The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under 66 KV Vesu-1 Sub Station of PIPLOD sub division as well as all Sub-Division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
320440
DGVCLDPPL/0685/06/2026 Approved Date: 25-06-2026
Open
Electrical
Surat
1 document required · 1 mandatory
₹1,180
SURAT DGVCL
₹30,000
3 Jul 2026
3 Jul 2026
3 Jul 2026
20 Jul 2026
3 Jul 2026
Sub:-Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end
termination & straight through jointing kit (to be supplied by contractor) on ARC basis under 66 KV Vesu-1 Sub Station of PIPLOD sub division as well as all Sub-
Division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
Item Code DETAILS OF WORKS Qty Unit Rate Amount
1 9925000001 Labour charge for excavation of cable trench of 400mm width x 1200mm Meter
depth , in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half trench
length is to be considered)
2 9925000002 Labour charge for excavation of cable trench of 600mm width x 1200mm Meter
depth , in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half trench
length is to be considered)
3 9925000003 Labour charge for excavation of cable trench of 400mm width x 1500mm Meter
depth , in any type of soil for laying of cable of size up to 240 mm2 (For
additional cable 200 mm additional width shall be considered i.e. half trench
length is to be considered)
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & Meter
preparation of sand layer 100mm thick, in the cable trench & covering the
cable with 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half
round muffs and providing and fixing of 4inch width yellow colour
polyethylene tape with printing "CAUTION ELECTRIC CABLE BELOW" at 0.75 m
depth from ground surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as to protect cable
from mechnical injuries, refilling the same, as per Instruction of Engineer in
5 9925000005 Labour charge for horizontal drilling using Auger machine without damage to Meter
surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-
1987(3rd revision) and BIS certification and laying of 11KV/22KV XLPE cable of
size up to 300 mm2 in HDPE pipe, as per Site Condition (excluding cost of
pipe). The detail map obtained from HDD machine and excell sheet(hard and
soft copy) indicating the respective depth and distance from adjacent
landmark for each segment for HDD is must required to be submitted. HDD to
be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as per
instruction of EIC.
6 9925000006 Labour charge for horizontal drilling manually without damage to surface Meter
road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color,
110mm O.D., 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV XLPE cable of size up to
300 mm2 size, as per Site Condition (excluding cost of pipe). The detail map
and excell sheet(hard and soft copy) indicating the respective depth and
distance from adjacent landmark for each segment of cable to be submitted.
Drilling to be carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per site
conditions as per instruction of EIC.
7 9925000007 Supply of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5 mm thickness Meter
H.D.P.E. pipe confirms to IS 4984 and BIS certification for laying of
underground 11KV / 22KV XLPE cable up to 300 mm2 size.
8 9925000008 Labour work for RCC concreting on disputed location and repairing of damage CMT
portion of road crossing for the work carried out for roads crossing as well as
concreting & muffing of ploes including all materials (1:2:4)
9 9925000009 Providing & fixing concrete stone route marker of 300 mm width x 150 mm No
thick x 650 mm height embedded in earth at least 300 mm below & 350 mm
above ground level respectively at distance approx 50 meters along the length
of cable. The RCC concreting (1:2:4)(all necessary maeterials will be in bidder's
scope) of route marker is to be carried out 300 mm width x 150 mm thick x
300 mm below ground level as per instruction of EIC. The route marker
should be with name of company with approved yellow colour-DGVCL. The
distance from marker to cable and cable depth with feeder name etc., marked
with arrow sign is to be painted on it.The route marker is to be fixed at
location near to any fixed permanent location (not necessary to fix exact on
top of cable) as per instruction of EIC.
10 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 300 mm 2 Per Job
on DP Structure with fixing of 02 Nos polymer cleats on top and middle part.
Polymer cleats, nut bolts etc. fixing material to be provided by contractor.
11 9925000015 Providing & fixing of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5mm Per Job
thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification on the
erected DP structure for the mechanical protection of cable by inserting the
cable inside HDPE pipe. The HDPE pipe shall be erected in such a way that
300mm shall be below the ground level and the rest 2700 mm shall be
supported on the DP Structure with 01 No Polymer cleat. All materials
including polymer cleat and Nut bolt to be provided by contractor.
12 9925000016 Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with No
pit to be filled with salt & coke and construction of chamber as per DGVCL
Drg. No. dg /100 for DP and cable. The earthing pit should be joined with
cable by G.I. strip of size 1” width & 2 mm thick. All material GI pipe, Coke,
Salt etc will be supplied by bidder.
13 9925000017 Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV No
3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
14 9925000018 Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV No
3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
15 9925000019 Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C No
x 185 mm2 size XLPE cable as per DGVCL technical specification.
16 9925000020 Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV No
3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
17 9925000021 Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x No
185 mm2 size XLPE cableas per DGVCL technical specification.
18 9925000022 Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C No
x 185 mm2 size XLPE cable as per DGVCL technical specification.
19 9925000023 Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm No
deep joint pits for installation of 11kV/22kV Straight through joints as per
instruction of engineer-in-charge & covering the cable with 150 mm dia
(Outer), thickness 25 mm, 1.0 meter long RCC half round muffs & refilling
same as per instruction of EIC .
20 9925000024 Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable No
after removal of semi conducting layer and applying of PVC heat shrinkable
anti-tracking core insulating tubing (1.1KV), on both end terminal using
Aluminium long barrel heavy duty up to 240 sq mm lugs, Aluminium bus
connector. Taping with PG- clamp for bus conductor as per drawing and as
per instruction of EIC. The Alluminium lugs and PG clamp shall be covered
with 11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable will be in scope of
DGVCL while all other materials will be in bidder's scope)
21 9925000025 Testing of cable at various points and commissioning the feeder as per No
instruction of engineer-in-charge. Test result shall be submitted by contractor
22 9925000026 Preparation and submission of 6 (six) copies , of complete layout drawings Set
with GIS mapping as per actual cable routing showing road crossing, HDPE
pipe sleeving, jointing locations, markers etc.
23 9925000027 Providing and fixing of Sign Board at junction point Made out of 2 mm No
aluminium sheet size 750x300 mm (2.5 x 1ft) rectangle, as per design, pre
treated with phosphate process and acid etching coated with one coat of
epoxy primer and two coats of best quality paints, refloctrorised with Hi-
Intensity retro – reflective sheeting as per the latest and frame fabricated
from suitable size iron angle. The Sign Board is to be fixed on the base
prepared from channel and bracing angles which is grouted by means of
cement concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm
to be grouted in ground). The details to be displayed on sign board will be
given by In-charge Engineer.
24 9925000028 Providing andMicro
(a) Hi intensity fixing of Sign
prismatic Board (Danger Board) on Distribution
Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design, pre
treated with phosphate process and acid etching coated with one coat of
epoxy primer and two coats of best quality paints, refloctrorised with Hi-
Intensity retro-reflective sheeting as per the latest and frame fabricated from
suitable size iron angle. The Sign Board (Danger Board is to be fixed at the
location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
25 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 No
mm aluminium sheet along with 1.0 mm dia aluminium binding wire for fixing
of aluminium tag near end termination joint at DP structure for identifyng the
cable. The details of feeder i.e. 11 / 22 KV with feeder name shound be
punched on the tag by letter punch of size 16 mm as per instruction of In-
charge Engineer.
26 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
27 9925000031 Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C Nos
x 240 mm2 size XLPE cable as per DGVCL technical specification.
28 9925000032 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
29 9925000033 Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
30 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 Nos
mm2 size XLPE cableas per DGVCL technical specification.
31 9925000035 Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
32 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in per cable
open space per mtr
33 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
34 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half NO.
35 9925000010 Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable NO.
connection arrangement along with fitting of necessary fabrication for 11KV
cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
36 9925000011 Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable NO.
connection arrangement along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of poles)
37 9925000012 Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable NO.
connection arrangement along with fitting of necessary fabrication for 11KV
cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
39 9925000013 Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection NO.
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable
including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
40 Laying (including installation, testing and commissioning) of various size of mtr 335 as per rate derived by UGVCL letter
Single circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable in no ugvcl/r&c/ug/Cost Data-2022-
ground 1200 mm deep and 300 mm wide trench, providing sand cushioning 23/816 Date:-27-01-2023
below (75 mm thick layer of sand) and above (75 mm thick layer of sand) of
the cable and covering it with RCC half round hume pipe (150 mm inner
diameter with thickness of 30 mm and One meter in length) before refilling
pre-bonding tap/warning tap should provide below 700 mm from the
ground level and back filling the same to make ground level as per original.
As per specification and drawing of DGVCL. ( RCC half round pipe should be
provide throughout on cable without gap).
41 Laying (including installation, testing and commissioning) of various size of mtr 468 as per rate derived by UGVCL letter
Double circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable in no ugvcl/r&c/ug/Cost Data-2022-
ground 1200 mm deep and 500 mm wide trench, providing sand cushioning 23/816 Date:-27-01-2023
below (75 mm thick layer of sand) and above (75 mm thick layer of sand) of
the cable and covering it with RCC half round hume pipe (150 mm inner
diameter with thickness of 30 mm and One meter in length) before refilling
pre-bonding tap/warning tap should provide below 700 mm from the ground
level and back filling the same to make ground level as per original. As per
specification and drawing of DGVCL. ( RCC half round pipe should be provide
throughout on cable without gap).
42 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x No 5549 as per rate derived by UGVCL letter
300 mm2 size XLPE cable as per technical specification. no ugvcl/r&c/ug/Cost Data-2022-
43 Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV No 6676 as per rate derived by UGVCL letter
3C x 300 mm2 size XLPE cable as per technical specification. no ugvcl/r&c/ug/Cost Data-2022-
44 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 300 No 8040 as per rate derived by UGVCL letter
mm2 size XLPE cableas per L technical specification. no ugvcl/r&c/ug/Cost Data-2022-
Rate as per SOR 30,00,000/-
Executive Engineer (O&M)
DGVCL, Division Office,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
TENDER APPROVAL UG 30 L PIPLODD SDN.pdf
2. BID DOCUMENT.pdf
3. Detail Technical Specification.pdf
SCHEDULE B UG PIPLOD.pdf
Download all tender documents and submit your bid