied at Q10 installation of FACT at Willingdon Island and must be unloaded as per the instruction of engineer-in-charge. Vechicles/loading and unloading shall be in contractors scope
Supply of single compression nickel plated brass cable glands suitable for 650/1100V cable of size 3.5 cores x 400 sq.mm., aluminium conductor, PVC/XLPE insulated, armoured, PVC outer sheathed. The bidder shall varify the entry thread, type of enclosure etc, to find out the actual type of gland required.
Supply of single compression nickel plated brass cable glands suitable for 650/1100V cable of size 3.5 cores x 185 sq.mm., aluminium conductor, PVC/XLPE insulated, armoured, PVC outer sheathed. The bidder shall varify the entry thread, type of enclosure etc, to find out the actual type of gland required.
Supply of single compression nickel plated brass cable glands suitable for 650/1100V cable of size 3.5 cores x 50 sq.mm., aluminium conductor, PVC/XLPE insulated, armoured, PVC outer sheathed. The bidder shall varify the entry thread, type of enclosure etc, to find out the actual type of gland required.
Supply of single compression nickel plated brass cable glands suitable for 650/1100V cable of size 3 cores x 50 sq.mm., aluminium conductor, PVC/XLPE insulated, armoured, PVC outer sheathed. The bidder shall varify the entry thread, type of enclosure etc, to find out the actual type of gland required.
Supply of single compression nickel plated brass cable glands suitable for 650/1100V cable of size 3 cores x 35 sq.mm., aluminium conductor, PVC/XLPE insulated, armoured, PVC outer sheathed. The bidder shall varify the entry thread, type of enclosure etc, to find out the actual type of gland required.
Supply of single compression nickel plated brass cable glands suitable for 650/1100V cable of size 5 cores x 2.5 sq.mm., copper conductor, PVC/XLPE insulated, armoured, PVC outer sheathed. The bidder shall varify the entry thread, type of enclosure etc, to find out the actual type of gland required.
Supply of heat srinkable cable jointing kit for armoured cable of size 3.5 cores x 300 sq.mm.
Supply of heat srinkable cable jointing kit for armoured cable of size 3 cores x 185 sq.mm.
Supply of heat srinkable cable jointing kit for armoured cable of size 3.5 cores x 120 sq.mm.
Supply of cable tags, aluminium or SS for cables (cable No. pre-fix will be given at the time of erection)
Supply and Installtion of UG LT Cable Route Marker as per engineer in charge instructions for cable identification
Laying of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured, PVC outer sheathed cable of size 3.5 cores x 400 sq.mm. through the existing cable tray at Q10 substation 25 mts / excavated trench 85 Mts and cable tray at phosphorc acid dic wall (35 Mts) as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays/racks/risers/walls/columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Laying of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured, PVC outer sheathed cable of size 3/3.5 x 50 sq.mm. through the existing and newly fabricated cable tray at various locations in Q10 berth installations of FACT, as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays /racks /risers /walls /columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Laying of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured, PVC outer sheathed cable of size 3 x 35 sq.mm. through the newly fabricated cable tray at phosphorc acid dic wall , as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays /racks /risers /walls /columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Laying of 1 core x 70 sq.mm. (2 Run x 110 Meter) unarmoured, earthing cable through the existing cable tray at Q10 substation 25 mts / excavated trench 85 Mts and cable tray at phosphorc acid dic wall (35 Meters) as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays/racks/risers/walls/columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Laying of 1 core x 35 sq.mm. unarmoured, earthing cable through the newly fabricated cable tray at phosphorc acid dic wall , as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays /racks /risers /walls /columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Laying of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured, PVC outer sheathed cable of size 5 cores x 2.5 sqmm armoured coper cable (4 run x 35 Meter) through the newly fabricated cable tray at phosphorc acid dic wall, as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays /racks /risers /walls /columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Rerouting and Laying of 650/1100V, Aluminium conductor PVC/XLPE insulated, armoured, PVC outer sheathed cable of size 3.5 x 185 sq.mm. through the excisting cable tray at phosphorc acid dic wall , as per the instruction of engineer-in-charge. The scope of work shall also include laying, dressing, fixing on cable trays /racks /risers /walls /columns clamping, tagging, tying, minor civil work etc. The rates quoted shall include supply of all accessories required such as, cable clamps, bolts, nuts, washers, cable tags, nylon ropes, etc.
Glanding and Termination of cable of size 3.5 core x 400 sq.mm. at PAT MCC Incomer and substation out going with suitable lugs and crimping.
Glanding and Termination of cable of size 3.5 core x 185 sq.mm. at PAT MCC Outgoing with suitable lugs and crimping.
Glanding and Termination of cables of size 3.5 core x 50 sq.mm. at various locations in Q10 berth installations of FACT with suitable lugs and crimping.
Glanding and Termination of cables of size 3 core x 50 sq.mm. at PAT to motor terminal (30 KW Motor, 2 Nos.) with suitable lugs and crimping.
Glanding and Termination of cables of size 3 core x 35 sq.mm. at PAT to motor terminal (15 KW Motor, 2 Nos.) with suitable lugs and crimping.
Termination of earthing cable of size 1 core x 70 sq.mm. at PAT MCC and substation with suitable lugs and crimping.
Termination of earthing cable of size 1 core x 35 sq.mm. at PAT MCC to motor terminals at acid P2O5 pump house with suitable lugs and crimping.
Glanding and Termination of cables of size 5 core x 2.5 sq.mm. at PAT MCC module to motor push button station with suitable lugs and crimping.
Jointing of armoured cable of size 3.5 cores x 300 sq.mm. using heat srinkable cable jointing kit
Jointing of armoured cable of size 3 cores x 185 sq.mm. using heat srinkable cable jointing kit
Jointing of armoured cable of size 3.5 cores x 120 sq.mm. using heat srinkable cable jointing kit
Excavation and back filling of cable trench for laying power/ earthing cables/ cable trench of not less than 300 mm width and 600 mm depth (0.6 meter depth from ground level)
Shifting of existing PAT MCC to temporary shed. The scope of work includes dismandling MCC and all incoming/outgoing cables and shifting to nearest temporary shed./reassembling/fixing the MCC and providing 1 number of incoming cable of size 3.5 cores x 400 sq.mm. and 5 numbers of out going power cables (2 no.s of 3 cores x 50 sq.mm., 2 no.s of 3 cores x 35 sq.mm., 1 no.s of 3.5 cores x 185 sq.mm.) and 4 numbers of control cables (5 cores x 2.5 sq.mm.) in newly fabricated cable tray/trench with suitable single compression gland.
stage.html
html • 0.02 MB
finance_947939.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.12 MB
BOQ_947939.xls
BOQ • 0.26 MB
Compliance.pdf
Tender Documents • 0.09 MB
SpecialConditions.pdf
Tender Documents • 0.17 MB
Tenderdocuments.pdf
Tender Documents • 1.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .