| 1.00 | Comprehensive Qutarly maintence/servicing checking caliberation testing of existing fire alram panel, connected wiring system, detectors and devices of any type as per existing on site, Programming and configuration check installed in Makarpura and Harni air field/darjipura AF Stn Vadodara. The detail scope of work consists of the following :-
(i) Cleaning, inspecting, checking and repairing if required all the equipments of fire detection system.
(ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge.
(iii) The contractor shall submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge on monthly basis.
(iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep.
(v) Emergency visit shall be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost.
(vi) Material required for replacement shall be measured and paid separately under respective items of this schedule as 'Supply and fixing' and labour component for the same is not included in comprehensive maintanance contractor shall quote the rate accordingly.
(vii) Testing of entire fire alarm system and rectification of fault complete to the entire satisfaction of engr-in-charge all as specified and directed .
(i) All Spares inclusive in the quoted rate excluding items here-in-after mentioned | 36 | Each system per Three Month | 6,515 ₹2,34,540 | 5,500 ₹1,98,000 Lowest |
| 2.00 | Taking down unserviceable DCP type portable fire extinguiser 6 kg ISI marked from the existing locations along with existing arrangements, Supply and fixing new DCP 6 Kg fire extinguisher with clamp,nut and bolt etc for ABC class of fire in and including proper fixing in the installtions complete all as specified and directed. | 5 | Each Job | 7,110 ₹35,550 | 5,500 ₹27,500 Lowest |
| 3.00 | Taking down unserviceable DCP type portable fire extinguiser 4 kg ISI marked from the existing locations along with existing arrangements, Supply and fixing new DCP 4 Kg fire extinguisher with clamp,nut and bolt etc for ABC class of fire in and including proper fixing in the installtions complete all as specified and directed.
Make for Sl item No. 2 to 3 - Safety Plus/Ceasefire/Safex | 5 | Each Job | 5,105 ₹25,525 | 4,500 ₹22,500 Lowest |
| 4.00 | Supply and fix Fire alarm conventional control panel complying with BS EN 54 Single loop panel of 4 zone upto 96 detector and module complete all as specified and directed | 8 | Each | 35,122 ₹2,80,976 | 32,000 ₹2,56,000 Lowest |
| 5.00 | Supply and fix Detectors Complying with and type certified to EN-45 Addressable type multisensor detector with heat and smoke combination Photoelectric / Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed. | 45 | Each | 3,110 ₹1,39,950 | 2,600 ₹1,17,000 Lowest |
| 6.00 | Supply and fixing MCP conventional ABS complete complete all as specified and directed. | 20 | Each | 1,655 ₹33,100 | 1,600 ₹32,000 Lowest |
| 7.00 | Supply and fixing Electronic Hooter 24 Volts DC complete all as specified and directed. | 20 | Each | 1,565 ₹31,300 | 1,520 ₹30,400 Lowest |
| 8.00 | Supply and fixing PVC insulated heavy duty armoured copper conductor of size 2x1.5 sqmm cable for fire alarm complete all as specified and directed. | 380 | RM | 156 ₹59,280 | 120 ₹45,600 Lowest |
| 9.00 | M & L for VRLA(Valve regulated lead acide)/Sealed Lead acid maintenace free battery cap 12 V/07 Ah for fire alarm system complete all as specified and directed. | 25 | Each | 1,425 ₹35,625 | 1,400 ₹35,000 Lowest |
| 10.00 | Comprehensive maintenance (Consisting of normal repairs) preventing maint as follows Ones in three months for 9 month of electrically operated travelling (EOT) Flame Proof cranes of capacity 5 Ton make: Rock well & Crane including at site complete all as specified and directed by Engineer -in- Charge
Note: - (a). Replacement of the unserviceable spare parts shall be measured and paid sepreatly.
(i) Long Traverse
(a). Cleaning of Gear box and oil level checking rectification of leakages if any.
(b). Checking Assembly vibration.
(c). Brake Adjustment.
(d). Long Traverse wheel checking for any noise.
(e). Geared couplings - grease checking and nut tightening.
(f). Checking of hydraulic oil in thristor brake
(g). Checking of electric motor connections
(h). To check the cut off at extreme end with limit switch.
(i). Checking and greasing \ oiling of plumber block.
(j). Long traverse. | 6 | Job | 6,509 ₹39,054 | 6,500 ₹39,000 Lowest |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
16 Aug 2025, 6:00 pmClosed
GE (AF) BARODA ,DARJIPURA
GE (AF) BARODA ,DARJIPURA , GUJARAT-390022
REPAIR AND MAINTENACE OF FIRE DETECTION SYSTEM, EOT CRANE, STABILIZER CERTAIN MISC WORKS AT AFS VADODARA
2025_MES_721479_1
8990/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
MAKARPURA
AS PER NOTICE OF TENDER
8 documents required · 8 mandatory
₹500
Yes
GE (AF) BARODA
₹40,000
Yes
11 Oct 2025
19 Jul 2025
18 Aug 2025
19 Jul 2025
16 Aug 2025
2 Aug 2025
19 Jul 2025 - 2 Aug 2025
Amount
Comprehensive Qutarly maintence/servicing checking caliberation testing of existing fire alram panel, connected wiring system, detectors and devices of any type as per existing on site, Programming and configuration check installed in Makarpura and Harni air field/darjipura AF Stn Vadodara. The detail scope of work consists of the following :- (i) Cleaning, inspecting, checking and repairing if required all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor shall submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge on monthly basis. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit shall be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Material required for replacement shall be measured and paid separately under respective items of this schedule as 'Supply and fixing' and labour component for the same is not included in comprehensive maintanance contractor shall quote the rate accordingly. (vii) Testing of entire fire alarm system and rectification of fault complete to the entire satisfaction of engr-in-charge all as specified and directed . (i) All Spares inclusive in the quoted rate excluding items here-in-after mentioned
Taking down unserviceable DCP type portable fire extinguiser 6 kg ISI marked from the existing locations along with existing arrangements, Supply and fixing new DCP 6 Kg fire extinguisher with clamp,nut and bolt etc for ABC class of fire in and including proper fixing in the installtions complete all as specified and directed.
Taking down unserviceable DCP type portable fire extinguiser 4 kg ISI marked from the existing locations along with existing arrangements, Supply and fixing new DCP 4 Kg fire extinguisher with clamp,nut and bolt etc for ABC class of fire in and including proper fixing in the installtions complete all as specified and directed. Make for Sl item No. 2 to 3 - Safety Plus/Ceasefire/Safex
Supply and fix Fire alarm conventional control panel complying with BS EN 54 Single loop panel of 4 zone upto 96 detector and module complete all as specified and directed
Supply and fix Detectors Complying with and type certified to EN-45 Addressable type multisensor detector with heat and smoke combination Photoelectric / Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed.
Supply and fixing MCP conventional ABS complete complete all as specified and directed.
Supply and fixing Electronic Hooter 24 Volts DC complete all as specified and directed.
Supply and fixing PVC insulated heavy duty armoured copper conductor of size 2x1.5 sqmm cable for fire alarm complete all as specified and directed.
M & L for VRLA(Valve regulated lead acide)/Sealed Lead acid maintenace free battery cap 12 V/07 Ah for fire alarm system complete all as specified and directed.
Comprehensive maintenance (Consisting of normal repairs) preventing maint as follows Ones in three months for 9 month of electrically operated travelling (EOT) Flame Proof cranes of capacity 5 Ton make: Rock well & Crane including at site complete all as specified and directed by Engineer -in- Charge Note: - (a). Replacement of the unserviceable spare parts shall be measured and paid sepreatly. (i) Long Traverse (a). Cleaning of Gear box and oil level checking rectification of leakages if any. (b). Checking Assembly vibration. (c). Brake Adjustment. (d). Long Traverse wheel checking for any noise. (e). Geared couplings - grease checking and nut tightening. (f). Checking of hydraulic oil in thristor brake (g). Checking of electric motor connections (h). To check the cut off at extreme end with limit switch. (i). Checking and greasing \ oiling of plumber block. (j). Long traverse.
(ii) Cross Traverse (a). Cleaning of Gear box and oil level checking rectification of leakages if any. (b). Checking Assembly vibration. (c). Brake Adjustment. (d). Long Traverse wheel checking for any noise. (e). Geared couplings - grease checking and nut tightening. (f). Checking of hydraulic oil in thristor brake (g). Checking of electric motor connections (h). To check the cut off at extreme end with limit switch. (i). Checking and greasing \ oiling of plumber block. (j). Cross traverse.
(iii) Hoist Motion (a). Gear box oil level check & rectification of leakages. (b). Checking Assembly vibration. (c). Brake Adjustment. (d). Checking for the main bearing of the rope drum including graesing. (e). Geared couplings - grease checking and nut tightening. (f). Checking of hydraulic oil in thristor brake. (g). Checking of electric motor connections. (h). Checking wire rope & greasing. (i). Adjustment of rotory limit switch. (j). Baering graese \ oiling in bottom block \ hock. (iv). Electrical Network (a). Checking the contactor for overheating and flashing. (b). general checking of contacts and connections. (c). Cleaning of control panels. (d). Checking of connection AC Drive and othher drives for smooth functioning of the same. (v). Down shop lead (DSL) (a). Checking the alingment and rectification. (b). Cleaning of the moving \ slidding objects.
Comprehensive maintenance (Consisting of normal repairs) preventing maint as follws Ones in three months of Hand operated travelling (HOT) Flame Proof cranes of capacity 5 Ton make: Rock well & Cranx including at site complete all as specified and directed by Engineer -in- Charge Note: - (a). Replacement of the unserviceable spare parts shall be measured and paid sepreatly. (i) Long Traverse (a). Cleaning of Gear box and oil level checking rectification of leakages if any. (b). Checking Assembly vibration. (c). Brake Adjustment. (d). Long Traverse wheel checking for any noise. (e). Geared couplings - grease checking and nut tightening. (f). Checking of hydraulic oil in thristor brake (h). To check the cut off at extreme end with limit switch. (i). Checking and greasing \ oiling of plumber block. (j). Long traverse.
(ii) Cross Traverse (a). Cleaning of Gear box and oil level checking rectification of leakages if any. (b). Checking Assembly vibration. (c). Brake Adjustment. (d). Long Traverse wheel checking for any noise. (e). Geared couplings - grease checking and nut tightening. (f). Checking of hydraulic oil in thristor brake (h). To check the cut off at extreme end with limit switch. (i). Checking and greasing \ oiling of plumber block. (j). Cross traverse.
(iii) Hoist Motion (a). Gear box oil level check & rectification of leakages. (b). Checking Assembly vibration. (c). Brake Adjustment. (d). Checking for the main bearing of the rope drum including graesing. (e). Geared couplings - grease checking and nut tightening. (f). Checking of hydraulic oil in thristor brake. (g). Checking of electric motor connections. (h). Checking wire rope & greasing. (i). Adjustment of rotory limit switch. (j). Baering graese \ oiling in bottom block \ hock. (iv). Electrical Network (a). Checking the contactor for overheating and flashing. (b). general checking of contacts and connections. (c). Cleaning of control panels. (d). Checking of connection AC Drive and othher drives for smooth functioning of the same. (v). Down shop lead (DSL) (a). Checking the alingment and rectification. (b). Cleaning of the moving \ slidding objects.
Attending Complaints and rectification of electronic, electrical and mechanical defects by authorized experience technician for flame proof EOT/HOT crane of capacity 5 Ton/2 TON, Checking of uncerviciable electrical system and find out defect of control wiring in control panel (Hoist, Long Travel, Cross Travel) Control Switch Limit Switch Rectified the seme and make serviciable complete and testing thereafter complete all as specified and directed by engineer - in - charge. Note: - (a). The complaint shall be notified to the contactor by engineer - in - charge / JE E&M telephonically / personnaly / by SMS recorded in the register mentioned for the purpose. (b). Contactor shall make neccessary arrangement to attend the complaint. (c). Cost of any minor nature of repair / replacement of petty item such as nuts, bolts, washers, screws, piece of electrical cable upto 0.5 meter length etc, is deemed included in the unit rate quoted by the contractor. (d). Any other major item / repair required for the rectification shall be measured and paid seperately under respective item of the schedule. (e). Complaint number, date, location, date of rectification shall be entered in MB for payment purpose.
M&L for annual load testing electrically operated travelling(EOT) crane upto 25 mtrs span 0.5 TON and up to 6 TON capacity including requirment of load and transportation of load material and necessary equipments for testing & including preperation of old steel surfaces and appying one coat of synthetic enamel paint complete all as specified and directed.
- Ditto - all as per item No.13.00 here in before but of hand operated ( HOT ) up to 10 mtrs span of capacity up to 2.5 Ton complete all as specified and directed.
Repair and making true alignment of crane track and track joint by means of welding, heating , cutting, grouting and fixing of new pressure plate of bolts including necessary plastering, repairing and leveling of crane track including grouting in PCC(1:2:4) and required new rolled mild steel angle (Fe-410-W, grade E-250, quality-B) of size 40 x 40 x5 mm at edge of trench including testing for smooth functioning complete all as specified and directed.
Supply only tripple spur gear chain pully block ( hand operative) capacity 2 Ton maximum hook 5 mtrs on from ground travel suitable for operation from floor including test certificate complete all as specified and directed.
Supply only push button switch for EOT crane with elements 6 Amps 415 volts 50 Hz complete all as specified and directed.
Supply only Geared rotary limit switch 3 phase 415 volt 50 Hz, 10 Amps No -22-1210-2 KV for EOT crane of any capacity suitable for any motion complete all as specified and directed.
Supply only TP contact, 3 phase, 20 Amps with coil complete all as specified and directed.
Supply only Carbon brush for clutch for micro movement of EOT crane complete all as specified and directed.
Supply only push button switch for EOT crane with elements 6 Amps 415 volts 50 Hz complete all as specified and directed.
S&F Electro hydraulic thrust break operated model 140321, drum dia 200mm, shoe width 70mm thurst 18 Kg strock 50mm 3 phase 400 / 400 volt, 50 cycle, 150 watt breaking torque 9 Kg maximam number of operation 360 per hour complete all as specified and directed. Make speed 'O' contral/stron/ sterling control or equivalent.
M&L for Comprehensive monthly maintence of 30 KVA/10KVA UPS system installed Makarpura. The detail scope of work consists of the following :- (i) Execute diagnostics and physical checks. (ii) Examine, clean, test, all equipment as required and repair parts as and when required. (iii) Measurement of UPS parameters like input/output voltage, frequency, current, frequency, room temperature etc. (iv) Battery Parameters like voltage, current and other relevant parameters. (v) Ensure dust free and controlled temperature conditions. (vi) The corrective maintenance may require multiple visits to site (vii) Check all Equipment LED LCD display board if any fault found to be rectified in the same cost. (viii) Checking of servicibility of MCB/MCCB if found unserviceable to be replace without any extra cost. (ix) Checking of UPS fuse. If found us to be replaced without any extra cost.. (x) Keeping of servicibility of UPS is the responsibility of the contractor for the entire contract period. Note : Response time should be not more than 24 hours from the time of receipt of complaint on any working day between 9 AM to 6 PM.
Attending Complaints and rectification of electronic and electrical defects by authorized experience technician for UPS of capacity 10KVA/30KVA, Checking of unserviciable electrical system and find out defect of control wiring in control panel and Rectified the seme and make serviciable complete and testing thereafter complete all as specified and directed:- charg Note: - (a). The complaint shall be notified to the contactor by engineer - in - charge / JE E&M telephonically / personnaly / by SMS recorded in the register mentioned for the purpose. (b). Contactor shall make neccessary arrangement to attend the complaint. (c). Cost of any minor nature of repair / replacement of petty item such as nuts, bolts, washers, screws, piece of electrical cable upto 0.5 meter length etc, is deemed included in the unit rate quoted by the contractor. (d). Any other major item / repair required for the rectification shall be measured and paid separately under respective item of the schedule. (e). Complaint number, date, location, date of rectification shall be entered in MB for payment purpose.
Supply and fixng Bypass card suitabel for 30 KVA DSP Based 3P -1Ph UPS complete all as specified and directed.
Supply and fixng Display card suiatbel for 15 KVA UPS complete all as specified and directed.
Supply and fixngTransformer card suiatbel for 15 KVA UPS complete all as specified and directed.
Supply and fixng Charging Card suiatbel for 15 KVA UPS complete all as specified and directed.
Supply and fixng DC driver Card suiatbel for 30 KVA UPS complete all as specified and directed.
Supply and fixng DC driver Card suiatbel for 15 KVA UPS complete all as specified and directed.
M&L for carrying out following work through manufacturer's authorised service engineer of voltage stabilizer disconnecting of all electrical connections of stabilizer and check the auto/manual function of stabilizer, to be check the oil level, oil seals leakage if any, check all volt meters and amp meter working condition or not, Taking out top cover of stabilizer for replacing defective parts/items clean the dust by air blower, check the neutral and earthing connections properly or not, to be done properly, to be check the all nut bolts tightining. and refixing the same in existing location and re-connect all the incoming/outgoing cables properly including testing and commissioning as mentioned below complete all as specified and directed of following capacities and located at various tech Accn
(i) Opening of stabilizer at tech Accn workshop and taking out all defective / serviceable parts fixing of new parts after repair inplace of defective part, rewiring of defective conduit wiring etc and assembling complete all as specified & directed.
(ii) Testing of stabilizer after repair on existing load to give desired & rated output
(iii) M & L for preparation of old painted surface by scrapping manualy and applying one coat of primer and two coats of synthetic enamel paint by spray painting.
Note : - All defective parts including cable & oil replaced will be measured & paid separately under relevent item of schedule as supply only. However cost of labour for fixing of new part deemed to be included in unit rate of sl item No.1 above.
(a) 20 KVA to 30 KVA capacity
(b) 50 KVA-60KVA capacity
(c) 75 KVA capacity
(d) 100 KVA capacity
(e) 150 KVA capacity
(f) 250 KVA Capacity
Supply only electronic servo card of suitable size as per ground including all accessories required for fitting complete all as specified and as directed. Make:- AE/ APLEB/ ANDREWYULE /SINETRAC/ VOLINA/ VINITEC/ IECO/ V-GUARD/ INDIAN TRANSFORMER & ELECTRICALS PVT. LTD.(GURGAON).
Supply only under mentioned spares for voltage stabilizer of different capacitites complete all as specified and directed:-
(a) Sychronising motor low speed instant start, stop high torque input voltage 250V single phase 50HZ 60 RPM type 53-102114, 0 to 15 Amp
(b) Control transformer 24 volt DC
(d) Toggle switch 10 Amps
(e) Indication lamp with bulb
(f) Limit switch with aluminium housing
(g) Reset switch 10Amps 230 V AC
(h) Aluminium brush assembly for 3 x 16.6 / 25 KVA stabilizer
(j) Terminal strip for stabilizer
(k) Insulator for dimmer
(l) MCCB TPN 63 Amp 16 KA With magnetic and thermal release
(m) MCCB TPN 100 Amp 25 KA With magnetic and thermal release
(n) MCCB TPN 160 Amp 25 KA With magnetic and thermal release
(o) MCCB TPN 200 Amp 35 KA With magnetic and thermal release
(p) MCCB TPN 250 Amp 35 KA With magnetic and thermal release
(q) MCCB TPN 315 Amp 35 KA With magnetic and thermal release
(r) MCCB TPN 400 Amp 35 KA With magnetic and thermal release
Material & Labour for refilling/topping up/replacement of stabilizer Oil with new dehydrated stabilizer Oil, open lid cover of stabilizer including changing of gasket set if required complete and re-fixing of top lid cover without any damage to stabilizer suitable for working voltage 440 volts grade including necessary dehydration to achieve dielectric strength min 40 KV including internal/external connection and testing on load of stabilizer complete all as specified and as directed. Make:- HPCL(SEETAL)/ HP (SEETAL)/ SERVO/GULF/ CASTROL
Supply and fixing coloured electric shock and its management chart of size 70x100 cm in english and hindi both languages and it should be water proof,t ear proof, dust proof and double side laminated with 30 micron thick plastic film suitable for fix on wall of machine room including all connected accessories and neccessory arrangement for fixing complete all as specified and as directed.
Supply and fixing coloured fire safety chart of size 70x100 cm in english and hindi both language and it should be water proof,tear proof, dust proof and double side laminated with 30 micron thick plastic film suitable for fix on wall of machine room including all connected accessories and neccessory arrangement for fixing complete all as specified and as directed.
Supply and fixing coloured lift DO and Don't chart of suitable size in english and hindi both languages and it should be water proof, tear proof, dust proof and double side laminated with 30 micron thick plastic film suitable for fix on wall including all connected accessories and neccessory arrangement for fixing complete all as specified and as directed.
Supply and fixing in repair of CO2 type fire extinguisher at stored pressure of capacity of 0.50 Kg complete all as specified and as directed
Refilling of CO2 in existing fire extigusher of capacity 2.5 ltr-5 ltr and testing and sealing complete
Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 125 KVARs and up 8/10 stages installed at various locations at AFS Baroda area including carrying out complete maintenance/repairs as required of all the sub systems viz. based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs/MCCBs for isolation (with all the accessoires) any breakdown maintenance and replacement of unserviceable parts, refixing of old serviceable parts/new parts if any project completion and trouble shooting responsibility also lies with contractor complete all as specified and directed. Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system fortnightly, replacement of defective control wiring, small part such as Push button, lugs any auxilary contatct,auto selctor switch etc and necessary servicing repair by expert technician and register will be maintaned for the same. (iii) The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii)Measure components such as capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCB shall be measured and paid saperatly
Supply only power factor correction capacitor, 5 KVAR, heavy duty 440 volts 50 Hz complete including taking down old unserviceable capacitor complete all as specified and directed.
All as per item No 41.00 above but 10 KVAR Capactor Bank
All as per item No 41.00 here-in-before but 15 KVAR Capactor Bank
S&F APFC relay eta CON L series with auto-set function 3-8 stage, Model etaCON L3 including taking down old unserviceable one complete all as specified and directed. Make:- L&T or equivalent make in Schneider/HPL/Indo Asian.
S&F in repairs, capacitor duty contactor, type MOC built in auxillary contact blocks, 8.5 KVAR, 415 volts, 3 phase, 50 Hz, type MO C8.5 complete all as specified and directed.
All as per item No above but capacitor duty contactor, type MO C12.5.
All as per item No Above here-in-before but capacitor duty contactor, type MO C15.
M&L for earthing using 25mmx3mm of copper strip and copper plate of size earth 300x300x3mm as earth electrode all as specified and directed.Note:- The rated quoted is deemed to the inclusive of the followings:- (a) The excavation and earth work (filling in, ramming in layers, watering etc as directed) in any type of soil for earth pit (pit size 1.20x 1.20x3.0mtr). (b) Perforated GI tubing (ISI marked) light grade 80mm bore 7.0 mtr long for strip protection and watering. (c) Common salt charcoal dust in alternative layers of 15cm, up to 90cm above the top of copper plate and one layers of 15cm Magnesium sulphate (MgSo4) all as directed (Salt - 500Kg, Charcoal dust - 1000 Kg & MgSo4 - 150 Kg). (d) Earth chamber of internal size 600mmx600mmx600mm, built in PCC (1:3:6) type C2 bed 15cm thick at bottom, brick work in CM 1:6 upto 45cm over PCC bed and PCC (1:3:6) type C1 coping 15cm above, embedded with MS angle 50x50x3mm frame work duly painted with anti corrosive bituminous paint, with and including RCC slab 50mm thick in cement concrete (1:2:4) type B1, reinforced with XPM (weight not less than 4Kg per Sqm) having lifting arrangement duly painted in green and making earth pit as directed.(e) On testing, after completion, if the earth resistance <0.5ohms is not obtained, earthing will be regenerated at no extra cost till the desired earth resistance is obtained. (f) GI tubing, bib tap etc for provisioning of continuous water supply at earthing pit will be deemed to be included in this item.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick electrode, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to GI strip 32x6mm by means of bolts, nuts, check-nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 (duly protected with 15 mm dia light grade GI pipe upto 7.5 m from the earth plate) and connected to GI steel earth plate including charcoal, dust, common salt necessary excavation in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 m from the starting point, watering pipe 20 mm dia GI light grade treated with 1 No PGI funnel, pit of PCC 1:2:4 type B-1, RCC 1:2:4 type B-1 pit cover 75 mm thick reinforced with 6 mm dia bars @ 75 mm c/c both ways and with MS handle 12 mm dia complete connected to earth test point including testing complete all as specified and directed.
Note for all items :- If any item gets repeated in this schedule, the lowest rate quoted for those same items by the L-1 bidder shall be considered for payment and decision of Accepting Officer i.e. GE(AF) Baroda in this regard shall be final and binding.
SNEH CORPORATION (BID ID -3396119)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .