Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 3 | Not Admitted-Fee/PreQual/Technical 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹63,000
Closing Date
27 Aug 2021, 11:30 amClosed
EEEANDMWSCN
EEEANDMWSCN NEAR KANHIYA NAGAR METRO STATION DELHI -35
S/I/T/C of HT panel at Sanjay Gandhi Transport Nagar BPS Re-invited
2021_DJB_206960_1
NIT NO. 06 (2021-2022)
Open Tender
Miscellaneous Services
Item Wise
90 days
EEEANDMWSCN
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
THROUGH DJB OFFICIAL WEBSITE IN LINK TENDER
₹63,000
Yes
26 Nov 2021
12 Aug 2021
27 Aug 2021
12 Aug 2021
27 Aug 2021
12 Aug 2021
Supply of 11kV, 800Amps, 25KA for 1 Sec metal clad Indoor VCB 5 Panel Board (2I/C+1B/C+2O/G) as per below Bill of Material. a) 230V AC Motorized Mechanism b) Bus bars with PVC Sleeve 800 Amp c) Color coded Wiring d) Degree of Protection - IP4X e) Paint Shade - RAL7032 as per IS (Inside, Outside) f) Shunt Trip/Close coils - 24 VDC g) Warning plates h) Aux. Contactor - 4 NO + 4 NC i) Earthing – Copper j) CT/PT Wiring - 2.5 Sq. mm , All Other wiring - 2.5 Sq. mm k) POXY RESIN CAST P.T. l) 3Ph , D/O TYPE, 11KV/Sqrt.3/ 110V/Sqrt.3 , Class-1 , Burden - 100VA m) EPOXY RESIN CAST , 1-Ph CT n) 100-50/5-5A , Cl-1/5P10,Burden-_15VA o) 200-100/5-5A, Cl -1/5P10, Burden - _ 15VA p) Digital Volt meter with VSS q) Digital Amp meter with VSS r) INDICATING LAMPS LED TYPE, BREAKER ON – Red, BREAKER OFF – GREEN, AUTO TRIP INDICATION – Amber, TRIP CIRCUIT Healthy – CLEAR, SPRING Charged – Blue, RYB Indication. s) ACCESSORIES Push Button for trip circuit healthy check, Emergency Trip Button, Local Remote Switch, Trip Neutral Close Switch, Panel Space Heater with Thermostat & switch, Panel Illumination Lamp with Switch, Door Operated Switch, Timer, 8 window Annunciation with hooter. t) RELAYS Numerical Non Communicable Non draw out type with 50/50N/51/51N Protection Model- CGI14N of CGL Make, Master Trip Relay, Auxiliary Relay for Transformer Fault Make :- ABB /Crompton/Schneider/Jyoti/Kirloskar
Providing and Fixing of Chemical Earthing
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.DSR (E&M) 2018 5.18
Dismantling of Old HTpanels from the site with the help of gas cutter And allied work & shifting the same in store
Installation by making necessary arrangements Base frame/foundation For fixing of panel and making end termination of the cable including replacing End Jointing Kits of the suitable size
Packing /forwarding & cartage up to site including loading & unloading
Testing & commissioning of installed equipment’s, ,as per required parameters with relevant IS .testing of the panel prior to switching on as follow i)Continuity and earth testing ii) Meggering of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. iii)checking for all tightness of nut and bolts iv) On load testing with engineer in charge
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .