Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.9 LAccepted-AOC | L1 | Accepted-AOC Lowest quoted bidder. | |
| 2 | L2₹35.7 L+₹3.4 L (10.5%)Rejected-Finance | L2 | Rejected-Finance Higher quoted bidder. | |
| 3 | Rejected-Technical | - | Rejected-Technical Do not held category of b(i) | |
| 4 | Rejected-Technical | - | Rejected-Technical No remark in WLR of HQ CEBZ for QE Jun 2022 |
Tender Value
₹31 L
EMD Value
₹62,000
Closing Date
30 Aug 2022, 6:00 pmClosed
GE Pithoragarh
GE Pithoragarh Post Bharkatia Pithoragarh ( UK)PIN-262520
REPAIR/REPLACEMENT OF SECURITY FENCING CHEQUERRED TILES AND STREET LIGHTS AND REPAIR/RENEWAL, CLEANING OF SEWAGE LINE, MANHOLES, SEPTIC TANK AND FILTER BEDS DRAIN AND MISC WORKS AT MIL STN DHARCHULA UNDER GE PITHORAGARH
2022_MES_542517_1
8486/DHR/E8
Open Tender
Miscellaneous Works
Item Rate
330 days
AGE Dharchula
Class D, Category a(i), a(ii) and b(i)
6 documents required · 6 mandatory
₹500
GE Pithoragarh
₹62,000
Yes
4 Nov 2022
2 Aug 2022
6 Sept 2022
2 Aug 2022
30 Aug 2022
16 Aug 2022
Amount
DESCRIPTION OF ITEMS
Demolition of cement concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) complete all specified and directed
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises
M&L for 40 mm th PCC 1:2:4 type B1 (using 20 mm graded stone agg) as in flooring finished even & smooth without using extra cement complete all as spfd & directed.
Chequered cement concrete tiles 20cm x 20cm x 25mm thick, set, jointed and pointed in neat cement slurry in floors with grey cement and pigment over and including 15mm thick screed in CM 1:6 all as specified.
Excavating post holes or similar holes, each not exceeding 0.5 Cum, getting out in Soft/ disintegrated rock, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering, and removing surplus soil to a distance n.exc 50m & making good surface complete all as specified and directed.
M&L for Plain Cement Concrete Type C2 1:4:8 (using 40 mm graded stone aggregate) in foundations, filling and mass concrete complete all as specified and directed.
Dismantling wrought iron or mild steel work of any description not otherwise provided for.
S & F Mild steel work in wind ties, including securing bolts and posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc., flat iron fillets (for securing wire mesh etc.) including round MS bars etc embedded in concrete/masonry complete duly tar painted and sanded the embedded portion of angle iron including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed. complete all as specified and directed.
M & L for MS round bars (Fe-410-W (Gde E-250) quality A or Fe-290 (Gde-E-165)) 10mm dia and over cut to Length bent to shape required incl cranking, bending, spirally for hooping for columns with an including MS wire(Annealed not less than .90 mm Dia) or securing with clips complete all as specified and directed.
Supply only chain link MS galvanised fencing any size and type complete all as specified and directed.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc., including provision of binding wire complete all as specified and directed.
S & F Galvanized, 2 strand, steel barbed wire 2.24 mm dia., barbed with 2 mm dia., barbs at 75 mm spacing and straining and fixing to any type of standard rails straining bolts, including securing or tying at crossings with and provision of galvanized mild steel wire, staples or steel pins, etc. as directed (each line wire to be measured) complete all as specified and directed.
Dismantling fencing wire mesh, any type complete all as specified and directed.
Dismantling post or struts (steel) any section, embedded in concrete etc including taking out embedded portion and making good the disturbed ground complete all as specified and directed.
M&L for 2 coats of synthetic enamel paint over one coat of red oxide on newly prepared steel surface of any description ,not otherwise description over 10cm width or girth.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m depth for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, etc n. exc 10 sqm on plan and n exc 1.5 m in depth and getting out hard and dense soil complete all as specified and directed.
Returning filling in, approved earth including spreading, levelling, watering and well ramming in layers n.exc 25cm thick, complete all as sspecified and directed.
Removing excavated materials n. exc 50m and deposting where directed at a level n.exc.1.50m above the starting point, complete all as spfd & directed.
Demolition of brick work, stone/boulder masonary built in cement mortar complete all speecified and directed
M&L for precast cement concrete block masonary with P.C.C 1:3:6 mix type C-1 block exc 10cm in width and set in CM1:6 complete all as specified and directed
Demolition of cement concrete in reinforced of any description and in any position not otherwise specifically provided, complete all as specified & directed.
Demolition and breaking up drain pipes (Salt glazed ware,AC or Reinfoced concrete),150 mm dia, set in cement mortar, complete all as specified and directed. Note :- Excavation & earth work shall be measured seprately.
M&L for precast cement concrete type B1 1:2:4 (Using 20 mm graded stone aggregate) as in cover slabs, manhole cover, chamber cover and drainage cover set in cement mortar 1:6 including necessary formwok complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 using 40 mm graded stone aggregate as in sub bases, floors and pavings complete all as specified and directed.
M&L for PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in coping including necessary formwork complete all as spfd and directed
M&L for PCC 1:2:4 type B-1 using 20mm graded stone aggregate in surface channel and drain complete all as spfd and directed
Extra for forming fair finished drain or channel 90 cm inner girth in cement concrete, using extrac cement including forms, mould, inte=red/stopped ends etc. complete all as specified and directed.
Taking down cement plaster on brick or stone walls, ect. Including racking out joints, hacking for keys, scrubbing down with water etc. complete all as specified and directed.
M&L for 15 mm thick rendering on fair faces of brick work or concrete surface in cement mortar 1:4 with water proofing compound, including finishing the surfaces even and smoothe (without using extra cement), complete all as specified and directed. Note : WPC shall be measured separately
Ditto on stone masonary surfaces or surface other than fair faces of brick work complete all as specified and directed
M&L TMT bars, 6 to 8mm, cut to length, bent to shape required including cranking,bending spirally for hooping for column, hooking ends and binding with and incl MS wire(annealed) not less than 0.9 mm dia complete all as specified and directed.
S&F reinforced concrete pipes, class NP2, 150mm dlaid and jointed complete with collars, complete all as specified and directed.
M&L for concrete bed 1:4:8 type D-2 (Using 40 mm graded stone aggregate) as in drain pipes including packing under, and haunching against the side of pipes after the are laid and tested in 150 mm bore pipe, complete all as specified and directed.
S&F in rep vitreous china squatting pan "Orissa pattern" size 580 mm x 440 mm white with integral foot rests, incl provn of lime concrete bedding complete all as spfd & directed.
S&F in repairs PVC flushing cistern low level white with inlet pipe,ball valve,float valve and handle including brackets complete all as specified and directed
S/F in repair 15 mm bore bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule complete all as spfd & directed.
S/F in Repair Pillar taps, cast copper alloy, with capstan heads, chromium plated, screwed down high pressure, with or without lettered ‘Hot' or ‘Cold' with long screwed shanks and fly-nuts, screwed for iron pipe and fixed complete all as spfd & directed.
S&F in repairs Health Faucet (ABS Body) MS, Chromium plated suitable for 15mm dia pipe with 1.25 mtr long flexible tube and ABS wall hook including making connections and fixed in position complete all as specified and as directed.
S&F in repair PVC connections 15 mm size with PTMT nuts of length 600 mm long all as spfd and as directed.
M&L in repair for 75mm PVC (SWR) pipes single socketed in any length with rubber ring joints, laid in trenches or in floor complete all as specified and as directed .
-Ditto- but 110 mm
Taking up existing manhole covers and cleaning of soak well / septic tank of any size and any capacity, by dewatering and removing sludge in liquid mud state after emptying the sewage / waste water and removing the sludge to a distance exc. 250 m and n.exc. 500m and disposed off as directed by the Engineer-in-Charge , and placing the cover in position, complete all as specified and directed. Note :- Measurement shall be made for actual quantity of sludge, removed from the tank in liquid mud state.
Cleaning of sewage line upto 150mm dia including manhole and disposal of waste materials / spoil up to a distance n.exc. 50m by any means complete all as specified and directed. Note :- Relaying / refixing or S&F of new pipe etc where required shall be measured seprately.
Cleaning of sewage line upto 200mm dia including manhole and disposal of waste materials / spoil up to a distance n.exc. 50m by any means complete all as specified and directed. Note :- Relaying / refixing or S&F of new pipe etc where required shall be measured seprately.
Cleaning of sewage line upto 250mm dia including manhole and disposal of waste materials / spoil up to a distance n.exc. 50m by any means complete all as specified and directed. Note :- Relaying / refixing or S&F of new pipe etc where required shall be measured seprately.
Removal of all blockage of WC, bath kitchen, WHB traps, soil waste/vent pipe (vertical or laid in trenches/floor any type /size) sewage line upto 1st manhole, pits and 1st manhole of any section /depth any situation by way of cleaning/dewatering manholes by using any type of manually or mechanically or by way of any other suitable means including foreign materials from manholes, traps, pits where required and directed by Engineer-in-Charge and keeping the sewage system upto 1st manhole function in perfect condition including final drop out from 1st manhole, all as specified and as directed.
M&L for servicing of Sewage treatment plant (STP) based on moving bed bioreactor (MBBR) Aerobic attached growth technology including servicing, checking and greacing/lubrication of 02 No Feed pump of Capacity up to 3HP, checking of one NO equalisation tank, greacing and testing of one Bar screen, oil & grease trap, Cleaning, checking of two moving bed bio reactor with media by visual checking of growth of Bio-Film and re-seeding of required quantity of MBBR media for propagate biofilm (bacteria colonies) and submit the report of effectiveness of the sewage tratment plant (STP). Servicing, checking and greacing/lubrication of 02 Nos Filter feed pump and moter set of capacity 7.5HP, opening of 01 No dual media filter and 01 No activated carbon media filter and checking the condition of existing media, cleaning and removing all sediment particles of sludge, mud, sand, vegetation and refix the all euipments at original position complete including testing and submit the test report of filtered water as per sewage charactristic for the treated water as followed:- (i) BOD (PPM) Treated waste water < 30 (ii) COD (PPM) Treated waste water < 250 (iii) TSS (PPM) Treated waste water < 30 (iv) Oil & Grease Treated waste water <1000 (v) PH Value Treated waste water ~6.6-8.5 (v) Total coliform Treated waste water <100MPN/100ml Note A : 1. The plant shall be visited twice as directed during contract period by auth service technician/Engineer of Fontus water pvt ltd or equivalent STP manufacturing or authorised service patner company approved by GE and will check all parameter /defects and growth of biofilm on the MBBR media and submit report to Engineer in charge. All necessary repair / servicing will be done by
auth service engineer. Cost visiting charges of engineer are deemed to be include in unit rate. 2. All spares/material reuired will be paid and measured separately against relevent items of schedule hereunder. Note B: The unit rate includes the following works (i) Checking of condition of MBBR media, dual media and activated carbon media. Changing of media shall be measured and paid separately. (ii) Carry out preventive maintenance as per the company recommandation and standard practice in every visit. Lubricating the bearing and motors & Air blower/compressor. (iii) Checking the growth of biofilm observed on the MBBR media, Biochemical Oxygen Demand (BOD) Removal efficiancy, range of F/M Ratio, Chemical Oxygen Demand (COD) Ratio and ensuring healthy condition of the plant. (iv) Taking set of reading and evaluating to ensure satisfactory performance of the plant. (v) Checking of functioning of air blower in every visit and set the pressure required to propagete of the bacteria colonies. (vi) Checking the pump moter set of existing size and repair the leakage and greacing/lubrication of moving part. (Vii) Servicing/repairs works will be carried out within 05 days after intimation to contractor on telephone followed in writing. Any delay beyound 05 day shall be penalised through panel recovery @ Rs 1000 per day till rectification/repair starts.
Supply and filling moving bed Biological MBBR biofilm filter media having approx size 25X12mm, cylindrical with external fins, white/black coloured for the treatment of sewage plant of capacity 700KLD including removal of existing MBBR filter media of any size and shape by dewatering the tank and removing all sedimented particles of sludge, mud, sand, vegetation etc complete all as specified and directed. Make:Biotech india Ltd/Aquatech international/Weldone water system
M&L for top up activated carbon media consist of single layer of activated carbon supported by gravels and pabbles at bottom, coconut shell carbon and coal based carbon used, adsorption capacity up to 90% chlorine, colour and odour removal 85 to 90%, top up up to 40 cm and maintain media density 500-700 kg/m3 all as specified and directed by Engr-in-charge.
M&L for top up dual media consist of silica sand (16-32 mm mesh) and anthracite( 0.6-1.2mm) provide more area & efficient filteration, supported by gravels and pebbles at bottom, topup silica sand up to 10 Cm thickness and top up anthracite up to 10 cm thickness to maintain the filteration level up to 40 microns complete all as specified and directed by Eng-in-Charge.
Cleaning of Equilization tank and air grid, removing all sludge and de-scaling vegitation on the inside and outside of tank and white washing (Two coat) including cleaning the surrounding area of the tank to a distance of 3 meter circumstance including cutting of grass, digging out roots, filling holes and levelling around and removing waste material to a distance not exceeding 50 Mtrs complete alll as specified and directed .
All as per item No 5 but Bar screen chamber and pit
All as per item No 5 but oil and grease trap
All as per item No 5 but FAB media/MBBR tank
All as per item No 5 but Tube settler tank
All as per item No 5 but Clean water tank
All as per item No 5 but chlorine contact tank Note: item Ser No:53 to 59 (i) Adequate manpower including necessary T&P and safety precaution to the individual working /carry out job at site is the responsibility of the contractor and the cost include in the quotated rate. (ii) All inlet/outlet pipes/ channels shall be properly sealed at the opening inside the clarifer while carring out cleaning. (iii) The work mentioned in item Ser No 05 to 11 will be carried out within 07 days after intimation to contractor on telephonic followed in writing. Any delay beyound 07 days shall be penalished through panel recovery @ 500 per day till rectification/repair.
Disconneting and taking down air blower/compressor with 20HP electric motor carefully from foundation manually or mechanically and transporting to workshop for repair and back, installation, refixing, reconnecting to electric and piping work with the repaired compressor including repacement of V type fan belts etc complete all as specified and directed by Engr-in-Charge. Note:- (i) The quoted rate shall be deemed to include the cost of transportation, fixing of spare parts complete. Spare parts shall be measured and paid for as supply only separately. (ii) Servicing / repairs works will be carried out whitin 03 days after intimation to contractor on telephone followed in writing. Any delay beyound 03 day shall be penalised through panel recovery @ 500 per day till rectification/repair starts.
Supply only non return valve suitable for 20 HP compressor
Supply only cylinder liner suitable for 20 HP compressor
Supply only piston with 'O' ring suitable for 20 HP compressor
Supply only connecting rod suitable for 20 HP compressor
Supply only inlet valve suitable for 20 HP compressor
Supply only outlet valve suitable for 20 HP compressor
Supply only gasket set suitable for 20 HP compressor
Supply only piston pin suitable for 20 HP compressor
Supply only safety valve suitable for 20 HP compressor
Supply only pressure gauge suitable for 20 HP compressor
Taking out the burnt electric motor of capacity 2 HP to 5 HP from existing position, transporting to civil work shop, separating the stator and rotor housing, cutting and removing the existing winding of stator completely, cleaning the slots and rewinding with existing gauge of super enamelled copper winding wire with suitable insulation, applying insulation varnish and heating in heating chamber till completely dried and reassembling the motor including supply and replacement of DE(01 No.) &NDE(01 No) bearings (make: NBC/SKF/TATA), transporting back to site and re-installing in its original position including proper alignment for smooth running and testing on completion complete all as specified and directed by Engineer-in-Charge.
All as per item No 23 but electric motor of capacity 7.5 HP
All as per item No 23 but electric motor of capacity 20 HP
Supply only terminal connector for 2 HP to 20 HP motor with high trensile brass bolts & nuts, washers etc complete all as specified and directed.
Supply only 2 HP to 20 HP capacity fabricate steel / cast or fabricate aluminium fan blade for motors as per the existing size complete all as specified and directed.
Repairs to rotors of squirrel cage induction motor 2 HP to 25 HP by metal filling, welding / cutting & grinding, polishing to required sizes for motors complete all as specified and directed.
Supply only star rubber bush coupling for motor 2 HP to 25 HP complete all as specified and directed.
Supply only star coupling key any size as per sample complete all as specified and directed.
Dismantling and taking up unserviceable non clogging type centrifugal pump sets of size 5 HP from foundations after disconnecting electric and water connections and transportation from site to contractor's work shop for carrying out repairs to pump sets as required incluidng re- assembling, re-fixing in position, including connecting and testing complete as specified and directed. Notes:- (i) Spare parts for pumps shall be measured and paid separately under respective items of this schedule. (ii) Transportation charges of pump sets from MES installations to contractors work shop and back is deemed to be included in the quoted rates. (iii) Pump sets issued for repairs / re-winding shall be returned back / re-installed at site within seven days from the date of receipt by the contractor. Any delay boyond 7 days shall be compensated through penal recovery @ Rs. 200 per day per pump set. (iv) Rates for minor items such as nut bolts, washers, thimbles, lugs, etc are deemed to be included in the quoted rates.
M&L for opening up centrifugal pump sets and replacement of unserviceable pump shaft 5 HP complete all as specified and directed.
M&L for opening up centrifugal pump sets and replacement of unserviceable pump impeller brass 5 HP complete all as specified and directed.
S&F in replacement of gun metal bush complete set of two as per sample for 5 HP complete all as specified and directed.
S&F in replacement of gun metal sleeves complete set of two Nos for 5 HP complete all as specified and directed.
M&L for the empty of slude chamber with the help of diesal driven pump set having suction up to 7 mtr and discharge up to 10Mtr from the slude chamber all as specified and directed by Engr-in-charge. Note:- (i) Diesel and transporting is deemed to be included in the quoted rates. (ii) Emptying the sludge chamber is carried out within one day from the date of receipt by the contractor. Any delay boyond 1 days shall be compensated through penal recovery @ Rs. 500 per day per installation
Supply and fixing in replacement of 500 ltr capacity of rotational moulded polyethylene water storage tank 2 layered construction ISI marked of make as specified cylindrical vertical with closed top hoisted and fixing in position including 20mm GI pipe medieum grade wash out pipe 450 mm long with and 20mm dia GI pipe medium grade over flow pipe 600mm long with fitting including dismantling of existing water tanks of any type and capacity complete all as directed.
S&F in replacement of cast iron sluice valve of 150 mm bore class PN-1.6 ISI marked (as per IS 14846 of 2000) heavy duty with flanged ends with gun metal spindle and gun metal check nut, iron hand wheel and fixing with providing suitable nuts, bolts, washers and rubber gasket for packing etc complete all as specified and directed. Note:- Any damage if occurs while replacing the sluice valve to pipe lines, over head reservoir will be responsibilty of contractor and will be repaired by contractor at his own cost. Nothing extra will be admissible on this account.
S&F in replacement cast iron non return valves 200mm bore swing/reflex type both end flanged PN 1.6 as per IS 5312 including necessary items such as nut, bolts, washers, rubber packing complete all as specified and directed.
Demolition of cement concrete (un-reinforced) any description and laid in any position complete all as specified and directed.
M&L earthing in replacement complete with galvanised steel earth plate electrode 600mmx600mmx6mm thick, burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate. Earth plate shall be surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to galvanised earth strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI or steel and thimbles and other end of the earth strip connected to machinery eqipment and protected by galvanized iron or steel pipe light grade 32 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009. Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate. 3. On testing after completion of earthing if desired earth resistance is not achieved, the earthing will be redone at no extra cost to obtain the desired earth values.
S&F in repair earth continuity conductor or main earthing lead fixed to wall on batten or buried in ground in pipe etc as required 25X4 mm galvanised iron strip complete all as specified and as directed by Engineer–in –Charge.
Supply only compressor oil 320 grade complete for top up oil level complete all as specified and directed.
Supply only Calcium hypo chloride 65%-70% Chlorine content (Calcium based granular disinfectant) for water treatment, in factory sealed container/drum (45 Kg packing, complete all as specified and directed as per following specifications:- (a) Chemical analysis & physical observations : Description: Whitish granuals, Granuals size : (Mesh passing through -100 BSS) : 1.1 (+0.1%), Water/Moisture : < 5.00% Mercury & other heavy metal contaminations : BDL (b) Strength in terms of quantity of chlorination chemical required to obtain free chlorine of 1 ppm per lakh litres of water : Requirement must be 140-200 gm per one lakh litre of water to achieve 1 ppm average at injection point (site & raw water quality variation may apply additionally) Note for Item No 92 :- (i) The chemical supplied against said items shall be deposited to MES store yard and RV to be produced for payment. (ii) The chemical should have min six month shelf life and supplied in two batches or as directed by Engr-in-Charge.
Supply only Calcium hydro-oxide (Lime, 80-85%) in powder form as pH Booster for STP water, packing in 40 Kg Packs complete all as specified and directed.
Supply only Ortho Tolidin solution (in pack of 20ml) for testing of dissolved chlorine in water complete all as specified and directed.
Supply only stable bleaching powder Grade-I conforming to IS-1065/1989 (Iind Revision) as amended upto date having available chlorine contents min 34% by mass and packed in 25 Kg polythene bag having double fold complete all as specified and directed by Engr-in-Charge and as per following specifications:- Bleaching powder (Calcium hypo chlorine formula : ca(OCl)₂, Molecular weight : 142.96, Physical appearance : White fine powder, Chlorine content : 30±1%, Moisture : 0.5% Max, On Heating at 10±2°C, its does not loose more than 1/15 of available Chlorine, Passing through 1.7 mm sieve : 99%.
Supply only Alum Ferric Sulphate (Grade-4) (best quality as per sample) for purification of water (containing lead (as PB) 30 ppm Max and arsenic 6 ppm Max) conforming to IS-299/2012 (Revised) as amended upto date complete all as specified and directed by Engr-in-Charge. Note : The Alumino Ferric Sulphate shall be supplied in superior quality bricks (slabs) as per IS specifications. Manufacturer name/trade mark shall be engraved on each brick (slab) in addition to marking of relevant clause of IS specifications.
M&L for chemical dosing pump of capacity 0-20 LPH operated on single phase 230 V, 50 Hz power supply high pressure single head gear motored adjustable with self priming suitable for interchangeable pump tubes and sub assemblies, mechanical control adjustable from 5% to 100% with non clogging capacity, pumping against pressure upto 100psi, mounting vertical or horizontal complete with 100 ltrs PE/FRP tank with lid, level gauge and rain shed cowl etc including taking out old unsv pump complete all as specified and directed.
M&L for Agitator 220 Volts 50 Hz AC for stirring of Chemicals in PVC Tank complete all as specified and directed incl taking down old agitator.
M&L for structure steel work, made out of Fe 410-W (gde-E-250) quality A rolled mild steel channel, Angle or Tee sections, MS sheet with hinges & locking arrangements etc. cut to shape / ordinary length, drilled and counter sunk for screws / bolts, including bending and welding duly painted with 2 coats of anticorrosive synthetic enamel paint over a coat of zinc Chromate as in framed work with MS Sheet cover complete all as specified and directed.
M&L for repair of outdoor type cubical control panel board compartmentalized suitable for 3 phase 4 wire, 415 volts, 50 HZ, AC supply system as per latest IS/IEC standards & regulations, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable single leaf doors with two point locking arrangements i.e. locking system with pad-locking facility. The contractor shall replace the faulty switch gear and do the re-wiring of unserviceable one to make the MCC functional. All the indication lamps need to be checked for proper function and the faulty parts needs to be removed with suitable spares. The rating out outgoing feeders are as under:- (a) Sewage transfer pump : 5 HP, 3 Phase (b) Air blower for STP : 20 HP, 3 Phase (c) Filter feed Pump : 7.5 HP, 3 Phase (d) Filter press feed Pump : 3 HP, 3 Phase (e) Altoch dosing pump : 1/2 HP, 1 Phase (f) Alum dosing pump : 1/2 HP, 1 Phase (g) Chlorine dosing Pump : 1/2 HP, 1 Phase
S&F in repair 3 pole contactor MNX A12 (12-30 Amp rating) 415 V with 220-240 Volt AC Coil with 1 NO/NC add on auxiliary contacts complete all as specified.
S&F in repair thermal overload relay 3 phase, relay range 14 to 23 Amps suitable for MNX type contactor complete all as specified.
S&F in repair 3 pole contactor MNX A18 (18-30 Amp rating) 415 V with 220-240 Volt AC Coil with 1 NO/NC add on auxiliary contacts complete all as specified.
S&F in repair thermal overload relay 3 phase, relay range 24 to 40 Amps suitable for MNX type contactor complete all as specified.
S&F in repair thermal overload relay 3 phase, relay range 9 to 15 Amps suitable for MNX type contactor complete all as specified.
S&F in repair star delta electronic timer ETR suitable for 220-240V AC, 50Hz supply complete all as specified and as directed.
Material and labour for disconnecting of defective filter press including motor of 3 phase and along with pipe including dismantling spare parts of Automated filter press, cleaning the serviceable parts, re-metalling machinery polishing and re-assembling including replacement of u/s parts including replacement of plates, plates holding frame, filter cloth and heavy duty cloth strips of filter press as per existing frame of size 24x24x23 with 500 GSM and complete overhauling of filter press including testing complete all as specfied and directed by Engr-in-Charge.
M&L for testing of treated sewage water from inlet and outlet of chlorine contact tank once in every two months from NABL accredited authorised lab as per IS 3025 for recording essential parameters such as BOD, COD, PH, suspended solids and total dissolved solids complete all as specified and directed by Engr-in-Charge. Note : Testing of the treated water shall be carried out at a frequency of two months as directed by Engr-in-Charge.
Labour only for dismantling and taking down street light fittings for repair/replacement including GI bracket and connection wire from light fitting to overhead line or pole box complete all as specified.
S&F LED street light luminaires of capacity 45 watt 230V AC outdoor type with high pressure die-cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engr-in-charge.
S&F bracket made out of GI tubing 1.20 mtr long of 40 mm dia light grade bent to shape with suitable size MS clamps, nut, bolts and washers including one coat of anti corossive primer and two coats of aluminium paints complete all as specified.
S&F PVC insulated 3 core 2.5 Sqmm multistranded Aluminium cable 1100 volts grade for making wiring from the street light fitting to the overhead line or junction/pole box complete all as speicified.
S&F in replacement of electronic driver suitable for 180-240 V, 50Hz AC, LED street light and refixng the street light in its original position or at new location complete all as specified and directed by Engr-in-Charge.
Disconnecting all electrical and copper pipe connection and taking down carefully split type AC of 1.5TR rating from existing position, dismantling, servicing, overhauling and cleaning of filters, fans, indoor and outdoor units through washing or air pressure throughly, checking cooling coil, compressor, gas level, oiling and greasing of fan & motor etc and re install at same ocations after replacing defective parts duly connected with existing AC supply complete all as specified and directed. Make : LG Note:Spare parts shall be measured and paid separately under relevent item only.
Supply only starting relay for 1.5 TR capacity AC of any make/Type
Supply only starting capacitor 60 Mfd for 1.5 TR capacity AC of any make/Type
Supply only running capacitor 36 Mfd for 1.5 TR capacity AC of any make/Type
Supply only thermostate unit including electronic relay eqpt and electronic plate for 1.5 TR capacity AC including taking down old thermostate unit omplete all as reqd at site and directed.
M&L for gas charging with suitable Refrigerant Gas R-32/R-410A after cutting opening sealed unit (compressor) of AC of any type and capacity upto 1.5 TR including replacement of capliary pipe and moisture driver filter etc including crimping and re soldering to charging line complete all as reqd at site and directed.
Cutting suction and discharge gas pipeline and taking out unserviceable compressor unit from refrigerator of 165/175/195 ltrs capacity and S&F new sealed compressor unit of same model or approved model of same capacity complete including commissioning and testing after installation at site complete all as specified and directed.
S & F Relay assy and OLP for Refrigerator, storage Capacity 165/285/310 Ltr (As per sample) including taking down old defective one complete all as specified and directed.
S & F thermostate unit for Refrigerator suitable for capacity 165/195/285/310 Ltr (As per sample) including taking down old defective thermostate unit complete all as specified and directed.
M&L for Charging with suitable Refrigerant Gas R-134a after cutting opening sealed unit (compressor) of water Cooler /Refrigerator of any size/capacity/type including replacement of capliary pipe and moisture driver filter etc including crimping and re soldering to charging line complete all as specified and directed.
Labour only for servicing of self container drinking water cooler storage capacity upto 150 Ltrs, dismantling inner tank and outer tank, pipe assembly, cleaning throughly with descalling liquid compound, overhauling complete to ensure free and constant flow of water through outlet , welding of inner tank if required at site rethreading of inlet/outlet pipe 15 mm dia, through checking/ rectification of fault in electrical circuits and refrigeration system, oiling & greasing of blower motor, replacement of compressor or other necessary parts as required, reassembling the same at existing/new location including necessary fasteners to ensure proper safety as reqd at site, testing and commissioning after re-installation at site complete all as specified and directed. Note:Spare parts shall be measured seperately and paid under relevent items as supply only.
Supply only compressor unit with all connected accessories of existing size/rating for self container drinking water cooler storage capacity upto 150 Ltrs
Supply only starting capacitor suitable for water cooler capacity upto 150ltrs (as per sample) complete all as specified and directed
Supply only running Capacitor suitable for water cooler capacity upto 150ltrs (As per sample) complete all as specified and directed
Supply only Relay assy for water cooler storage type, storage Capacity upto 150 Ltr(As per sample) including taking down old defective running Capacitor complete all as specified and directed
Supply only thermostate unit for storage type water cooler of capacity upto 150ltrs (As per sample) including taking down old defective thermostate unit complete all as specified and directed
Supply only over load protection for water cooler storage type , storage Capacity upto 150 Ltr (As per sample) including taking down old defective assy complete all as specified and directed
M&L for Taking down Fan/blower motor of storage type water cooler Capacity upto 150 Ltr and refixing after rewinding blower motor, fan blade of suitable size, testing after complete all as specified and directed
M&L for disconnecting all electrical connections of 2-4 KVA voltage stablizer, transporting to workshop for repair work, rewinding the voltage stablizer with super enamelled copper wire of same gauge as existing and varnishing, heating including refixing the same complete all as specified and directed by Engr-in-Charge.
M&L for disconnecting all electrical connections of 5 KVA voltage stablizer, transporting to workshop for repair work, rewinding the voltage stablizer with super enamelled copper wire of same gauge as existing and varnishing, heating including refixing the same complete all as specified and directed by Engr-in-Charge.
Supply, laying, testing and commissioning 3 core 16 sqmm, 1100 volts grade heavy duty XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape, armoured with galvanized steel wire or strip and over all PVC sheathed solid conductor complete all as specified and directed including taking down/removing the old unserviceable cable complete all as directed. Note:- Cable shall be laid in cable treches/ cable tray & sand cushioning where reqd. shall be measured & paid separately under relevant items.
All as per Item No. 87 above but cable size of cross sectional area 10 sqmm of 2 core
Supply, laying, testing and commissioning 3 core 10 sqmm, 1100 volts grade submersible pump motor cable with PVC insulated PVC sheathed copper conductor cable complete including taking down unserviceable cable complete all as specified and directed by Engr-in-Charge.
M & L for Sand cushioningng (dry sand) to under ground cable for cable protection provided with layers 8cm thick before laying and 15cm thick after laying the cable and punned down to 23 cm thickness complete all as specified and directed. Note : For payment purpose punned thickness of 18cm shall be measured against spread thickness of 18cm as mentioned in para19.75 of SSR Part-I
M/S ANAND SINGH DHAMI
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .