Loading…
Loading…
Tender Value
₹3.7 Cr
EMD Value
₹7.3 L
Closing Date
5 Aug 2026, 3:00 pmClosed
(A) Electrical General work for "Raising of Existing ML P.F into HL P.F of Halt Station at GBN, SATR, HOD, GPE & DLZ including Improvement/Development of Station Buildings, Sitting Benches, Mini Heds and P.F Toilets under the jurisdiction of ADEN/PRNA". (B) Electrical General work for "Raising of Existing ML & RL PF into HL P.F at RNX, KUB, JAG, KSY, SMH, BTF and JBN under ADEN/PRNA Jurisdiction".
49_2026~NFR
49_2026
Open
Works - General
6 Months
Sikar, Rajasthan
₹0
₹7.3 L
5 Aug 2026
13 Jul 2026
22 Jul 2026
A-Electrical General work for "Raising of Existing ML P.F into HL P.F of
B-Electrical General work for "Raising of Existing ML & RL PF into HL P.F
Supply, wiring, testing & commissioning of FL Numbers point/ Lamp point/Fan point (loop wiring) with angular/ batten holder by FR PVC insulated and unsheathed single core, 1.5 sq mm multistranded copper cable to be drawn through rigid PVC conduit pipe not less than 20 mm dia medium gauge including bends, joints etc. from main line under PP shed and 1 sq mm single core FR PVC insulated and unsheathed copper wire for earth continuity without controlling switch under PP shed/FOB as per instruction of Engineer incharge at site.
Supply, wiring, testing & commissioning of Numbers concealed point wiring by FR PVC insulated and unsheathed 1.5 sq mm, single core multi strand copper wire with earth continuity wire by PVC insulated and unsheathed 1 sq mm , single core multi strand copper wire concealed on wall through PVC rigid conduit pipe of dia not less than 20 mm dia heavy duty including all types of joints and bends as required, complete with 6 amps flush type controlling modular switch to be mounted on modular GI inner plate and modular mounting frame of suitable module as per requirement complete to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material. (a) FL Point/LED Tube Point/LED Recess Light Point with c/rose
(b) Lamp Point with angle holder
(c) Fan point with c/rose and 5 step fan Numbers regulator 2 M
(d) Exhaust fan point with c/rose
(e) Plug point 6 amps on board complete
Supply, wiring, testing & commissioning of Numbers c o n c e a l e d plug point on separate board complete with 2 x 6 Amp modular socket and 6/10 amps modular switch to be mounted on modular GI inner plate 6M and 6M modular mounting frame with GI box to be concealed in wall as per instruction of Engineer Incharge at site. Existing wall should be cut and re-mended to original finish by contractor's own material.
Supply, wiring, testing & commissioning of Numbers concealed 6/16 amps power plug point on separate board complete with modular 16 amps switch (with indicator) and 6/16 amps 3 pin combined shuttered socket to be mounted on modular GI inner plate 4M or suitable size with modular mounting frame to be concealed in wall as per instruction of Engineer Incharge at Site.
Supply, wiring, testing & commissioning of Numbers mobile charging point complete with 3 nos 6 A flush type controlling switch and 3 nos 6 amps, 5-pin socket and 1 no MCB DP 10 amps fitted on separate half flush MS board with hylem sheet top including provision of painted MS tray of size (8 x 6) inch for mobile holding as per instruction of Engineer incharge at site.
Supply, fixing, connection & testing of 40 Watt Numbers LED Tubelight, Surface/ Pendent mounting LED Battens in Extruded aluminium housing as per instruction of Engineer Incharge at Site.
Supply, fixing & testing and commissioning of Numbers LED 12 W B22 CDL INVERTER BULB V2 as per instruction of Engineer Incharge at Site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Fixing, testing & commissioning of ceiling fan Numbers with supply & fixing of MS clamp with hook, nut, bolt, washer etc. as per instruction of Engineer incharge at site. (Fan will be supplied by Railway)
Supply, installation, testing & commissioning of Numbers 300 mm sweep (metallic) heavy duty exhaust fan, 1400 RPM complete with fixing on wall by suitable size bolts & nuts grouted on wall as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 2.5 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 4 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 concealed in wall through PVC rigid conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, wiring & testing of main wire by 6 sq Metre mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts and earth continuity wire by 1.0 sq mm FR-LSH PVC Insulated Industrial Grade Copper Conductor Conforming to IS: 694 through PVC rigid conduit pipe/polythene pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers modular power unit complete with 32 Amp mini MCB DP "C" series 3kA , 25 amps starter, 25 Amp Socket and 25 Amp plug to be mounted on 6 module GI box, 6 module combined plate concealed on wall and wiring by 6 sq mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts with earth coninuity wire by 1 sq mm copper cable Conforming to IS: 694 to be drawn through Rigid PVC conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers Inverter Split Air Conditioners 1.5 Ton, (BEE star raying-5 star, Coil material-Copper, Echo- friendly refrigerant, Nominal cooling capacity in Ton / (kcal/hr)-1.5 Ton / 4500 kcal/hr) with all accessories as per OEM suitable for operation on 230V AC ,single phase, 50 Hz as per instruction of Engineer incharge at site. Re- mending work should be done after installation of RAC. (with 1 pair outdoor wall stand) (Industrial AC/Heavyduty AC)
Supply, installation, testing and commissioning Numbers of 7 KVA HONDA POWER Petrol start, Petrol run Power Generators And Portable Generators, Model-HONDA EU70is as per instruction of Engineer Incharge at Site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, installation, testing & commissioning of Numbers Pure Sine Wave 2400 VA Inverter with Integrated 2560 WH LiFePO4 Lithium-Ion Battery as per instruction of Engineer Incharge at Site.
U p r o o t i n g / D i s m a n t l i n g of Pole/Tubular Pole/Octagonal Pole without damaging the pole by excavation of earth & refilling of the excavated place with soil as per instruction of Engineer incharge at site.
Loading, unloading and Carrying of HT/LT Rail Numbers Pole/Tubular Pole/Octagonal Pole from site to SSE's store by contractor own arrangement.
Supply & testing of GI octagonal pole 6 mt long Numbers with foundation bolt, loop box of bakelite sheet with one 6A SP MCB and 16 sq mm stud type connector etc. The octagonal pole shall be hot dip galvanized in single dip. Technical specification of pole as following:- Height - 6 mt Top dia (A/F) - 70 mm Bottom dia (A/F) - 130 mm Sheet thickness - 3 mm Base plate (L x B x T) - (200 x 200 x 12) mm Foundation Bolt size (no.x dia) - 4 x 20 dia mm Pitch Circle Dia (PCD) - 200 mm Bolt length - 600 mm Projected Bolt Length - 100 mm .
Supply & fixing of 1 mtr GI Single arm bracket Numbers (header) and holder with Nut & bolt as per instruction of Engineer incharge at site.
Erection of Rail/Tubular/Octagonal pole to 1/5 th Numbers of its height with CC foundation from base block (30 cm x 30 cm x 15 cm) including digging & refilling of earth to a height of 30 cm above ground level as per drawing no.CEE/OH@47'40@FGA) in ratio 1:3:6 by cement sand & Chips 19 mm & down including excavation of earth.
Supply, installation, testing & commissioning of Numbers 90 Watt LED street light with pressure die-cast housing and toughened glass and individual LEDs with secondary lens optics for City Road application withIP66 ingress protection. 4kV inbuilt and 10kV external surge protecton with Top opening driver cover for easy maintenance as per instruction of Engineer incharge at site.
Supply, testing & fixing of LED Rope Light 50 Numbers Meters (Red, Yellow, Blue, Green, White as required) Waterproof, IP 65 or above as per instruction of Engineer Incharge at Site.
Supply, installation, testing & commissioning of Numbers 200 watt LED flood light luminaires complete with pressure die cast aluminium housing, IP 66, Luminous efficacy >= 120 lm/watt with heat sink feature, surge protection etc including wire connection as per instruction of Engineer incharge at site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, installation, commissioning & testing of Square LED indication station name board (Length of Foot board will be as per proportion of letter so that all the 4 side of the board will have extra space) with channel letters with 3.75 ft. in lenght with suitable widen and 4 mm projection size which inside ACP board (Brand- ALUDECOR, category- AL 33 series exterior & thikness-3 mm) with acrylic face on front and having Sumsung 5630 LED's (Shape- Lens type, operating voltage- 12 V DC, carring current-80 mA, power Dissipation- 0.96 watt, working hours-50000, case material- ABS ,protection-IP68) inside for illumination letters in English, Hindi, Bengali or regional language complete with all materials including provision of erection structure made of MS angle/channel/flat duly painted with aluminium paint over a coat of red oxide primer with CC foundation (1:3:6) of cement, sand and stone chips as required at site and as per instruction of Egnineer incharge at site.
Design, manufacture, display of wall /hanging / Square floor mounting type LED illuminated sign / Foot direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD-II/22/07/02 Date. 15.05.2023)
Erection and installation of wall / hanging / floor Square mounting type LED illuminated sign / direction Foot boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed / router cut on monomeric calendered vinyl of 70 mm thickness and shall be firmly pasted on display sheets. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The LED board shall have uniform illumination with 4-8 W / sq. ft and with brightness more than ambient light. Suitable size end cap of 1.5 mm thick SS 304 should be provided. (Signage Board should as per Railway Board Letter No. 2023/SD-II/22/07/02 Date. 15.05.2023) KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply, erection, testing & commissioning of 11 Set kV lightning arrestor polymer type with all accessories. Lighting arrestor must conform to IEC-60099-4 IS: 3070 (Part-III) (3 no in a set) as per instruction of Engineer incharge at site.
Supply, installation, testing & commissioning of Numbers poly carbonate/Thermoplastic cable cable junction box of size (155 x 210 x 92) mm with IP 67 grade protection with metric knock out with terminals as per instruction of Engineer incharge at site.
Supply, fixing, testing & commissioning of IP Numbers 66/67 thermoplastic cable junction box / loop box of size (210 x 310 x 116) mm with knockouts & 04 nos terminals as per instruction of Engineer incharge at site.
Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers long (3.6 mm thickness) GI pipe, 32x6 mm GI strip- 5 Mtrs, GI nuts, bolts including masonry materials for earthing pit, salt, charcoal, soldered end terminal etc. and construction of earth pit covered with RCC cover slab12.7 mm thickness and watering pipe as per Drg. No.- PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as per instruction of Engineer Incharge at site.
(a) Supply, installation, testing & commissioning Set of oudoor type weather proof sheded feeder pillar box of suitable size made of powder coated 14 SWG MS/CRCA sheet, angle, flat etc. The feeder pillar box four legs should be grounted on CC foundation (1:3:6). Cable entry should have PVC glands. Feeder pillar box should have double door system with locking arrangement with fixing of rubber gasket for protection of entry of dust and water alongwith supply and fixing of following MCCB as per instruction of Engineer Incharge at site.
(b) MCCB FP 200 amps, 25 kA, Ics=100% Icu
(c) MCCB FP 125 amps, 36 kA, Ics=100% Icu
(d) MCCB FP 63 amps, 25 kA, Ics=100% Icu
(e) Copper bus bar 200 amps made of Set electrolytic grade copper consisting of 4 bars ( 3 Ph and Neutral ) ( Bus bar should have insulation cover)
Laying, commissioning & testing of HT/LT Metre XLPE/PVC cable of different sizes partly along the pole and partly through ground in cable trench by excavation of ground below 1.5 mt from ground level with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt. Loading, Unloading & Carrying of cable to actual work site by contractor's own arrangement. (Aluminium Crimping Socket should be provided for each Cable Termination). (Cable will be supplied by Railway)
Cable Trench Cutting of LT XLPE insulated Metre armoured, aluminium conductor cable, making good the damages, end terminations with aluminium crimping socket/plugs, provisions of cable route markers, testing & commissioning etc. as required as per technical specifications of different size armoured cable as per instruction of Engineer Incharge at Site. KATIHAR DIVISION-ELECTRICAL/N F RLY
Supply and spreading of gravel/ballast in the cum swithing yard as per instruction of Engineer incharge at site. (Removal and cleaning of existing gravels and thereafter new gravels should be filled if any) (Outdoor switch-yard areas are usually covered with about 10 cm of gravel of crushed rock of 40 mm size)
Supply and repainting of Power supply assets Sqm like GI structure, Fencing panels, fencing uprights, barbed wires, SWS and tubular poles at sub-station with aluminium paint as per site requirement as per instruction of Engineer Incharge at Site. Total 15729595.00 Schedule B-Electrical General work for "Raising of Existing ML & RL PF into HL P.F at RNX, KUB, JAG,
KSY, SMH, BTF and JBN under ADEN/PRNA Jurisdiction".
Item- 1 Please see item breakup for details.
S No. Item Description of Item Unit Qty Rate Amount
1 1 Supply, wiring, testing & commissioning of FL Numbers 500.00 184.00 92000.00
point/ Lamp point/Fan point (loop wiring) with
angular/ batten holder by FR PVC insulated and
unsheathed single core, 1.5 sq mm
multistranded copper cable to be drawn
through rigid PVC conduit pipe not less than 20
mm dia medium gauge including bends, joints
etc. from main line under PP shed and 1 sq mm
single core FR PVC insulated and unsheathed
copper wire for earth continuity without
controlling switch under PP shed/FOB as per
instruction of Engineer incharge at site.
2 2 Supply, fixing, connection, testing & Numbers 500.00 4503.00 2251500.00
commissioning of Surface/Suspended mounted
LED Trunking Batten 40 watt, extruded
aluminum housing provided for efficient heat
dissipation with polycarbonate diffuser & Built-
In electronic driver. IP 54, CRI >=80, THD(%)
<=10, CCT. 6500 K Power Factor 0.95,
Operating temperature: -10 C to +50 C,
Operating voltage range: 165 V - 270 V,
Average life 50000 hours, LED lumen efficacy
145 lm/W with a viewing angle of 120, Powered
by built-in electronic driver (SMPS based
constant current supply) with Output
Open/Short-circuit, Thermal fold back, 440V 8
Hrs protection, Surge protection 4 KV & others
safety test as per IS:15885 Part 2/Sec 13.
ACETRUNKINGADVS40WLED865PSYMBOPCWHT.
3 3 Supply, wiring, testing & commissioning of Numbers 420.00 797.00 334740.00
concealed point wiring by FR PVC insulated and
unsheathed 1.5 sq mm, single core multi strand
copper wire with earth continuity wire by PVC
insulated and unsheathed 1 sq mm , single core
multi strand copper wire concealed on wall
through PVC rigid conduit pipe of dia not less
than 20 mm dia heavy duty including all types
of joints and bends as required, complete with 6
amps flush type controlling modular switch to
be mounted on modular GI inner plate and
modular mounting frame of suitable module as
per requirement complete to be concealed in
wall as per instruction of Engineer Incharge at
site. Existing wall should be cut and re-mended
to original finish by contractor's own material.
(a) FL Point/LED Tube Point/LED Recess Light
Point with c/rose
KATIHAR DIVISION-ELECTRICAL/N F RLY
5 5 (c) Fan point with c/rose and 5 step fan Numbers 77.00 1450.00 111650.00
7 7 (e) Plug point 6 amps on board complete Numbers 98.00 361.00 35378.00
8 8 Supply, wiring, testing & commissioning of Numbers 77.00 737.00 56749.00
c o n c e a l e d plug point on separate board
complete with 2 x 6 Amp modular socket and
6/10 amps modular switch to be mounted on
modular GI inner plate 6M and 6M modular
mounting frame with GI box to be concealed in
wall as per instruction of Engineer Incharge at
site. Existing wall should be cut and re-mended
to original finish by contractor's own material.
9 9 Supply, wiring, testing & commissioning of Numbers 77.00 855.00 65835.00
concealed 6/16 amps power plug point on
separate board complete with modular 16 amps
switch (with indicator) and 6/16 amps 3 pin
combined shuttered socket to be mounted on
modular GI inner plate 4M or suitable size with
modular mounting frame to be concealed in wall
as per instruction of Engineer Incharge at Site.
10 10 Supply, wiring, testing & commissioning of Numbers 77.00 231.00 17787.00
mobile charging point complete with 3 nos 6 A
flush type controlling switch and 3 nos 6 amps,
5-pin socket and 1 no MCB DP 10 amps fitted
on separate half flush MS board with hylem
sheet top including provision of painted MS tray
of size (8 x 6) inch for mobile holding as per
instruction of Engineer incharge at site.
11 11 Supply, fixing, connection & testing of 40 Watt Numbers 500.00 1676.00 838000.00
LED Tubelight, Surface/ Pendent mounting LED
Battens in Extruded aluminium housing as per
instruction of Engineer Incharge at Site.
12 12 Supply, fixing & testing and commissioning of Numbers 200.00 670.00 134000.00
LED 12 W B22 CDL INVERTER BULB V2 as per
instruction of Engineer Incharge at Site.
13 13 Fixing, testing & commissioning of ceiling fan Numbers 40.00 46.00 1840.00
with supply & fixing of MS clamp with hook, nut,
bolt, washer etc. as per instruction of Engineer
incharge at site. (Fan will be supplied by
14 14 Supply, installation, testing & commissioning of Numbers 30.00 2824.00 84720.00
300 mm sweep (metallic) heavy duty exhaust
fan, 1400 RPM complete with fixing on wall by
suitable size bolts & nuts grouted on wall as per
instruction of Engineer incharge at site.
15 15 Supply, wiring & testing of main wire by 2.5 sq Metre 8050.00 75.00 603750.00
mm, Single Core FR-LSH PVC Insulated
Industrial Grade Copper Conductor
(Unsheathed) Flexible Cables, 1100 Volts and
earth continuity wire by 1.0 sq mm FR-LSH PVC
Insulated Industrial Grade Copper Conductor
Conforming to IS: 694 concealed in wall through
PVC rigid conduit pipe not less than 20 mm dia
as per instruction of Engineer incharge at site.
16 16 Supply, wiring & testing of main wire by 4 sq Metre 6020.00 87.00 523740.00
mm, Single Core FR-LSH PVC Insulated
Industrial Grade Copper Conductor
(Unsheathed) Flexible Cables, 1100 Volts and
earth continuity wire by 1.0 sq mm FR-LSH PVC
Insulated Industrial Grade Copper Conductor
Conforming to IS: 694 concealed in wall through
PVC rigid conduit pipe not less than 20 mm dia
as per instruction of Engineer incharge at site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
17 17 Supply, wiring & testing of main wire by 6 sq Metre 3010.00 100.00 301000.00
mm, Single Core FR-LSH PVC Insulated
Industrial Grade Copper Conductor
(Unsheathed) Flexible Cables, 1100 Volts and
earth continuity wire by 1.0 sq mm FR-LSH PVC
Insulated Industrial Grade Copper Conductor
Conforming to IS: 694 through PVC rigid conduit
pipe/polythene pipe not less than 20 mm dia as
per instruction of Engineer incharge at site.
18 18 Supply, installation, testing & commissioning of Numbers 15.00 1193.00 17895.00
modular power unit complete with 32 Amp mini
MCB DP "C" series 3kA , 25 amps starter, 25
Amp Socket and 25 Amp plug to be mounted on
6 module GI box, 6 module combined plate
concealed on wall and wiring by 6 sq mm,
Single Core FR-LSH PVC Insulated Industrial
Grade Copper Conductor (Unsheathed) Flexible
Cables, 1100 Volts with earth coninuity wire by
1 sq mm copper cable Conforming to IS: 694 to
be drawn through Rigid PVC conduit pipe not
less than 20 mm dia as per instruction of
Engineer incharge at site.
19 19 Supply, installation, testing & commissioning of Numbers 15.00 54091.00 811365.00
Inverter Split Air Conditioners 1.5 Ton, (BEE star
raying-5 star, Coil material-Copper, Echo-
friendly refrigerant, Nominal cooling capacity in
Ton / (kcal/hr)-1.5 Ton / 4500 kcal/hr) with all
accessories as per OEM suitable for operation
on 230V AC ,single phase, 50 Hz as per
instruction of Engineer incharge at site. Re-
mending work should be done after installation
of RAC. (with 1 pair outdoor wall stand)
(Industrial AC/Heavyduty AC)
20 20 Supply, installation, testing & commissioning of Numbers 40.00 6632.00 265280.00
Wall Air Circulator Fan (Industrial fan), 600 mm
sweep (Speed- 1440 RPM, Max. wattage-180
Watt, Air delivery > 16000 CMH,
Aerodynamically designed aluminum alloy
single piece blades for high air delivery> 16500
CMH, conforms to IS 2997-1964 standards) with
suitable fixing arrangement on wall as per
instruction of Engineer incharge at site.
21 21 Supply, installation, testing & commissioning of Numbers 3.00 100011.00 300033.00
Aquaguard Institutional Water cooler-cum-
Purifier with Storage Capacity 120 Ltrs. &
Option for Cold & Normal Purified Water. a)
Approx. Dimensions : 750 mm (W) x 570 mm
(D) x 1350 mm (H) b) Power rating : 850 ± 10%
w a t t c) Water flow capacity : 80 LPH
d)Operating power supply : 170-260 VAC, 1 ph
e)No. of stages for filter-cum-purifier : 3 nos. f)
Storage capacity : 120 Ltr g) Nos. of Faucets :
03 nos. h) Body material: Front SS 304 and the
rest in Pre-coated steel i) Refrigerant used:
Freon 22 or latest
22 22 Supply, welding, making & erection of Job 3.00 11043.00 33129.00
fencing/cage of approx size 7 ft x 4.5 ft with
provision of two fold gate with locking
arrangement and leg by providing suitable size
MS angle (50 x 50 x 6 mm), MS flat (25 x 5
mm), MS sheet (1.6 mm thickness), hinges,
aldrops etc. with supply of paint and painting
the whole structure including CC work (1:3:6)
for grouting of four legs as per instruction of
Engineer incharge at site. (For protection of
KATIHAR DIVISION-ELECTRICAL/N F RLY
23 23 Supply, installation, testing and commissioning Numbers 5.00 243360.00 1216800.00
of 7 KVA HONDA POWER Petrol start, Petrol run
Power Generators And Portable Generators,
Model-HONDA EU70is as per instruction of
Engineer Incharge at Site.
24 24 Supply, installation, testing & commissioning of Numbers 25.00 59202.00 1480050.00
Pure Sine Wave 2400 VA Inverter with
Integrated 2560 WH LiFePO4 Lithium-Ion
Battery as per instruction of Engineer Incharge
25 25 U p r o o t i n g / D i s m a n t l i n g of HT/LT Rail Numbers 245.00 405.00 99225.00
Pole/Tubular Pole/Octagonal Pole without
damaging the pole by excavation of earth &
refilling of the excavated place with soil as per
instruction of Engineer incharge at site.
26 26 Loading, unloading and Carrying of HT/LT Rail Numbers 200.00 249.00 49800.00
Pole/Tubular Pole/Octagonal Pole from site to
SSE's store by contractor own arrangement.
27 27 Supply & testing of GI octagonal pole 6 mt long Numbers 60.00 14193.00 851580.00
with foundation bolt, loop box of bakelite sheet
with one 6A SP MCB and 16 sq mm stud type
connector etc. The octagonal pole shall be hot
dip galvanized in single dip. Technical
specification of pole as following:- Height - 6 mt
Top dia (A/F) - 70 mm Bottom dia (A/F) - 130
mm Sheet thickness - 3 mm Base plate (L x B x
T) - (200 x 200 x 12) mm Foundation Bolt size
(no.x dia) - 4 x 20 dia mm Pitch Circle Dia (PCD)
- 200 mm Bolt length - 600 mm Projected Bolt
Length - 100 mm .
28 28 Supply & fixing of 1 mtr GI Single arm bracket Numbers 60.00 1615.00 96900.00
(header) and holder with Nut & bolt as per
instruction of Engineer incharge at site.
29 29 Erection of Rail/Tubular/Octagonal pole to 1/5 th Numbers 60.00 1712.00 102720.00
of its height with CC foundation from base block
(30 cm x 30 cm x 15 cm) including digging &
refilling of earth to a height of 30 cm above
ground level as per drawing
no.CEE/OH@47'40@FGA) in ratio 1:3:6 by
cement sand & Chips 19 mm & down including
excavation of earth.
30 30 Supply, installation, testing & commissioning of Numbers 120.00 8823.00 1058760.00
90 Watt LED street light with pressure die-cast
housing and toughened glass and individual
LEDs with secondary lens optics for City Road
application withIP66 ingress protection. 4kV
inbuilt and 10kV external surge protecton with
Top opening driver cover for easy maintenance
as per instruction of Engineer incharge at site.
31 31 Supply, testing & fixing of LED Rope Light 50 Numbers 200.00 7237.00 1447400.00
Meters (Red, Yellow, Blue, Green, White as
required) Waterproof, IP 65 or above as per
instruction of Engineer Incharge at Site.
KATIHAR DIVISION-ELECTRICAL/N F RLY
32 32 Supply, installation, commissioning & testing of Square 210.00 1772.00 372120.00
LED indication station name board (Length of Foot
board will be as per proportion of letter so that
all the 4 side of the board will have extra space)
with channel letters with 3.75 ft. in lenght with
suitable widen and 4 mm projection size which
inside ACP board (Brand- ALUDECOR, category-
AL 33 series exterior & thikness-3 mm) with
acrylic face on front and having Sumsung 5630
LED's (Shape- Lens type, operating voltage- 12
V DC, carring current-80 mA, power Dissipation-
0.96 watt, working hours-50000, case material-
ABS ,protection-IP68) inside for illumination
letters in English, Hindi, Bengali or regional
language complete with all materials including
provision of erection structure made of MS
angle/channel/flat duly painted with aluminium
paint over a coat of red oxide primer with CC
foundation (1:3:6) of cement, sand and stone
chips as required at site and as per instruction
of Egnineer incharge at site.
33 33 Design, manufacture, display of wall /hanging / Square 208.00 2868.00 596544.00
floor mounting type LED illuminated sign / Foot
direction boards in half elliptical shape. The
display sheet shall be of unbreakable 040
translucent polycarbonate sheet of 2 mm
thickness. The text / graphics matter visibility
shall not be less than 160 deg. The approved
colour text and graphics shall be printed / router
cut on monomeric calendered vinyl of 70 mm
thickness and shall be firmly pasted on display
sheets. The mounting arrangement shall be
hanging, wall mounting, ceiling mounting, pole
mounting or floor mounting and as per site
requirement. The signage shall have the
integral mounting arrangements with sturdy
structural frame and ACP cladding on the back
side of the signage to avoid rusting and entry of
dust. The LED board shall have uniform
illumination with 4-8 W / sq. ft and with
brightness more than ambient light. Suitable
size end cap of 1.5 mm thick SS 304 should be
provided. (Signage Board should as per Railway
Board Letter No. 2023/SD-II/22/07/02 Date.
34 34 Erection and installation of wall / hanging / floor Square 208.00 287.00 59696.00
mounting type LED illuminated sign / direction Foot
boards in half elliptical shape. The display sheet
shall be of unbreakable 040 translucent
polycarbonate sheet of 2 mm thickness. The
text/graphics matter visibility shall not be less
than 160 deg. The approved colour text and
graphics shall be printed / router cut on
monomeric calendered vinyl of 70 mm
thickness and shall be firmly pasted on display
sheets. The mounting arrangement shall be
hanging, wall mounting, ceiling mounting, pole
mounting or floor mounting and as per site
requirement. The signage shall have the
integral mounting arrangements with sturdy
structural frame and ACP cladding on the back
side of the signage to avoid rusting and entry of
dust. The LED board shall have uniform
illumination with 4-8 W / sq. ft and with
brightness more than ambient light. Suitable
size end cap of 1.5 mm thick SS 304 should be
provided. (Signage Board should as per Railway
Board Letter No. 2023/SD-II/22/07/02 Date.
KATIHAR DIVISION-ELECTRICAL/N F RLY
35 35 Supply, installation, testing & commissioning of Numbers 12.00 7703.00 92436.00
1 HP, 0.75 kW self primimg monoblock pump
motor set complete, suitable for 220 Volt, 50
Hz, 1 phase supply as per instruction of
EngineerIncharge at Site.
36 36 Supply, erection, testing & commissioning of 11 Set 25.00 5174.00 129350.00
kV lightning arrestor polymer type with all
accessories. Lighting arrestor must conform to
IEC-60099-4 IS: 3070 (Part-III) (3 no in a set) as
per instruction of Engineer incharge at site.
37 37 Supply, installation, testing & commissioning of Numbers 140.00 1292.00 180880.00
poly carbonate/Thermoplastic cable cable
junction box of size (155 x 210 x 92) mm with
IP 67 grade protection with metric knock out
with terminals as per instruction of Engineer
incharge at site.
38 38 Supply, fixing, testing & commissioning of IP Numbers 105.00 5291.00 555555.00
66/67 thermoplastic cable junction box / loop
box of size (210 x 310 x 116) mm with
knockouts & 04 nos terminals as per instruction
of Engineer incharge at site.
39 39 Supply & Erection of earth by 50 mm dia 3 Mtrs. Numbers 200.00 4349.00 869800.00
long (3.6 mm thickness) GI pipe, 32x6 mm GI
strip- 5 Mtrs, GI nuts, bolts including masonry
materials for earthing pit, salt, charcoal,
soldered end terminal etc. and construction of
earth pit covered with RCC cover slab12.7 mm
thickness and watering pipe as per Drg. No.-
PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and
as per instruction of Engineer Incharge at site.
40 40 (a) Supply, installation, testing & commissioning Set 10.00 5070.00 50700.00
of oudoor type weather proof sheded feeder
pillar box of suitable size made of powder
coated 14 SWG MS/CRCA sheet, angle, flat etc.
The feeder pillar box four legs should be
grounted on CC foundation (1:3:6). Cable entry
should have PVC glands. Feeder pillar box
should have double door system with locking
arrangement with fixing of rubber gasket for
protection of entry of dust and water alongwith
supply and fixing of following MCCB as per
instruction of Engineer Incharge at site.
electrolytic grade copper consisting of 4 bars ( 3
Ph and Neutral ) ( Bus bar should have
insulation cover)
45 45 Laying, commissioning & testing of HT/LT Metre 10000.00 55.00 550000.00
XLPE/PVC cable of different sizes partly along
the pole and partly through ground in cable
trench by excavation of ground below 1.5 mt
from ground level with suitable fixing
arrangement by MS clamp of size 50x6 mm and
suitable size nut, bolt. Loading, Unloading &
Carrying of cable to actual work site by
contractor's own arrangement. (Aluminium
Crimping Socket should be provided for each
Cable Termination). (Cable will be supplied by
KATIHAR DIVISION-ELECTRICAL/N F RLY
46 46 Cable Trench Cutting of LT XLPE insulated Metre 10000.00 338.00 3380000.00
armoured, aluminium conductor cable, making
good the damages, end terminations with
aluminium crimping socket/plugs, provisions of
cable route markers, testing & commissioning
etc. as required as per technical specifications
of different size armoured cable as per
instruction of Engineer Incharge at Site.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .