| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.6 CrAccepted-AOC 2ND FLOOR TIDEL PARK NO 4 RAJIV GANDHI SALAI TARAMANI CHENNAI TAMIL NADU 600113 | CHENNAI | TAMIL NADU | 600113 | ₹23.6 Cr | L1 | Accepted-AOC L1 Bidder.
Excluding GST |
| 2 | L2₹24.5 CrRejected-Finance | ₹24.5 Cr | L2 | Rejected-Finance L2 Bidder.
Amount excluding GST |
| 3 | L3₹25.3 CrRejected-Finance OLYMPIA PLATINA PLOT NO 33B SOUTH PHASE GUINDY CHENNAI 600032 | CHENNAI | CHENNAI | TAMIL NADU | 600032 | ₹25.3 Cr | L3 | Rejected-Finance L3 Bidder.
Amount excluding GST |
Tender Value
Refer Docs
EMD Value
₹26 L
Closing Date
24 Dec 2022, 6:55 pmClosed
Director
Kerala State IT Mission, Saangethika, Vrindhavan Gardens, Pattom, Thiruvananthapuram
Expansion and Revamping of Non-Computing Infrastructure of Kerala State Data Centres
2022_KSITM_530456_1
DDFS/nSDC/426/2014-KSITM
Open Tender
Miscellaneous Works
180 days
Thiruvananthapuram
Please refer Tender documents.
6 documents required · 6 mandatory
₹29,500
Yes
₹26 L
Online
4 Sept 2023
17 Nov 2022
26 Dec 2022
17 Nov 2022
24 Dec 2022
5 Dec 2022
18 Nov 2022 - 25 Nov 2022
28 Nov 2022
Amount
PACKAGE - CIVIL AND INTERIOR
DISMANTLING WORK
i) Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material within 50 meters lead as directed by Engineer-in-charge. ii)Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead of area 3 sq. metres and below
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead for thickness of tile 10 mm to 25 mm
Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates, bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50 metres lead
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge
Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved
Un-installation, un-mounting, taking out of AHUs, wall split ACs, Furniture’s, pipes, cables and all other material from site and keeping in a place as directed by Engineer-in-Charge
Buy back of all items such as door, windows, partitions, modular ceiling, Storage cabinets, modular desk with partitions, Glazing, Electrical cables, wires, conduits, switches, Transformer, DG, Panels, AHU, Ducts, Pipes, Chillers and IBMS system etc in SDC 1, 2 and 3.
FLOORING
CARPET FLOORING:Providing and installing 600mm x 600mm Nylon Carpet Tiles with secondary backing of P.V.C The rate shall include cutting, trimming, fixing and clearing away of residual material to a location as directed. The rate shall also include supplying and laying of a protective layer of PVC sheet of 50 microns thickness, held together with scotch tape. The laid carpet to be vacuumed after the removal of protective cover/on commissioning. In case the stains are observed in the carpet after the protective layer is removed, because of inadequate protection, the same shall be shampooed and made good to the satisfaction of the project managers.
ANTISTATIC VINYL FLOORING
P/F Homogeneous Compact vinyl flooring of 2mm thickness in tile or role form. Cost should include providing and fixing of copper strip grid under the vinyl floor and same should be connected with the Earthing
RAISED FLOORING (Height- 600mm)
Supply and fixing Access floor systems as per following specifications confirming to EN 12825 standards. Access floor system should be made from high density Calcium Sulphate and Provide Class 1 Fire Ratings and fire resistance up to 90 min as per NFPA 75. System should have antistatic property and air leakage resistance. The system should be able to withstand a minimum UDL of 1800 kg. Per sqmt. and a point load of 400 kg. The pedestal shall withstand Axial Load of 2200 kg. Panels: The entire Access floor system will provide for adequate fire resistance, acoustic barrier and air leakage resistance. Panels will be made up of inert material Calcium sulphate with laminate having Antistatic properties. The bottom of the panel should be of 0.05 mm Aluminium foil to create a fire and humidity barrier and this should provide floor’s electrical continuity. Panels will remain flat through and stable unaffected by humidity or fluctuation in temperature throughout its normal working life. The Panels edging will be UL approved. Panels will provide for impact resistance top surfaces minimal deflection, corrosion resistance properties and should not be combustible or aid surface spread of flame. Panels will be insulated against heat and noise transfer. Panels will be 600 x 600mm x 35 mm height fully interchangeable with each other within the range of a specified layout. Panels shall rest on the grid formed by the stringers which are bolted on to the pedestals. Panels should be finished with anti-static 0.9 mm Laminate and 0.45mm thick plastic edge material that is self-extinguishing and will be PVC free Panel Loading Fire Rating: The Panels will confirm to class O and Fire Rating: The Panels will confirm to class O and Class 1 Fire Ratings tested `as per CIRC 91/61 or BS 476 Part 6 & 7 (30 min).
VITRIFIED TILES (600x 600mm)
12 mm thick (mirror polished) of approved quality and shade for corridor flooring, with 4"skirting & wall in required position with readymade tile adhesive mortar of approved quality, including backing coat of cement mortar 1:3 (1: cement, 3: fine aggregate), joint filling with white slurry, cleaning, curing complete all as directed by the Engineer. The levelling of base floor to be included, laid in pattern in desired shade with adhesive 600 x 600 with pigmented additives to match shade of the stone, cleaning, cost to be inclusive of chemical treatment of approved AQUA SEALANT on surface etc complete as per directed.
FALSE CEILING
MINERAL FIBER CEILING
Modular False Ceiling: Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance ?85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt – 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawl plug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge
GYPSUM CEILING-
Providing and fixing Fireline gypsum board false ceiling for providing 120 min. fire rating in horizontal/vertical surfaces, coffers etc. as per design given in the drawings. It shall consist of GI suspension system comprising of India gypsum sections and 12.5mm thick gypsum board. The cost should include Gyp Board with GI sections including framework as necessary for AC / Light fittings, trap door in ceiling, any other cut-out as directed
PARTITIONS
GYPSUM PARTITIONS: 100mm GYPSUM board partition with two layers of 12.5 mm thick Gypsum Board on each side of the frame- screw fixed with drywall screws of 25mm & 35mm at 300mm centres to either side of 48mm. Stud (0.5mm thick having one flange of 34mm and another flange of 36mm made of GI Steel) placed at 610mm c/c in 50mm floor and ceiling channel (0.5mm thick have equal flanges of 32mm made of GI steel) anchored to the floor & true ceiling using suitable anchor fasteners or metal screws with PVC plugs. The boards are to be fixed to the framework with joints staggered to avoid leakage through joints. Rate to include making provisions in panels, grooves and finishing the same to fix soft board (0.45x1.8m) and whiteboard (1.2mx3.2m) fixed flush on the partition. Note soft board and whiteboards will be paid for separately. Rate also to include making openings for glass panels, ducts, services and doors by providing concealed frames on all sides, framework above false ceiling and any other provisions reqd. to facilitate the same, all hardware etc. all complete. 75 mm overall thickness partition with 12.5 mm thick double skin fire rated board conforming to IS: 2095: part I
GLASS PARTITIONS : Providing and fixing 12mm toughened glass of required height and length with mirror polished edges, fixed as per specified layout with patch fittings fixed as and where required, specially ordered stainless steel patch fittings as legs, tees, junctions, angles, glass to glass connectors, wall to glass connectors, L angle connectors, 2 way glass connectors with SS patti with double sided bolt including all Stainless steel bolts with nuts etc. used as and where required as per layout plan, glass to be of required length with proper support with all gap filled with silicon sealant glass to have holes/ cut outs to accommodate patch fittings, all complete as per entire satisfaction of Engineer-in-charge.
Glass partition - Fire rated
Providing and fixing non-load bearing fixed frame for fire resistant glazed Partition for 120 minutes Fire Rating, made out to a profile of dimension 60mm x 70 mm of 1.6 mm thick galvanized steel sheet as per test evidence suitable for fixing fire rated glass for 120 minutes of both integrity & radiation control (EW120) & minimum 20 minutes of insulation (EI20).
Providing and fixing 12 mm thick toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge
Toughened Glass Door 1000 X 2100 Mm with all accessories
Toughened Glass Door 1200 X2100mm (Reception) with all accessories
Door handle of 450mm tubular bar, Lock, Stopper
STEEL FIRE RATED DOOR
Providing and fixing Metal Fire door from ISO 9001:2015 certified Manufacturer. The door must have been manufactured with galvanized - GI sheet of GPSP Grade as per IS 277. All Fire doors must satisfy the requirement of latest Fire & Life Safety guidelines for 120 minutes Fire Rating with its Stability & Integrity for 120 minutes. The door must also suffice the criterion of 20 minutes insulation as per NBC 2016 guidelines. The Prototype sample of the door must carry a prior test evidence as per IS 3614 part-2 / BS 476 Part 20 & 22. The manufacturer must submit the copy of test evidence prior to start of production. The offered test certificate should either carries it's Validity or certificate must not be older than 5 years from NABL Accredited Lab i.e. Spectro / International Lab i.e. Exova / TBW etc. or by any accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The door must carry a Batch sticker with details of the door after scanning. All doors should be finished with Powder coating in desired regular RAL Shades.
Fire rated door with vision panel with PANIC BAR and all accessories- 1500 x 2400mm Double leaf Door (even Leaves) (750+750mm)
Fire rated door with vision panel with PANIC BAR and all accessories- 1200 x 2400mm Double leaf Door (even Leaves) (600+600mm)
WOODEN FLUSH DOOR
Providing and fixing ISI marked flush door shutters conforming to IS :2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters, With all accessories.
Wooden Flush doors 750x 2100mm
FINISHING
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface. Water thinnable cement primer
Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade Two or more coats on new work
Providing and applying white cement-based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete
Fire Rated Paint Provide and apply fire retardant paint of approved make and shade to give an even shade over a primer coat as per manufacturers’ recommendations after applying painting putty to level and plumb. Final finishing shall be with 2 coats of fire-retardant paint. Paint must with stand minimum 1000 degrees temperature.
FURNITURE
Modular Workstation (with Pedestal)1150 (W) x 600 (D) x 750 (H) mm (Each Seat), Top: 25 mm Thick made of Pre-laminated Particle Board with 2 mm PVC Edge-banding, Screen: Half Pin-up & Half White Marker Board, Partition: 45 mm thick, Wire Management: Wire Manager Hole on Table Top & CPU Trolley, Keyboard Provision, Half Curved Glass Divider with D-Bracket between the seat, Power Distribution Sockets: within the Table for Powering of Active Devices
2 Seater BMS room Table (with Pedestal) (H x W x D = 750mm X 2400mm X 600mm) Top: 25 mm Thick made of Pre-laminated Particle Board with 2 mm PVC Edge-banding - Wire Managers - For routing LAN & Power Cables within the Table. - Power Distribution Sockets - within the Table for Powering of Active Devices.
10 Seater Conference Room Table (H x W x D = 750mm X 2595 X 990mm) -Made of 40mm thick laminated MDF Top, powder coated metal / 25mm laminated MDF under structure as per client choice. - Wire Managers - For routing LAN & Power Cables within the Table. - Power Distribution Sockets - within the Table for Powering of Active Devices.
High back, hand rest, lumbar support, head rest, movable, hydraulic adjustable swivel, net upholstered chair
Medium back, hand rest, lumbar support, movable, hydraulic adjustable swivel, net upholstered chair
3 seater leather Upholstered sofa set with hand rest and lumbar support
1 seater leather Upholstered sofa set with hand rest and lumbar support
Glass top center table with SS legs (785mm x 500mm)
Reception Table, L-shaped of size - (1500 x 800 x 750mm)
Storage Cabinets (L x D x H = 1500 x 450 x 1800)
MISCELLANEOUS
Writing board (glass)
Pinup board
Frost film for glass with approved design
Cemented Ramp Entry to Server Room with Nitrile Finish on top
Nitrile rubber insulation for 23 mm on floor and under roof of Server Room
MS Frame for Glass Partitions:
Providing and fixing frame work for partition made of 50x50x1.6 mm hollow MS tube, placed along the walls at required spacing near opening, with necessary welding at junctions and fixing the frame to wall with steel dash fasteners of 8 mm dia, 75 mm long bolt, including making provision for opening for doors, windows, electrical conduits, switch boards etc., including providing with two coats of approved steel primer etc. complete, all as per direction of Engineer-in-charge.
Installation and Commissioning Charges
Excavating trenches of required width for cables including excavation for sockets, and dressing of sides, ramming of bottoms, depth of 1.0 m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, Trench of size- 600mm wide and 1000mm depth.
DG Set Area
Foundation for DG Area: - Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation, including dressing of sides and ramming of bottoms, also Soil Compacting, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. Including the Centering and shuttering including strutting, propping etc. and removal of formwork for DG Foundation. Steel reinforcement for R.C.C. work (for DG Set area) ready to use "cut and bend"
rebars of approved make from factory/workshop to construction site including placing in position and binding all complete upto plinth level (Thermo-Mechanically Treated bars of grade Fe-500D or more.)
Galvanized Wire Mesh for DG Set Area Shed: - Galvanized wire mesh of average width of aperture 1.4 mm and nominal dia of wire 0.63 mm
Civil Work for HVAC
Providing necessary civil works as per requirement, including:
Providing, making up and finishing of Cutouts for passing refrigerant pipes, conduit/ cables, and drainage piping through walls,
Chasing, making up and finishing of vertical walls for refrigerant piping, conduit/ cables and drainage piping.
Providing, making up and finishing of wall openings for supply air and return air ducts and collars
Providing, making up and finishing of wall openings for Fire Smoke Extraction outlets on exterior wall (Ground. First & Second Floor)
Excluded: Core cutting, if required
(FOR SDC-1) Modular False Ceiling: Providing and fixing mineral fibre false ceiling tiles at all heights of size 595X595mm of approved texture, design and pattern. The tiles should have Humidity Resistance (RH) of 99%, Light Reflectance 85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Fire Performance as per (BS 476 pt – 6 &7)in true horizontal level suspended on interlocking T-Grid of hot dipped all round galvanized iron section of 0.33 mm thick (galvanized @120 gsm) comprising of main T runners of 15x32 mm of length 3000 mm, cross T of size 15x32mm of length 1200 mm and secondary intermediate cross T of size 15x32 mm of length 600 mm to form grid module of size 600x600 mm suspended from ceiling using galvanized mild steel item (galvanised@80gsm) 50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm diameter fully threaded hanger rod up to 1000 mm length and L-shape level adjuster of size 85x25x2 mm, spaced at 1200 mm centre to centre along main ‘T’. The system should rest on periphery walls /partitions with the help of GI perimeter wall angle of size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed to the wall with help of plastic rawlplug at 450 mm centre to centre & 40 mm long dry wall S.S. screws. The exposed bottom portion of all T-sections used in false ceiling support system shall be pre-painted with polyester baked paint, for all heights. The work shall be carried out as per specifications, drawings and as per directions of the engineer-in-charge.
PACKAGE - ELECTRICAL
Power Transformer
Supply, storing, handling, installation, testing and commission of 1250 KVA capacity 11/ 0.415 KV step down Cast Resin dry type transformers with off load tap changer on HV side complete as required.
Electrical Panels
New LT Panel
Supplying, installation, testing & commissioning of Cubical Type Low Voltage Panel suitable for415 V, 3 Phase, 4 wire 50 Hz AC supply system fabricated in totally enclosed compartmentalized flush finish design from CRCA not less than 2mm thick for load bearing members and 1.6mm for doors of LT panels, 3mm thick for gland plates in split sections, including powder coating painting in approved shade, provision for incoming & outgoing with suitable capacity cable chamber, bus bar chamber having horizontal and vertical 4pole bus bars of copper/aluminium Alloy of high conductivity as per SLD enclosed herewith and DMC/ SMC bus bar supports, having short circuit withstand capacity of 36kA for 1 Sec., suitable ventilation, bottom base frame with MS channel ISMC 150 designation and fabrication of the panel shall be done in transportable sections, entire width of the panel shall have common Aluminium/ copper earth bar at the rear with 2 Nos. earth stud, connection and interconnections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 1.5 sq.mm. zero halogen fire retardant ZHFR PVC insulated copper conductor single core cable, cable alleys, detachable cable gland plates including providing and fixing the following ( Refer Tender SLD for reference )
MCCBs/ Switchgears /metering accessories.
The job includes all material cost (MCCBs & other Accessories) labour carriage of panel to the site testing and commissioning as required to complete the job as per drawing of the panel to the entire satisfaction of the Engineer in charge.
The All outgoing MCCB of all the panels should be provided with LED indication on rotary handles.
Section - 1
Incoming - 1 Air Circuit Breaker `A’
(For Grid supply - 1 & Source - 2 DG supply)
4 sets of 1600 amps 4P EDO fully draw out type air circuit breaker with built in microprocessor-based release unit for protection and measurement as per specification and with following accessories:
Phase indicating light through shall be protected by 2amps MCB’s. - 4 set
Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 4 set
Under voltage release
24 V DC Shunt trip coil
4Nos. 96 x 96 mm sq. 0-1600/ 5 amps CTR digital ammeter with 3 nos 1600/ 5 amps 15 VA CL : 1 CT’s - 2 sets
FOUR number Intelligent multifunction digital meter to read V, A, KVA, KWH, THD, PF Hz, kVARh, Vah, VARh, MD, and RS 485 port etc. with 3 Nos. resin cast CTs of 1600/5 A class 1.0 accuracy and 15 VA burden - 2 sets
CBCT WITH ELR
Load Manager
Breaker control switch
Bus Coupler
1600 amps 4P EDO fully draw out type air circuit breaker with built in microprocessor based release unit for protection and measurement as per specification - 2 sets in series connection.
Incoming - 2 Air Circuit Breaker `B’
(For DG supply)
1600 amps 4P EDO fully draw out type air circuit breaker with built in microprocessor-based release unit for protection and measurement as per specification and with following accessories:
Phase indicating light through shall be protected by 2 amps MCB’s. - 1 set
4 Nos. 96 x 96 mm sq. 0-1600/ 5 amps CTR digital ammeter with 4 nos 1600/ 5 amps 15 VA CL: 1 CT’s
Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 set
one number Intelligent multifunction digital meter to read V, A, KVA, KWH, THD, PF Hz, kVARh, Vah, VARh, MD, and RS 485 port etc. with 3 Nos. resin cast CTs of 1600/5 A class 1.0 accuracy and 15 VA burden
Under voltage release
24 V DC Shunt trip coil
Under voltage relay with timer (27)
Over voltage relay with timer (59)
CBCT WITH ELR
Load Manager
Breaker control switch
4 Nos. 96 x 96 sq.mm 0-1600 / 5 amps CTR digital ammeter with 3 nos 1600 / 5 amps, 15 VA Class I CT’s.
Bus BAR:-
4P Al bus bars (having 100% Neutral) of minimum of 2500 Amps. Capacity with heat shrinkable colored sleeves and I/C DMC/SMC bus bar supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 36 KA for 1 Sec with SPD.
Out Going Feeders:
2 Nos x 800 Amps. 36kA, 4P MCCB with Digital Energy Meter (DLM)
2 Nos x 400 Amps. 36kA, 4P MCCB with Digital Energy Meter (DLM)
1 No x 1000 A 4P ,50 KA ACB with Digital Energy Meter (DLM)
Spare feeder - 2 Nos x 400 Amps. 36kA, 4P MCCB with space for Digital Energy Meter
Spare feeder - 1 Nos.x 100 Amps. 36kA, 4P MCCB with space for Digital Energy Meter
Main LT Panel (As described above)
UPS OUTPUT PANEL- 1A & 1B
One number 800 Amps. 36kA, 4P, microprocessor release, MCCB (Ics = Icu at 415V) with K - 13 rated Isolation Transformer of 500 KVA along with 800 A 4P MCCB in by pass line with Electrical Interlocking with Main MCCB with all accessories complete
One set of Phase indication LED lamps with 2 Amps. Back up MCB, breaker ON/OFF indicating light with MCB, test terminal block set as required
CBCT WITH ELR
BUS BAR:-
4P Copper bus bars (having 100% Neutral) of minimum of 800 Amps. Capacity with heat shrinkable coloured sleeves and I/C DMC/SMC bus bar supports at required intervals complete for cross section, size supports & their spacing etc. for withstanding fault level of 36 KA for 1 Sec with SPD.
OUTGOINGS:
4 Nos x 160 Amps. 36kA, FP MCCB (Ics = Icu at 415V) with Digital Energy Meter (DLM)
2 Nos x 250 Amps. 36kA, 4P MCCB with Digital Energy Meter (DLM)
Spare feeder - 1 Nos x 250 Amps. 36kA, 4P MCCB with space for Digital Energy Meter
Spare feeder - 1 Nos x 160 Amps. 36kA, 4P MCCB with space for Digital Energy Meter
UPS OUTPUT PANEL- 1A & 1B as described above
Utility Panel
Incomer 1 Nos x 400 A 4P MCCB
Al Bus Bar 4pole 600 A - 1 set
Out Going Feeders :
40 A 4P MCB - 28 Nos
100 A 4P MCCB- 1 No
Spare Feeders
40 A 4P MCCB -5 No
Utility Panel A & B as described Above (Refer SLD)
Emergency / BMS Panel (DC Block)
Incomer 2 Nos x 40 A 4P MCCB with 2 set of MFM Meter
Al Bus Bar 4pole 40 A - 1 set
Out Going Feeders:
32 A 4P MCB - 3 No
Spare 32 A 4P MCB - 2 Nos
Emergency / BMS Panel (DC Block)
GRID SPLITTER PANEL
Incomer
One set of 2000 amps 4P EDO fully drawout type air circuit breaker with built in microprocessor-based release unit for protection and measurement as per specification and with following accessories:
Phase indicating light through shall be protected by 2 amps MCB’s. - 1 set
Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 set
Under voltage release
24 V DC Shunt trip coil
3 Nos. 96 x 96 mm sq. 0-2000/ 5 amps CTR digital ammeter with 3 nos 2000/ 5 amps 15 VA CL: 1 CT’s
One number Intelligent multifunction digital meter to read V, A, KVA, KWH, THD, PF Hz, kVARh, Vah, VARh, MD, and RS 485 port etc. with 3 Nos. resin cast CTs of 2000/5 A class 1.0 accuracy and 15 VA burden
Load Manager
Breaker control switch
BUS BAR - 2500 A, 4P Al Busbar - 1 set
Out Going Feeders
800 A 4P ACB - 1 Nos (For 400 A capacitor)
1250 A 4P ACB - 1 Nos (Feed to Existing LT Panel)
1600 A 4P ACB - 2 Nos (Feed to New LT Panel)
GRID SPLITTER PANEL
DG Splitter Panel
Incomer
2 x 1600 A 4P EDO fully drawout type air circuit breaker with built in microprocessor-based release unit for protection and measurement as per specification and with following accessories:
Phase indicating light through shall be protected by 2 amps MCB’s. - 1 set
Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 set
Under voltage release
24 V DC Shunt trip coil
3 Nos. 96 x 96 mm sq. 0-1600/ 5 amps CTR digital ammeter with 3 nos 1600/ 5 amps 15 VA CL: 1 CT’s
One number Intelligent multifunction digital meter to read V, A, KVA, KWH, THD, PF Hz, kVARh, Vah, VARh, MD, and RS 485 port etc. with 3 Nos. resin cast CTs of 1600/5 A class 1.0 accuracy and 15 VA burden
Load Manager
Breaker control switch
Bus Coupler - 1 x 1600 A, 4P EDO ACB with all accessories with Indication Lamps & ON/Off Trip.
BUS BAR - 1600 A, 4P cupper Busbar - 1 set
Interlocking (Mech & Electrical with mini PLC for auto command to run one DG - 1 in failure of Grid power & vice Versa & back to switch off the DG once resume the Grid power - 1 set.
Out Going Feeders
1600 A 4P ACB - 1 Nos (Feed to Existing LT Panel)
1600 A 4P ACB - 1 Nos (Feed to New LT Panel)
DG Splitter Panel (As described above)
400 A CAPACITOR BANKS WITH AUTOMATIC CONTROL PANELS
Incoming
800 amps TPN ACB ,50 KA with following accessories.
MFM 1 SET
Phase indicating light through 415 V supply from 415 V shall be protected by 2 amps TP MCB - 1 Set
Bus Bars:
800 amps TP copper bus bars with coloured heat Shrinkable insulated sleeves.
Outgoings:
Outgoing feeders consisting of following accessories.
125 amps TP MCCB - 6 Sets.
125 amps TP capacitor duty 415 volts 50Hz heavy duty contactors. 6 Sets
63 amps TP MCCB - 4 Sets.
63 amps TP capacitor duty 415 volts 50Hz heavy duty contactors - 4 Sets
“ON” /” OFF” push buttons and indicating lamps - 10 sets
150 & 80 A amps rating TP terminal blocks
50 KVAR mixed dielectric extra low loss type capacitor unit - 6
25 KVAR mixed dielectric extra low loss type capacitor unit 4
All MCCB’s shall be of 35 KA breaking capacity.
Automatic Control Panel with 400 KVAR Capacitors including 7% detuned reactor as described above.
Supply and installation and commissioning of outdoor type ACB Panel for Temporary DG set with comprising the followings: 1No - 1600A 4P ACB Micoprocessor based release with O/C, S/C, UV release 1No -1600A/5A CT, 1No -MFM with RS485, 1set -indication lamps 1lot -control MCBs
BUS BAR TRUNKING (BBT) SYSTEM
Supplying, installation, testing & commissioning of Air insulated compact type copper bus bar trunking system, with vertical & horizontal bends, with joints where ever required. BBT shall be with hitch support rods with adjustable height, supports shall be given at suitable intervals as required. Max. length of the rod shall be 1000mm. Bends shall not be measured separately, bends shall be considered as straight pieces & measured along the centre line of BBT and support. The BBT should be as per SLD & detailed Specifications attached
Supplying, installation, testing & commissioning of Air insulated type bus bar trunking system (indoor), System voltage - 600 V & Insulation voltage of 1000V, 4pole, with neutral of 100% of phase conductor rating & externally mounted aluminium earth bus , Short circuit rating of 25 KA, IP-2X, with capability to place tap off boxes anywhere on the entire length without distance restrictions’ and color coding for easy identification of connected power supply as per SLD &detailed Specifications attached.
160 A ,4P (As described above)
Supplying, installation, testing & commissioning of 160 A End Flange Unit 4 pole with RYB indicating lamps & MCB, powder coated, with suitable bus bar to terminate necessary cables as per SLD & detailed Specifications attached.
Supplying, installation, testing & commissioning of 160 A End cap at the end of the every BBT as per SLD & detailed Specifications attached.
SITC of Tap Off Boxes with suitable rating of connectors as per requirement
Final Distribution Board
MCB DBs : Double Door with IP42 protection, prewired as per technical specification. .
Incomer- 40A, 4P, MCB
Outgoing - 18 Nos - SP, 6/10A MCBs with complete accessories
Incomer-40A, 4P, MCB
Outgoing - 18 Nos - SP, 10/20A MCBs
IBMS DB
Incomer-32A, 4P, MCB
Outgoing - 12 Nos - SP, 10/20A MCBs
Emergency LDB
Incomer- 32A, 4P, MCB
Outgoing - 18 Nos - SP, 10/20A MCBs with complete accessories
CAC DB
Incomer- 100A, 4P, MCB
Outgoing - 32A DP- 07 Nos
40A TPN- 05 Nos
WS DB (WorkStation DB)
Incomer- 25A TPN
Outgoing- 16/10A SP-12Nos
MCB ENCLOSURE
63A, 4P, ELMCB in an outdoor enclosure (IP54)
MCB ENCLOSURE
40A, 4P, ELMCB in an outdoor enclosure (IP54)
8 Way SPN DB with I/C 32 A DP MCB + 6 Nos x 10 A SP MCB Double Door with all accessories.
16 Way AC DB with I/C 40 A DP MCB & O/G 6 Nos x 16 A DP MCB Double Door with all accessories.
16 A Metal clad single Phase MCB Box
63A, 4P, MCCB (In the output Panel of 20Kva UPS of SDC2
Light Fixtures
* Catalogue numbers indicated are only to know type of light fixture required.
* All electronic ballast shall have THD: less than 10%.
* All copper ballasts shall be of low loss type (max-4W).
Recess mounted down lighter suitable for 15 W (100 Lumen/watt) LED with electronic ballast
Recess mounted light fixture suitable for 1 x32 W LED (125 Lumen/watt) 600mmx600mm with electronic ballast suitable for Grid Ceiling
4 ft, LED Tube Light fixture suitable for 28 W (125 Lumen/watt) with electronic ballast.
Recess mountable stand-alone PIR presence detector. The device should be able to Switch & Regulate a Lighting load of at least 8 DSI Ballasts based on Human Presence availability. Detection coverage of 6m dia when mounted at a Height of 3m. The device should be equipped with a Field adjustable delay timer (5 - 60 mins).
CABLES & END TERMINATIONS.
1100 V grade, stranded (above 10Sq.mm) Copper/aluminium conductor, XLPE insulated, PVC Inner sheathed, armoured, FRLS Outer sheath cables as per IS1554. The cables shall be laid in tray/built up trench etc., Rate shall exclude cost of tray/trench.
End termination: Providing end Termination of cables with supply of brass, double compression cable glands & solderless crimping type aluminium lugs for aluminium cables & copper lugs for copper cables. End termination shall also include braided earthing cable & clamp for cable glands.
ALUMINIUM CABLE
4Cx 400 Sq.mm Al. Ar FRLS XLPE
4Cx 300 Sq.mm Al. Ar FRLS XLPE
4Cx 240 Sq.mm Al. Ar FRLS XLPE
4Cx 185 Sq.mm Al. Ar FRLS XLPE
Supply and laying of 3CX185SQ.MM.11KV(E) HT UG Cable.
ALUMINIUM END TERMINATIONS
4Cx 400 Sq.mm Al. Ar FRLS XLPE
4Cx 300 Sq.mm Al. Ar FRLS XLPE
4Cx 240 Sq.mm Al. Ar FRLS XLPE
4Cx 185 Sq.mm Al. Ar FRLS XLPE
Supply and providing of 3CX185SQ.MM.11KV(E) HT UG Cable endtermination kit indoor type (If Required)
COPPER CABLES
1100/650 V Grade, PVC insulated, Single/multi Core, multi strand Unarmoured (YY)/armoured-YWY Copper Conductor Cables. The cables shall be laid in cable tray & all single core cables shall be laid in trefoil form with necessary clamps.
Providing end termination of cables with supply of suitable cable glands with earth clips, solderless crimping type copper sockets for Copper cables.
4Cx 16 Sq.mm CU. FRLS
4Cx 10 Sq.mm CU. FRLS
1Cx 95 Sq.mm CU. FRLS
1Cx 240 Sq.mm CU. FRLS XLPE
1Cx 120 Sq.mm CU. UnAR. FRLS XLPE
4Cx 2.5 Sq.mm CU. AR. FRLS XLPE
1Cx 120 Sq.mm CU. UnAR. FRLS XLPE
4Cx 2.5 Sq.mm CU. AR. FRLS XLPE
1C x 240 Sq.mm CU. FLEX FRLS (GREEN)
1C x 120 Sq.mm CU. FLEX FRLS (GREEN)
1C x 95 Sq.mm CU. FLEX FRLS (GREEN)
1C x 70 Sq.mm CU. FLEX FRLS (GREEN)
1C x 10 Sq.mm CU. FLEX FRLS (GREEN)
1C x 6 Sq.mm CU. FLEX FRLS (GREEN)
Copper END TERMINATIONS
4Cx 16 Sq.mm CU. FRLS
4Cx 10Sq.mm CU. FRLS
1Cx 95 Sq.mm CU. FRLS
4Cx 240 Sq.mm CU. FRLS XLPE
1C x 240 Sq.mm CU. FLEX FRLS (GREEN) TERMINATION
1C x 120 Sq.mm CU. FLEX FRLS (GREEN) TERMINATION
1C x 95 Sq.mm CU. FLEX FRLS (GREEN) TERMINATION
1C x 70 Sq.mm CU. FLEX FRLS (GREEN) TERMINATION
1C x 10 Sq.mm CU. FLEX FRLS (GREEN) TERMINATION
1C x 6 Sq.mm CU. FLEX FRLS (GREEN) TERMINATION
SUB Main Wiring
Wiring of Sub Mains/circuit mains in concealed or surface conduit system with 2mm thick MS conduits & 1100 V grade, multi strand copper conductor, FRLS insulated wires asper IS694, for phase, neutral & earth, shall include end termination. The conduits shall be complete with bends, JBs etc,. The laying cost shall also include supports/anchor rods for conduits & chipping works if necessary.
3Rx1.5 sq.mm cable, multi strand copper wire in 25mm dia MS conduit with accessories.
3Rx 2.5 sq.mm cable, multi strand copper wire in 25mm dia MS conduit with accessories.
3Rx 4.0 sq.mm cable, multi strand copper wire in 25mm dia MS conduit with accessories.
POINT WIRING
Primary Light Point controlled by 6 A Switch
Loop Points for above.
Primary Light Point controlled by MCB (MCB not in scope)
Loop Points for above.
POWER RECEPTACLES.
Supply, installation of switched socket outlets, modular socket outlets and switches mounted separately for group control on wall and modular type partition with front plate & accessories including civil works like chipping etc. There is no circuit, sub-circuit measurements. All sockets shall be provided with suitable stickers to indicate the UPS/RP source, ckt. Nos. etc..
Wiring for 250 volt single phase and neutral 2 x 6 amps switch socket outlet with 2.5 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLS wires in concealed or surface mounted 25 mm dia 16 gauge MS conduit, including providing and fixing of 6 amps 3 pin switched socket of approved make colour and design in 16 gauge GI box with grid plate and earthing of third pin of the socket outlet and the GI box with 2.5 Sq.mm PVC insulated copper conductor stranded flexible FRLS wire ( For UPS & Raw Power )
Wiring for 250 volts single phase and neutral 3 x 13 amps switched socket outlet with 4 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible FRLS wires in concealed or surface mounted 25 mm dia 16 gauge MS conduit, including providing and fixing of 2 nos. 16 amps 3 pin switched socket of approved make and design in 16 gauge GI boxes with grid plates and earthing the third pin of socket outlet with 4 Sq. mm PVC insulated copper conductor stranded flexible FRLS wire (Three nos. switched socket outlet connected on one circuit).
Wiring for 250 volts single phase and neutral 1 x 16 amps switched socket outlet with 4 sq.mm PVC insulated copper conductor 1100 volts grade stranded FRLS wires in concealed or surface mounted 25 mm dia 16 gauge MS conduit, including providing and fixing of 16 amps 3 pin switched socket of approved make and design in 16 gauge GI boxes with grid plates and earthing the third pin of socket outlet with 4 Sq. mm PVC insulated copper conductor stranded FRLS wire.
EARTH ELECTRODES AND EARTH STRIPS
Earthing Pits
Providing and laying of 600 x 600 x 6.3 mm thick GI plate electrode, with 2 nos. 40 X 6 mm GI strips from earth plate electrode to inspection chamber, 50 mm dia medium class GI Perforated pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 450 X 450 mm with concrete base CI manhole cover with frame painted with bitumastic paint and packing with mixture of charcoal and common salt around plate electrode including digging of pit up to permanent moisture level but not less than 3 meters and back filling as required.
Supply, Unloading, Handling, Installation, Testing, Commissioning & Handing Over of 600 x 600 x 3.15 mm thick tined copper plate electrode, with 2 Nos 32 x 6 mm copper strips from earth plate electrode to inspection chamber, 50 mm dia medium class GI perforated pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 450 x 450 mm with concrete base C I heavy duty / chequered plate manhole cover with frame painted with bitumastic paint and packing with mixture of charcoal and common salt around plate electrode including digging of pit up to permanent moisture level and as per soil condition but not less than 3 meters and back filling as required. The pipe shall have provision for watering through a funnel. It shall also have provision for connecting 25 x 6 mm. Copper Flat on two sides.
1) Earthing stations should contain relevant grade of charcoal/coke and salt packed around the earth plate/earth pipe as called for in the item.
2) Adequate number of earth strips with proper sized holes shall be provided for extending earthing/looping earth connections at various floors shall be provided and executed as per the requirement.
3) All earth pits shall be as per IS 3043 with latest amendments.
4) Earthing shall be done at indicted location by the Consultants. The minimum distance between the two-earth station shall be 3 meters and that from the building is 2500 mm.
Earthing Strips
50 x 6 mm GI. Strip with for body earthing of panels.
25 x 6 mm GI. Strip in PVC Sleeve
25 x 3 mm GI. Strip in PVC Sleeve
32 x 6 mm Copper strip in PVC Sleeve.
8 swg GI wire
19 x 3 mm Copper strip for SRG Earth
MISCELLANEOUS ITEMS
Ladder type cable tray
Tray shall be of GI & made out of 2mm thick GI sheet, bent in 'C' shape with adequate load bearing capacity.
Size of Cable Tray: 600 mm x 50 x 50 mm
Size of Cable Tray :450 mm x 50 x 50 mm
Size of Cable Tray :300 mm x 50 x 50 mm
Supply fabrication and erection of vertical cable chamber which is attached with existing 1No-1250A ACB panel and also provide full height CRCA sheet folded door for the same panel (if required)
Supply and fixing of 11KV 160/5A class 0.5 5VA cast resin type CT and its complete busbar interconnections. The scope also inclusive removing of existing CT.
Preparation of CEIG drawings, obtaining of CEIG approvals ,documents preparation, arranging inspection and getting Safety certificate
Supply and fixing of cable idendification tag to all incoming and outgoing cables
Charges for Hiring crane
Towards charges for rental DG with cable - 600KVA
Supply of Diesel
Supply and fixing of Pop up box with 2x10Amps, 2x10A socket
Supply and fixing of Pop up box suitable for 2Nos x HDMI & 2xRJ45 port
DG Area lighting work , the scope inclusive of SPN DB, light fixtures and its cabling work
Perforated type cable tray
For Electrical
Size of Cable Tray :50 X 300 X 50 mm
Size of Cable Tray :50 X 200 X 50 mm
Size of Cable Tray :50 X 150 X 50 mm
Size of Cable Tray :50 X 100 X 50 mm
Shock treatment chart laminated
First aid kit
Rubber mat 1100V grade ISI approved 2 m x 1m.
Temporary Lighting and DB for Power Supply to all service Vendor for Data Centre Construction.
UPS System
UPS Systems 500 kVA/kW for IT/Server Load:
Supply , installation, testing & commissioning of IGBT based, Dual Conversion Modular 500 kVA/kW UPS system ,wide input voltage range ( 229 V~478 V ) , 3 phase (415 V ± 15%) Volts input & 3 phase output (415 V ± 1%), 50 Hz, unity power factor ( Output ),TDHi % <3% at full linear load ,Inverter overload capacity :110% for 60 min; 125% 10min; 150% for 1 min ,Online mode efficiency up to 96.4% , Protection level of IP20.
Li-ion Battery for IT/Server Load:
Supply, installation, testing & commissioning of Battery set with 15 minutes back up along with Battery racks, copper cables between batteries, copper cables between UPS & batteries, DC MCCB Box. The breaker & cable sizing will be done as per the technical specs. average UPS to battery bank distance shall be 10 meters or as per site requirement. Li-ion Battery Bank with 15 minutes battery backup for each UPS in suitable for (N+N) configuration complete in all respect .
Diesel Generator and accessories
Supply & Installation of 1010 KVA SILENT DG Set developing minimum 1180 BHP Coupled to 1010 kVA, 415 V alternator mounted on a common base frame, complete with:
(a) Fuel tank 990 Litres. (Outside Enclosure)
(b) Batteries & Leads.
(c) AVM Pads
(d) Silencer.
(e) First fill of lube oil.
(f) Radiator
Acoustic Enclosure
Load side terminal box
EXHAUST SYSTEM
Supply and installation of exhaust piping of following sizes MS B Class exhaust pipes conforming to IS:3589 with welding joint including bends, clamps, dash fastener, flanges, nuts, bolts etc. complete as required and as per specifications detailed below.
10" dia. (250 mm NB), MS, 4.85 mm thick plate, Exhaust pipe
14" dia. (350 mm NB), MS, 4.85 mm thick plate, Exhaust pipe
Supply and installation of 50mm thick glass wool/ mineral wool, wire chicken mesh over insulation and 24 gauge aluminium sheet cladding over the following sizes exhaust pipes from silencer to atmosphere.
10" dia. (250 mm NB), MS, 4.85 mm thick plate, Exhaust pipe
14" dia. (350 mm NB), MS, 4.85 mm thick plate, Exhaust pipe
Supply and installation of Aluminium cladding for residential silencers with Mineral Wool 50mm Thick, density 64 Kg/cu. mtr., wire mesh and 24gauge aluminium cladding.
Supply and installation of SS Flexible Bellows, 14" dia. (350 mm NB), complete with counter flanges, heat resistant gaskets, nuts-bolts-washers etc., complete as required.
Supply and installation of MS Support structure The MS Structure. will be duly coated with two coats of red-oxide primer and two coats of enamel paint. The colour shade of final paint will be as decided by the client.
Supply and installation of Lightning Arrestors Non-Seamer Type with GI Strip up to Earth Pit
FUEL SYSTEM
Supply and Installation of MS Class C Pipe 25 mm ID with Bends, flanges packing as required. (Considering DG set to be placed at a distance of 5-6 mtr)
Supply and fixing of set of Fuel Pipe fittings like valves, tee, elbows etc.
POWER CABLES
3.5C x 240 sqmm, 6 runs, PVC Insulated XLPE, 1.1kV grade Aluminium armoured type cable (considering panel placed at a distance of 20 mtrs)
Cable termination kit for 3.5Cx 240 sqmm power cable
CONTROL CABLES
Supply & laying of Power & Control Cables
24C x 2.5 Sqmm CU armoured Control Cable.
4C x 2.5 Sqmm CU armoured Control Cable.
2C x 2.5 Sqmm CU armoured Control Cable.
2C x 4 Sqmm CU armoured Control Cable.
3C x 6 sqmm
Providing & Fixing of Cables End Termination for following size of cables
24C x 2.5 Sqmm CU armoured Control Cable.
4C x 2.5 Sqmm CU armoured Control Cable.
2C x 2.5 Sqmm CU armoured Control Cable.
2C x 4 Sqmm CU armoured Control Cable.
3C x 6 sqmm
Removal of existing DG sets along with synchronisation panel and buying it back
SITC of Two iPDU's in each rack with different color chassis, 32A, 230V with UL certified hybrid outlets (can be utilised as C13 or C19). 3-meter-long and inlet cable with input plug type should be IEC603029 2P+E, Splash proof IP44. Monitoring capability at Strip and circuit/breaker level. With metering accuracy of +/- 1% compliant to ANSI C12.1 and IEC 62053-21 with monitoring capability at strip level, the iPDU should have color coded outlets based on circuit breaker color for easy identification of circuits for quick troubleshooting and ease in maintenance.
SITC of Three sensors for each rack (two in the front and one in the back) covering one data point for dew point and air flow along with three data points for temperature- humidity. Sensors should be integrable with supplied iPDUs.
Recess mounted light fixture suitable for 1 x32 W LED (125 Lumen/watt) 600mmx600mm with electronic ballast suitable for Grid Ceiling (For SDC -3)
4 ft, LED Tube Light fixture suitable for 28 W (125 Lumen/watt) with electronic ballast. (For SDC-1)
Recess mounted light fixture suitable for 1 x32 W LED (125 Lumen/watt) 600mmx600mm with electronic ballast suitable for Grid Ceiling (For SDC -2) OPTIONAL
4 ft, LED Tube Light fixture suitable for 28 W (125 Lumen/watt) with electronic ballast. (For SDC-2) OPTIONAL
PACKAGE - HVAC SYSTEM
Precision air conditioning
SITC of Precision air conditioner with horizontal air flow pattern, can be placed in-between the racks or at the ends of rows, (Depth 300 mm max) close to the heat source with min 26 kW capacity at site condition. Inside of Cold Aisle should maintain 23+/-1 oC, 50+/-5% RH. Unit should have Variable Scroll compressor compatible with R410a refrigerant, EC plug fan locking disconnect switches fan, condensate pump, Adjustable baffle system, Heater, Humidifier, G4 (EU4) gravimetric + Clogged Filter, Display with temperature & Humidity Control. Outdoor Condenser unit shall comprise of Copper coil with Aluminum fins and Axial fan with fan speed controller motor. The microprocessor control system should have requisite sensors & BMS card for advanced diagnostic and maintenance support, enabling multiple units to communicate and work together as a team to precisely control temperature and humidity across a room. In addition, the controller network should provide a choice of Teamwork, Lead/Lag and Cascade functions.
Refrigerant pipe (include interconnecting insulated copper piping of suitable size as per manufacturer between indoor & outdoor unit)
Min 26KW net sensible capacity (at site condition)
Supply, Installation, Testing & Commissioning of 4 way Cassette type Indoor Unit (approx. size 600mm x 600mm) , sophisticated decoration panel with 360 degree airflow, with filter and with motorised louvres, 3 step airflow control, Dx type, electronic control valve, dual suction fan, statically and dynamically balanced , cooling coils of seamless copper tubes, cleanable type filters with anti-mould and anti-bacterial treatment , drain pump, PID Control, fixtures and supports complete in all respect, of following capacities: The price should include interconnecting insulated copper piping between indoor & outdoor unit of minimum 20m length & complete in all aspect.
High sensible split units should have intelligent microprocessor controller to take care of proper and efficient working of the units. Controller should have provision to communicate with multiple units up to 8 nos (considering future expansion), Unit to have temperature sensors for monitoring supply and return air temperatures. Unit to have RS485 communication protocol for remote monitoring. High sensible units should have all necessary refrigeration and electrical safety. Unit to have HP/LP switches/transducer etc., and to have all phase protection, voltage protection and necessary sized MCB. The price should include interconnecting insulated copper piping of suitable size as per manufacturer between indoor & outdoor unit of minimum 20m length & complete in all aspect. Note- All Hi-wall units and celling Suspended Units should have the capability to run in sequence mode.
Capacity of each unit - 3TR (3W+1S) (High wall & high sensible
Capacity of each unit - 2TR (Normal Split AC)
Supply and installation of control cum transmission wiring of copper in suitable size of 2Cx1.5 sqmm/2.0sqmm as per manufacturer's specification in MS conduit along with terminations lugs, glands, tagging etc Supply and installation of UPVC piping complete with fittings, supports as per specifications and duly insulated with 13 mm thick nitrile rubber insulation, complete in all respect:
25 mm dia
32 mm dia
40 mm dia
AISLE CONTAINMENT
The Containment uses a series of panels, door frames and doors, and air blocks to enclose a cold aisle zone which contains cooling unit supply air
The cold aisle zone is the space between two rows of IT equipment racks with cold air being supplied between the two rows of racks (or one row of racks and an architectural wall) and the IT equipment exhausts hot air away from the aisle. In this enclosed space cooling unit supply air is collected inside of the Containment. The cool air is supplied to the IT equipment while the IT equipment exhaust air is pushed outside the Containment and returned to the cooling unit.
By preventing mixing of cool supply air and hot exhaust air, this self- contained configuration is capable of supporting a complete range of low, medium and high power/heat density loads, and can be deployed in multiple environments without affecting the surrounding area.
The Cold Aisle Containment Glass has to withstand temperature of 80 celsius
Ceiling Panel
Ceiling panels shall be minimum 5.0 mm or more thick Lexan clear-ribbed panels or 2.36 mm thick V0 clear panels with aluminium framing.
Flame spread rates: Smoke development index "0-65" and flame spread index “0” in accordance with UL723 or ASTM84. Nominal thickness: 2.36 mm (V0 clear) –or-- Smoke development index "20" and flame spread index "0" in accordance with UL723 or ASTM84. Nominal thickness: 6.0 mm (Lexan)
Minimum Light Transmission per ASTM D1003 equal to 82% or greater.
Ceiling panels shall be designed to be supported by the frames of the IT Equipment racks. Ceiling Panel frames sizes shall be suitable to match up with various rack widths, row width, and aisle widths.
The ceiling system shall be designed to permit removal of the ceiling panel from within the contained zone without the use of tools for service access to the space above the Aisle
Door Frames and Door
Metal door frames and doors shall be provided to establish air containment at the end of two rows of racks. The door frame system shall match the height of the rack-based equipment, and match the design width of the contained aisle
Doors shall be Sliding, to permit access into the contained aisle for maintenance or servicing
Doors shall be provided with a window and handles
Automatic door closure system for sliding door
Frames and Component Seal
Foam Rubber gaskets or metal/composite, brush, or plastic air blocks shall be installed at Aisle joints to minimize open gaps between containment system components, such as door frames, ceiling and duct panels, and IT Equipment racks and rack-based equipment. Gasketing and/or air blocks may include, but not be limited to, the following.
Joints between adjacent ceiling/duct panels
Joints between ceiling/duct panels and top of racks, if not metal to metal
Joints between door frames and ceiling/duct panels, if not metal to metal
Joints between door frames and racks at the end of the row
Joints between rack bottom rear frame and floor
Joints between duct panel and ceiling/roof of room
Blanking Panels, Height Adapters, and Depth Extenders
Can be used to provide an aesthetic alternative for varying dimension enclosures
Blanking Panels shall be placed where gaps between racks exist to seal contained aisle. The panel shall match the height of the enclosures and match the width of the gap. It shall not be mounted to any adjacent blanking panels nor shall it support any adjustable height supports.
Depth Extenders shall mount to front or back of enclosures to align aisle. The extender shall match the depth of the adjacent racks and match the width and height of the enclosure (including any height adapters) of which it is being mounted
Height Adapters shall mount to the top of enclosures to align the enclosure height. The height adapter matches the height of the adjacent racks and shall match the width and depth of the rack (including any depth adapters) of which it is being mounted
Installation, Testing and Commissioning has to be done by Engineer.
Lighting for Containment
09 Watts round LED light
Cable Tray
Supplying and installing on the floor or ceiling, the following sizes of rung type ladder or perforated cable trays with epoxy finish as per the Architect's drawing and rate to include for all necessary supporting brackets, clamps, saddles, fixing hardware etc.
450 X 50 Perforated cable tray
450 X 50 Ladder cable tray
300 X 50 MM Ladder Cable tray
Supply & Installation of MS Fabrication support for Cable tray
PACKAGE - SAFETY SECURITY SURVEILLANCE AND MONITORING
LOCATION - SDC -1
Fire Alarm System
Fire alarm Control panel Comprised of the following system components:
Operating units, Periphery boards, Power supplies, System enclosures, 170Watt power supply. The panel must support or comply to:
-one (1) to four (4) ‘Class B’; one (1) to two (2) ‘Class A’
-Includes one (1) ‘Class A’, or two (2) ‘Class B’ notification appliance circuits (NACs)
Intelligent Addressable Multi-Sensor Smoke detector:
Intelligent Addressable Type Manual Call Point:
Intelligent Manual Fire Alarm Box is constructed of durable, moulded and polycarbonate material that is matte finished in red with raised white lettering Single-action,
- Pull-down lever shall remain down, until manually reset
- connectivity shall be Polarity insensitive via SureWireTM technology
- device programming vide Electronic programming with self-test facility
Short circuit Isolator Base:
Requires no programming
Does not occupy a device address
Local light-emitting diode (LED) indicator
Conventional Type Hooter with Strobe:
Response Indicator for below false floor detector
Intelligent Addressable Relay control module for Hooter + Control module for 3rd Party equipment (Precision AC unit)
Interfacing and supervising normally open (N.O) or normally closed (N.C) contacts, Integral single-pole, double-throw (SPDT) relay (up to 4 amps), Multi-color light-emitting diode (LED) indicates system status:
Intelligent Addressable Monitor module for VESDA:
Interfacing and supervising normally open (N.O) or normally
closed (N.C) contacts, Integral single-pole, double-throw (SPDT) relay (up to 4 amps), Multi-color light-emitting diode (LED) indicates system status:
2 core x 1.5 sq.mm Armoured FRLS cable
Supply & Installation of CO2 Type Extinguishers - 2 Kg
Supply & Installation of GLOW SIGNAGE
Public Address System
6 Watt Ceiling speaker: The loudspeaker can be used for reproducing music as well as speech. The speaker assembly consists of a single-piece, dual cone loudspeaker and frame, with a 100 matching transformer mounted on the back. A circular metal grille is an integrated part of the front. 1.5W,3W,6 Watt various tapping
9 Watt Ceiling speaker: Rated voltage 100V,. 1.5W,3W,6 Watt various tapping
Mixer Amplifier with Microphone
240 Watt Amplifier
2 core 1 sq.mm Armoured
2 core 1 sq.mm Armoured
RACK 9U
CCTV SYSTEM
IP based Dome camera with fixed lens,2 Megapixel Full HD Network IR Dome Camera
IP based Dome camera with Varifocal lens,Max. 2M (1920 x 1080) resolution
• 2.8 ~ 12mm (4.3x) varifocal lens,IR viewable length 30m, IP66, IK10,Motion detection, Tampering, Defocus detection
NVR: 16 CH Network Video Recorder, with 6month storage backup
21" LED Monitor
24 Port 10/100/1000 Mbps L2 Managed switch
CAT6 Armoured Cable
ACCESS CONTROL SYSTEM
Intelligent 8 Reader Door Master Access Controller, via a 10/100Mb Ethernet connection, Support for 500,000 cardholders
- Operating voltage 8 to 40 VDC, 8 to 30 VAC
- Operating temperature 0 to +50 °C (32 to +122° F)
- Card capacity 40,000
Dual Reader Interface (DRI): Interface module for up to two card readers, supports all popular reader technologies, Auxiliary 12VDC power source (min. voltage input 18VDC), Lock / door strike output (relay driven), Request-to-exit input, Door contact input, Communications status LED, Activity status LED, Power status LED
Eight Reader Interface (ERI): Interface module for up to eight card readers, Supports all popular reader technologies, Auxiliary 12VDC power source (min. voltage input 18VDC), Lock / door strike output (relay driven), Request-to-exit input, Door contact input , Communications status LED ,Activity status LED, Power status LED
Power Supply Unit with battery back-up for Controller and Door Interface modules
Biometric Reader for Server room
iCLASS SE R10 Reader (Entry/Exit): iCLASS Seos: 2.4” (6 cm), indoor/Outdoor IP55; IP65 if installed with optional gasket, Wiegand, Clock-and-Data, Open Supervised Device Protocol (OSPD) via RS485, UL94 Polycarbonate
Electromagnetic lock - 600 lbs with ZL / UL bracket, as required - Single Leaf
► Voltage Input: 12 VDC / 24 VDC
► Current Draw: 12V / 500mA; 24V / 250mA (±5%)
► Holding Force: Up to 600 lbs (272 kg)
Electromagnetic lock - 600 lbs with ZL / UL bracket, as required - Double Leaf
Resettable Emergency Release Switch
Magnetic Contact
Access Control Software & time attendance:
l Anti-pass back
3 wrong PIN mode
Time scheduling
Manual system override capabilities
Enrolment reader support
Multi-user, multi-tasking environment
PC for Access control software
6 core x 1 Sq.mm - Armoured
4 core x 1 Sq.mm - Armoured
2 core x 1 Sq.mm - Armoured
Cat6e cable - Armoured
Exit Switch
Access Cards
Novec Based gas Suppression System for Server Room and communication room
SITC of CCOE Approved Seamless NOVEC1230 Cylinder and Valve Assembly, 120 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised to 42 bar.
Master Completer Kit complete with Solenoid, Pneumatic actuators, Pressure
Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses and connectors. For Multiple cylinder system -VDS/UL approved
Slave Completer Kit complete with Pneumatic actuators, Pressure Gauge, Low
pressure supervisory switch, Discharge hoses, Flexible actuation hoses, manual actuator and connectors. -VDS/UL approved
SITC of NOVEC1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
Manifold to cater Multiple Cylinder Bank
MS Powder coated 2"x2" hollow box frame Cylinder(s) support assembly with manifold support system duly fastened to the slab floor & wall / Ceiling complete with cylinder brackets / U clamps etc. Need to distribute the floor load
SITC of NOVEC Piping & Manifold as required, Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & Support the Manifold and Piping properly.
Complete with Pressure testing for piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen prior to handover.
Detection Systems
Supply installation Testing & commissioning of Single zone Gas Release Panel facility to connect Manual Abort/Release switches. The Panel shall provide Potential free contacts for First knock, second knock, Trouble / Fault Status.
The Panel shall be Complete with Red Colour Housing, Power supply unit, Battery charger & batteries
Manual Release Switch
Abort Switch
Novec 1230 System - UPS room
SITC of CCOE Approved Seamless NOVEC1230 Cylinder and Valve Assembly, 80 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised to 42 bar.
Master Completer Kit complete with Solenoid, Pneumatic actuators, Pressure Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses and connectors. For Multiple cylinder system -VDS/UL approved
Slave Completer Kit complete with Pneumatic actuators, Pressure Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses, manual actuator and connectors. -VDS/UL approved
SITC of NOVEC1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
Manifold to cater Multiple Cylinder Bank
MS Powder coated 2"x2" hollow box frame Cylinder(s) support assembly with manifold support system duly fastened to the slab floor & wall / Ceiling complete with cylinder brackets / U clamps etc. Need to distribute the floor load
SITC of NOVEC Piping & Manifold as required, Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & Support the Manifold and Piping properly.
Complete with Pressure testing for piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen prior to handover.
Rodent VHFO system
VHFO master controller can drive up to 20 transducers.
TRANSDUCERS
Wire Bundle
PVC Conduit 20mm
Water leak detection
Conventional 6 Zone Water Leak detection panel with Modbus RS485
Water leak detection cable sensor
Electronic Hooter
2 core x 1.5 sq.mm Armoured cable
Aspiration Detector (Early warning Detection)
Single channel Aspirating Detector, coverage 500 SQM (2*25 M Pipe length maximum) for server room only
Single channel Aspirating Detector, coverage 800 SQM (2*60 M Pipe length Maximum)
Power Supply with Battery backup Unit
Air termination Nozzles with Capillary set
Aspiration 25mm OD CPVC Sampling Pipes with accessories
Electronic Hooter with mounting arrangement
2C x 1.5 sq.mm PVC insulated sheathed FRLS copper conductor armoured cable.
Building Management System
Server class Workstation machine: INTEL CORE I5 processor with minimum 4 GB DDR RAM, minimum 500 GB SATA Hard Disk, DVD R/W, Lan Card 10/100/1000 base-T, Multi Monitor Support, Optical Mouse, 104 Keys Keyboard, latest windows OS compatible with BMS Software, high quality media graphics card, MS Office with Antivirus software.
19" colour, Flat Screen Type Professional HD monitor for above client workstation
A 4 size Laserjet Printer suitable for the application, with driver software.
Proposed Integrated Software for BMS & FAS (Graphic Software)
Building management software shall include alarm handling, scheduling, trending, reporting engine, database system, system activity log, historical data management, real time vector graphics, system backup and restore, HTML based documentation and help. Graphical user interface based software for iBMS monitoring with 200 BMS points(including Soft +Hard)
Third Party Integration
Third Party Integration: The Protocol Integrator/ Convertor shall be Capable to Integrate Open protocol systems on BACnet/ Modbus/ LONWORKS/ M-Bus/ J-Bus Protocol Made available on IP, or on serial RS 485/ 232 interface. ( Separate Integrator for each system)
Integrator for PAC for Server room (20Soft Points considered for each PAC Unit) on MODBUS RTU PROTOCOL.
Integrator for UPS (20Soft Points considered for each UPS) on MODBUS RTU PROTOCOL.
Integrator for DG (20Soft Points considered for each DG) on MODBUS RTU PROTOCOL.
Integrator for PDU (20Soft Points considered for each PDU) on MODBUS RTU PROTOCOL.
Integrator for WLD (20Soft Points considered for each WLD) on MODBUS RTU PROTOCOL.
FAS soft integration (100 Soft Points)
Direct Digital Controllers: BACnet/IP
Networkable 32 Bit DDC Controllers with I/O points as per enclosed IO List, inbuilt real time clock, Battery backup. The controllers shall be capable of standalone operation with real time clock and historical database. The DDC's shall be capable of peer to peer communication without help of system interface controller or PC. The DDCs shall be with suitable IP 54 enclosure complete with all wiring and accessories. BTL Approved.
DDC for Server room Temperature & RH, WLD, Gas release status.
Field Sensors
Temperature and RH sensor for server room
Diesel level switch
H2 sensor for Battery room
Cable and Conduit
2 Core x 1 sq mm FRLS Armoured Cable for control cabling
4 Core x 1 sq mm FRLS Armoured Cable for control cabling
Communication cable: FRLS Armoured CAT6 Cable
LED TV
High-Definition Smart LED TV 85" (for BMS ROOM)
PACKAGE - SAFETY SECURITY SURVEILLANCE AND MONITORING
LOCATION: SDC 2
Fire Alarm System
Fire alarm Control panel Comprised of the following system components: ƒ Operating units, Periphery boards, Power supplies, System enclosures, 170Watt power supply. He panel must support or comply to: -one (1) to four (4) ‘Class B’; one (1) to two (2) ‘Class A’ -Includes one (1) ‘Class A’, or two (2) ‘Class B’ notification appliance circuits (NACs) - Resettable and non-resettable 24VDC, [nominal] auxiliary power - Digital alarm communication transmitter (DACT)
Intelligent Addressable Type Manual Call Point: Intelligent Manual Fire Alarm Box is constructed of durable, moulded and polycarbonate material that is matte finished in red with raised white lettering Single-action, - Pull-down lever shall remain down, until manually reset - connectivity shall be Polarity insensitive via SureWireTM technology - device programming vide Electronic programming with self-test facility
All control Panels, Modules and detectors related to related to Safety Security and Surveillance Monitoring should have UL listed certification
Short circuit Isolator Base: Requires no programming Does not occupy a device address Local light-emitting diode (LED) indicator
Response Indicator for below false floor detector
Intelligent Addressable Relay control module for Hooter+ Control module for 3rd Party equipment (Precision AC unit) Interfacing and supervising normally open (N.O) or normally closed (N.C) contacts, Integral single-pole, double-throw (SPDT) relay (up to 4 amps), Multi-color light-emitting diode (LED) indicates system status: § GREEN / AMBER / RED,
All control Panels, Modules and detectors related to related to Safety Security and Surveillance Monitoring should have UL listed certification
Intelligent Addressable Monitor module for VESDA: Interfacing and supervising normally open (N.O) or normally closed (N.C) contacts, Integral single-pole, double-throw (SPDT) relay (up to 4 amps), Multi-color light-emitting diode (LED) indicates system status:
All control Panels, Modules and detectors related to related to Safety Security and Surveillance Monitoring should have UL listed certification
2 core x 1.5 sq.mm Armoured FRLS cable
Supply & Installation of CO2 Type Extinguishers - 2 Kg
Supply & Installation of GLOW SIGNAGE
Public Address System
6 Watt Ceiling speaker: The loudspeaker can be used for reproducing music as well as speech. The speaker assembly consists of a single-piece, dual cone loudspeaker and frame, with a 100 matching transformer mounted on the back. A circular metal grille is an integrated part of the front. 1.5W,3W, 6 Watt various tapping
240 Watt Amplifier
2 core 1 sq.mm Armoured
CCTV SYSTEM
IP based Dome camera with fixed lens,2 Megapixel Full HD Network IR Dome Camera
IP based ,2Megapixel Full HD 23x Network IR PTZ Dome Camera, IP66, IK10, IR LED, Intelligent video analytics.
NVR: 16 CH Network Video Recorder, with 6month storage backup.
21" LED Monitor
24 Port 10/100/1000 Mbps L2 Managed switch
CAT6 Armoured Cable
Video data storage for 6 months at min 12FPS
ACCESS CONTROL SYSTEM
Intelligent 8 Reader Door Master Access Controller, via a 10/100Mb Ethernet connection, Support for 500,000 cardholders
- Operating voltage 8 to 40 VDC, 8 to 30 VAC
- Operating temperature 0 to +50 °C (32122° F)
- Card capacity 40,000
Dual Reader Interface (DRI): Interface module for up to two card readers, Supports all popular reader technologies, Auxiliary 12VDC power source (min. voltage input 18VDC), Lock / door strike output (relay driven), Request-to-exit input, Door contact input, Communications status LED, Activity status LED, Power status LED
Eight Reader Interface (ERI): Interface module for up to eight card readers, Supports all popular reader technologies, Auxiliary 12VDC power source (min. voltage input 18VDC), Lock / door strike output (relay driven), Request-to-exit input, Door contact input, Communications status LED, Activity status LED, Power status LED
Power Supply Unit with battery back-up for Controller and Door Interface modules
Biometric Reader for Server room
iCLASS SE R10 Reader (Entry/Exit): iCLASS Seos: 2.4" (6 cm),indoor/Outdoor IP55; IP65 if installed with optional gasket , Wiegand, Clock-and-Data, Open Supervised Device Protocol (OSPD) via RS485, UL94 Polycarbonate
Electromagnetic lock - 600 lbs with ZL / UL bracket, as required - Single Leaf
► Voltage Input: 12 VDC / 24 VDC
► Current Draw: 12V / 500mA ; 24V / 250mA (±5%)
► Holding Force: Up to 600 lbs (272 kg)
Electromagnetic lock - 600 lbs with ZL / UL bracket, as required - Double Leaf
Resettable Emergency Release Switch
Magnetic Contact
Access Control Software & time attendance:
l Anti-pass back
3 wrong PIN mode
Time scheduling
Manual system override capabilities
Enrolment reader support
Multi-user, multi-tasking environment
PC for Access control software
6 core x 1 Sq.mm - Armoured
4 core x 1 Sq.mm - Armoured
2 core x 1 Sq.mm - Armoured
Cat6e cable - Armoured
Exit Switch
Access Cards
Novec 1230 System - Server room
SITC of CCOE Approved Seamless NOVEC1230 Cylinder and Valve Assembly, 120 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised to 42 bar.
Master Completer Kit complete with Solenoid, Pneumatic actuators, Pressure Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses and connectors. For Multiple cylinder system -VDS/UL approved
Slave Completer Kit complete with Pneumatic actuators, Pressure Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses, manual actuator and connectors. -VDS/UL approved
SITC of NOVEC1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
Manifold to cater Multiple Cylinder Bank
MS Powder coated 2"x2" hollow box frame Cylinder(s) support assembly with manifold support system duly fastened to the slab floor & wall / Ceiling complete with cylinder brackets / U clamps etc. Need to distribute the floor load
SITC of NOVEC Piping & Manifold as required, Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & Support the Manifold and Piping properly.
Complete with Pressure testing for piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen prior to handover.
Detection Systems
Supply installation Testing & commissioning of two zone Gas Release Panel facility to connect Manual Abort/Release switches. The Panel shall provide Potential free contacts for First knock, second knock, Trouble / Fault Status.
The Panel shall be Complete with Red Colour Housing, Power supply unit, Battery charger & batteries
Manual Release Switch
Abort Switch
NOVEC1230 System for UPS Room
SITC of CCOE Approved Seamless NOVEC1230 Cylinder and Valve Assembly, 100 Litres. capacity, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised to 42 bar.
Master Completer Kit complete with Solenoid, Pneumatic actuators, Pressure
Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses and connectors. For Multiple cylinder system -VDS/UL approved
Slave Completer Kit complete with Pneumatic actuators, Pressure Gauge, Low
Pressure supervisory switch, Discharge hoses, Flexible actuation hoses, manual actuator and connectors. -VDS/UL approved
SITC of -NOVEC1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
Manifold to cater Multiple Cylinder Bank
MS Powder coated 2"x2" hollow box frame Cylinder(s) support assembly with manifold support system duly fastened to the slab floor & wall / Ceiling complete with cylinder brackets / U clamps etc. Need to distribute the floor load
SITC of NOVEC Piping & Manifold as required, Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & Support the Manifold and Piping properly.
Complete with Pressure testing for piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen prior to handover.
Rodent VHFO system
VHFO master controller can drive up to 20 transducers.
TRANSDUCERS
Wire Bundle
PVC Conduit 20mm
Water leak detection
Conventional 6 Zone Water Leak detection panel with Modbus RS485
Water leak detection cable sensor
Electronic Hooter
2 core x 1.5 sq.mm Armoured cable
Aspiration Detector(Early warning Detection)
Single channel Aspirating Detector, coverage 500 SQM (2*25 M Pipe length maximum) for server room only
Single channel Aspirating Detector, coverage 800 SQM (2*60 M Pipe length Maximum)
Power Supply with Battery backup Unit
Air termination Nozzles with Capillary set
Aspiration 25mm OD CPVC Sampling Pipes with accessories
Electronic Hooter with mounting arrangement
2C x 1.5 sq.mm PVC insulated sheathed FRLS copper conductor armoured cable.
Building Management System
Server class Workstation machine: INTEL CORE I5 processor with minimum 4 GB DDR RAM, minimum 500 GB SATA Hard Disk, DVD R/W, Lan Card 10/100/1000 base-T, Multi Monitor Support, Optical Mouse, 104 Keys Keyboard, latest windows OS compatible with BMS Software, high quality media graphics card, MS Office with Antivirus software.
19" colour, Flat Screen Type Professional HD monitor for above client workstation
A 4 size LaserJet Printer suitable for the application, with driver software.
Proposed Integrated Software for BMS & FAS ( Graphic Software)
Building management software shall include alarm handling, scheduling, trending, reporting engine, database system, system activity log, historical data management, real time vector graphics, system backup and restore, HTML based documentation and help. Graphical user interface based software for iBMS monitoring with 200 BMS points(including Soft +Hard)
Third Party Integration
Third Party Integration: The Protocol Integrator/ Convertor shall be Capable to Integrate Open protocol systems on BACnet /Modbus/LONWORKS/M-Bus/J-Bus Protocol Made available on IP, or on serial RS 485 / 232 interface. ( Separate Integrator for each system)
Integrator for PAC for Server room (20Soft Points considered for each PAC Unit) on MODBUS RTU PROTOCOL.
Integrator for UPS (20Soft Points considered for each UPS) on MODBUS RTU PROTOCOL.
Integrator for DG (20Soft Points considered for each DG) on MODBUS RTU PROTOCOL.
Integrator for PDU (20Soft Points considered for each PDU) on MODBUS RTU PROTOCOL.
Integrator for WLD (20Soft Points considered for each WLD) on MODBUS RTU PROTOCOL.
FAS soft integration (100 Soft Points)
LED TV
High Definition Smart LED TV 85" (for Conference Room,BMS ROOM,DC Operation Room)
PACKAGE - SAFETY SECURITY SURVEILLANCE AND MONITORING
LOCATION - SDC 3 (NEW SETUP)
Fire Alarm System
Fire alarm Control panel Comprised of the following system components: Operating units, Periphery boards, Power supplies, System enclosures, 170Watt power supply. The panel must support or comply to: -one (1) to four (4) ‘Class B’; one (1) to two (2) ‘Class A’ -Includes one (1) ‘Class A’, or two (2) ‘Class B’ notification appliance circuits (NACs) - Resettable and non-resettable 24VDC, [nominal] auxiliary power - Digital alarm communication transmitter (DACT)
Intelligent Addressable Type Manual Call Point: Intelligent Manual Fire Alarm Box is constructed of durable, moulded and polycarbonate material that is matte finished in red with raised white lettering Single-action, - Pull-down lever shall remain down, until manually reset - connectivity shall be Polarity insensitive via SureWireTM technology - device programming vide Electronic programming with self-test facility
All control Panels, Modules and detectors related to related to Safety Security and Surveillance Monitoring should have UL listed certification
Short circuit Isolator Base: Requires no programming Does not occupy a device address Local light-emitting diode (LED) indicator
Response Indicator for below false floor detector
Intelligent Addressable Relay control module for Hooter+ Control module for 3rd Party equipment (Precision AC unit) Interfacing and supervising normally open (N.O) or normally closed (N.C) contacts, Integral single-pole, double-throw (SPDT) relay (up to 4 amps), Multi-color light-emitting diode (LED) indicates system status: § GREEN / AMBER / RED,
All control Panels, Modules and detectors related to related to Safety Security and Surveillance Monitoring should have UL listed certification
Intelligent Addressable Monitor module for VESDA: Interfacing and supervising normally open (N.O) or normally closed (N.C) contacts, Integral single-pole, double-throw (SPDT) relay (up to 4 amps), Multi-color light-emitting diode (LED) indicates system status:
All control Panels, Modules and detectors related to related to Safety Security and Surveillance Monitoring should have UL listed certification
2 core x 1.5 sq.mm Armoured FRLS cable
Supply & Installation of CO2 Type Extinguishers - 2 Kg
Supply & Installation of GLOW SIGNAGE
Public Address System
6 Watt Ceiling speaker: The loudspeaker can be used for reproducing music as well as speech. The speaker assembly consists of a single-piece, dual cone loudspeaker and frame, with a 100 matching transformer mounted on the back. A circular metal grille is an integrated part of the front. 1.5W,3W, 6 Watt various tapping
9 Watt Ceiling speaker: Rated voltage 100V,. 1.5W,3W, 6 Watt various tapping
Mixer Amplifier with Microphone
240 Watt Amplifier
DVD Player
2 core 1 sq.mm Armoured
RACK 12U
CCTV SYSTEM
IP based Dome camera with fixed lens,2 Megapixel Full HD Network IR Dome Camera
IP based Dome camera with Varifocal lens, Max. 2M (1920 x 1080) resolution • 2.8 ~ 12mm (4.3x) varifocal lens, IR viewable length 30m, IP66, IK10, Motion detection, Tampering, Defocus detection
IP based ,2Megapixel Full HD 23x Network IR PTZ Dome Camera, IP66, IK10, IR LED, Intelligent video analytics.
NVR: 24 CH Network Video Recorder, with 6month storage backup.
21" LED Monitor
24 Port 10/100/1000 Mbps L2 Managed switch
CAT6 Armoured Cable
Video data storage for 6 months at min 12FPS
ACCESS CONTROL SYSTEM
Intelligent 8 Reader Door Master Access Controller, via a 10/100Mb Ethernet connection, Support for 500,000 cardholders
- Operating voltage 8 to 40 VDC, 8 to 30 VAC
- Operating temperature 0 to +50 °C (32122° F)
- Card capacity 40,000
Dual Reader Interface (DRI): Interface module for up to two card readers, Supports all popular reader technologies, Auxiliary 12VDC power source (min. voltage input 18VDC), Lock / door strike output (relay driven), Request-to-exit input ,Door contact input ,Communications status LED ,Activity status LED, Power status LED
Eight Reader Interface (ERI): Interface module for up to eight card readers, Supports all popular reader technologies, Auxiliary 12VDC power source (min. voltage input 18VDC), Lock / door strike output (relay driven) ,Request-to-exit input ,Door contact input ,Communications status LED ,Activity status LED, Power status LED
Power Supply Unit with battery back-up for Controller and Door Interface modules
Biometric Reader for Server room
iCLASS SE R10 Reader (Entry/Exit): iCLASS Seos: 2.4" (6 cm), Indoor/Outdoor IP55; IP65 if installed with optional gasket, Wiegand, Clock-and-Data, Open Supervised Device Protocol (OSPD) via RS485, UL94 Polycarbonate
Electromagnetic lock - 600 lbs with ZL / UL bracket, as required - Single Leaf
► Voltage Input: 12 VDC / 24 VDC
► Current Draw: 12V / 500mA; 24V / 250mA (±5%)
► Holding Force: Up to 600 lbs (272 kg)
Electromagnetic lock - 600 lbs with ZL / UL bracket, as required - Double Leaf
Resettable Emergency Release Switch
Magnetic Contact
Access Control Software & time attendance:
l Anti-passback
3 wrong PIN mode
Time scheduling
Manual system override capabilities
Enrolment reader support
Multi-user, multi-tasking environment
PC for Access control software
6 core x 1 Sq.mm - Armoured
4 core x 1 Sq.mm - Armoured
2 core x 1 Sq.mm - Armoured
Cat6e cable - Armoured
Exit Switch
Access Cards
Novec 1230 System - Server room
SITC of CCOE Approved Seamless NOVEC1230 Cylinder and Valve Assembly, 120 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised to 42 bar.
Master Completer Kit complete with Solenoid, Pneumatic actuators, Pressure
Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses and connectors. For Multiple cylinder system -VDS/UL approved
Slave Completer Kit complete with Pneumatic actuators, Pressure Gauge, Low
pressure supervisory switch, Discharge hoses, Flexible actuation hoses, manual actuator and connectors. -VDS/UL approved
SITC of NOVEC1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
Manifold to cater Multiple Cylinder Bank
MS Powder coated 2"x2" hollow box frame Cylinder(s) support assembly with manifold support system duly fastened to the slab floor & wall / Ceiling complete with cylinder brackets / U clamps etc. Need to distribute the floor load
SITC of NOVEC Piping & Manifold as required, Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & Support the Manifold and Piping properly.
Complete with Pressure testing for piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen prior to handover.
Detection Systems
Supply installation Testing & commissioning of Single zone Gas Release Panel facility to connect Manual Abort/Release switches. The Panel shall provide Potential free contacts for First knock, second knock, Trouble / Fault Status.
The Panel shall be Complete with Red Colour Housing, Power supply unit, Battery charger & batteries
Manual Release Switch
Abort Switch
NOVEC1230 System for UPS Room
SITC of CCOE Approved Seamless NOVEC1230 Cylinder and Valve Assembly, 100 Ltrs. capacity, OEM Factory filled with Novec 1230 Suppression Liquid, pressurised to 42 bar.
Master Completer Kit complete with Solenoid, Pneumatic actuators, Pressure
Gauge, Low pressure supervisory switch, Discharge hoses, Flexible actuation hoses and connectors. For Multiple cylinder system -VDS/UL approved
Slave Completer Kit complete with Pneumatic actuators, Pressure Gauge, Low
pressure supervisory switch, Discharge hoses, Flexible actuation hoses, manual actuator and connectors. -VDS/UL approved
SITC of NOVEC1230 Fire Protection Fluid, OEM Factory Filled per Kgs.
Manifold to cater Multiple Cylinder Bank
MS Powder coated 2"x2" hollow box frame Cylinder(s) support assembly with manifold support system duly fastened to the slab floor & wall / Ceiling complete with cylinder brackets / U clamps etc. Need to distribute the floor load
SITC of NOVEC Piping & Manifold as required, Sch 40; ASTM A106 Gr B, as per flow calculations for the specific hazard volume and stand to hold, position & Support the Manifold and Piping properly.
Complete with Pressure testing for piping with nitrogen as per NFPA 2001 & Flushing with Nitrogen prior to handover.
Detection Systems
Supply installation Testing & commissioning of Single zone Gas Release Panel facility to connect Manual Abort/ Release switches. The Panel shall provide Potential free contacts for First knock, second knock, Trouble/ Fault Status.
The Panel shall be Complete with Red Colour Housing, Power supply unit, Battery charger & batteries
Manual Release Switch
Abort Switch
Rodent VHFO system
VHFO master controller can drive up to 20 transducers.
TRANSDUCERS
Wire Bundle
PVC Conduit 20mm
Water leak detection
Conventional 6 Zone Water Leak detection panel with Modbus RS485
Water leak detection cable sensor
Electronic Hooter
2 core x 1.5 sq.mm Armoured cable
Aspiration Detector (Early warning Detection)
Single channel Aspirating Detector, coverage 500 SQM (2*25 M Pipe length maximum) for server room only
Single channel Aspirating Detector, coverage 800 SQM (2*60 M Pipe length Maximum)
Power Supply with Battery backup Unit
Air termination Nozzles with Capillary set
Aspiration 25mm OD CPVC Sampling Pipes with accessories
Electronic Hooter with mounting arrangement
2C x 1.5 sq.mm PVC insulated sheathed FRLS copper conductor armoured cable.
Building Management System
Server class Workstation machine: INTEL CORE I5 processor with minimum 4 GB DDR RAM, minimum 500 GB SATA Hard Disk, DVD R/W, Lan Card 10/100/1000 base-T, Multi Monitor Support, Optical Mouse, 104 Keys Keyboard, latest windows OS compatible with BMS Software, high quality media graphics card, MS Office with Antivirus software.
19" colour, Flat Screen Type Professional HD monitor for above client workstation
A 4 size Laserjet Printer suitable for the application, with driver software.
Proposed Integrated Software for BMS & FAS( Graphic Software)
Building management software shall include alarm handling, scheduling, trending, reporting engine, database system, system activity log, historical data management, real time vector graphics, system backup and restore, HTML based documentation and help. Graphical user interface based software for iBMS monitoring with 200 BMS points(including Soft +Hard)
Third Party Integration
Third Party Integration: The Protocol Integrator/ Convertor shall be Capable to Integrate Open protocol systems on BACnet /Modbus/LONWORKS/M-Bus/J-Bus Protocol Made available on IP, or on serial RS 485 / 232 interface. (Separate Integrator for each system)
Integrator for PAC for Server room (20Soft Points considered for each PAC Unit) on MODBUS RTU PROTOCOL.
Integrator for UPS (20Soft Points considered for each UPS) on MODBUS RTU PROTOCOL.
Integrator for DG (20Soft Points considered for each DG) on MODBUS RTU PROTOCOL.
Integrator for PDU (20Soft Points considered for each PDU) on MODBUS RTU PROTOCOL.
Integrator for WLD (20Soft Points considered for each WLD) on MODBUS RTU PROTOCOL.
FAS soft integration (100 Soft Points)
PACKAGE - DATACENTER INFRASTRCUTURE MANAGEMENT
LOCATION: SDC 1,2 & 3
Supply, Installation, Testing and Commissioning of DCIM Solution, DCIM application should be 100% web based without requiring any client to be deployed to view and explore application functionality. The Solution should integrate with all the three Data Centres for a unified view (This includes the two-existing Data Centre along with KSDC 3.0.). Any instrumentation or controller required has to be considered by the bidder.
Application should provide overview of Data Centre operations through inventory management and location-based drill-down. Managing Layer - Inventory / Asset Management / Energy Cost Management.
A location-based drill-down view provides a structured overview of Data Centre locations, from a global to local view down to single assets.
This software shall be seamlessly integrated to the Controller through industry standard protocols such as MODBUS IP, SNMP & BACnet IP.
Vendor to consider rack count across all three Data Centre and other supporting infrastructure as per IO list and system architecture. Rack Level power consumption to be seen in single Window/web page.
Supply, Installation, Testing and Commissioning of Capacity planning predicts the optimal location for physical infrastructure and rack-based IT equipment based on the availability and requirements of physical infrastructure capacity.
Visualization of the Data Centre and Racks. should visualize the heat maps in a rendering of the floor view & should allow to view actual rack heat load and to help balancing and optimizing the system and generate reports - with this feature DC operation team will be able to identify potential hot pockets, airflow problem on floor, also this must help operation team to optimize the cooling inside /outside of room/rack thus bringing room & rack level cooling efficiency
Supply, Installation, Testing and Commissioning of Standard Dashboard and Reporting, Audit Trail, Capacity, History, Contiguous Free U-Space, Customer Inventory Report, Executive Power and Space Rack U.
Customize Dashboard and Reporting as per Customer Expectation Vendor to consider rack counts across all three Data Centre and other supporting infrastructure as per IO list and system architecture
Supply, Installation, Testing and Commissioning of necessary instrumentation controller required for monitoring layer should be supplied, configured and maintain.
i) Supply, Installation, Testing and Commissioning of necessary hardware with required Operating system must be supplied.
ii) System architecture design should work in 100% HA mode (High Availability mode) with Zero Data loss. i,e if One Primary DCIM Application fails for any reason then Secondary(HA) instance should take over as primary and work as production.
PACKAGE - SERVER AND NETWORK RACK
SERVER RACK
SITC of 42U Racks (600 mm x 1200 mm x 2000mm. The Rack should be able to with stand a minimum Static load of 1200 Kgs and Rolling load of 1022 Kgs. The unit should have a minimum of IP 20 rating for protection against touch, ingress of foreign bodies, and ingress of water. Rack front door should have minimum 63 % of open perforation for efficient air flow. ROHS Compliant. UL Approved.
Horizontal Cable Manager (1Ux4' deep single sided with cover) made up of steel & PVC material as per site requirement.
Vertical cable manager (600MM, 42U height with Cover) made up of steel & PVC material as per site requirement.
Blanking Panels (1U,19') black plastic tool less construction in each rack -20 nos
NETWORK RACK
SITC of 42U Racks (800 mm x 1200 mm) The Rack should be able to with stand a minimum Static load of 1200 Kgs and Rolling load of 1022 Kgs. The unit should have a minimum of IP 20 rating for protection against touch, ingress of foreign bodies, and ingress of water. Rack front door should have minimum 63 % of open Perforation for efficient air flow. ROHS Compliant.
Horizontal Cable Manager (1Ux4' deep single sided with cover) made up of steel & PVC material as per site requirement.
Vertical cable manager (800MM, 42U height with cover) made up of steel & PVC material as per site requirement.
Blanking Panels (1U,19') black plastic tool less construction in each rack -20 nos
PACKAGE - PASSIVE NETWORKING
From NR to server rack
1U modular cassette panel, accepts min 4 modular cassettes with Fiber Cable Management
OM4 , Distribution cassette, MPO/ F to LC , 24F
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 8m
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 10m
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 15m
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 30m
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 35m
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 40m
OM4 , Distribution cassette, MPO/ F to LC , 24F
4U modular cassette panel, accepts min 12 modular cassettes with Fiber Cable Management
OM4, LC to LC , 2.0 mm Duplex Fiber Patch Cord, Low Smoke Zero Halogen- 3m
OM4, LC to LC , 2.0 mm Duplex Fiber Patch Cord, Low Smoke Zero Halogen- 3m
Blind Plates
Network Rack to MUX / ISP Rack
1U modular cassette panel, accepts min 4 modular cassettes with Fiber Cable Management
OM4 MPO/M-MPO/M, Preconnect fiber trunk,Type-B, 12-Fiber, Low Smoke Zero Halogen (LSZH) , 20m
OM4 , Distribution cassette, MPO/ F to LC , 24F
OM4 , Distribution cassette, MPO/ F to LC , 24F
OM4, LC to LC , 2.0 mm Duplex Fiber Patch Cord, Low Smoke Zero Halogen- 3m
From NR to server racks: Copper
Cat6A indoor U/FTP cable, LSZH, 305m/reel
Cat6a UTP Modular Patch Panel, 24-port (with keystones)
Cat6a RJ45-RJ45 UTP 4-pair Patch cord LSZH, Grey, 1m,Grey
Cat6a RJ45-RJ45 UTP 4-pair Patch cord LSZH, Grey, 2m,Grey
Cat6a RJ45-RJ45 UTP 4-pair Patch cord LSZH, Grey, 3m,Grey
DC Support Area LAN - 60 Nos
1-port RJ45 Plane Faceplate, White
2-port RJ45 Plane Faceplate, White
4-port RJ45 Plane Faceplate, White
Cat6a UTP Standard Keystone, Ivory, 180°
Cat6a UTP Modular Patch Panel, 24-port (with keystones)
Cat6a RJ45-RJ45 UTP 4-pair Patch cord LSZH, Grey, 3m,Grey
Cat6a RJ45-RJ45 UTP 4-pair Patch cord LSZH, Grey, 2m,Grey
Cat6A indoor U/FTP cable, LSZH, 305m/reel
Back Box ,wall / surface mounted for the faceplate
Fiber Runner
Raceway, 240 Straight section, 2m, Yellow
Raceway, 240 Straight section cover, 2m, Yellow
240mm Connector Kits, Type B, Yellow
240mm Horizontal 90° Elbow, Yellow
240mm Horizontal 90° Elbow Cover, Yellow
240mm Horizontal Tee, Yellow
240mm Horizontal Tee Cover, Yellow
240mm Horizontal Cross, Yellow
240mm Horizontal Cross Cover, Yellow
240mm End Cap, Yellow
90mm Moveable Cable Exit Kits, Yellow, PVC
90mm Moveable Cable Exit Kits Cover, Yellow, PVC
Pipe fixer, 50, Yellow, PVC
Φ50Corrugated pipe, Yellow, PVC
Accessories to complete the installation
Hinged Cover Upper Part,50×18.5×11.5
Hinged Cover Lower Part,50×36×11.5
Plastic Round Head Bolt,M5×15
Plastic Square Nut,M5
Plastic T Shape Head Bolt,M6×15
Plastic Rotary Knob Nut,M6
Dual Hole Bar (240 straight section),Electroplated Zinc Powder Coated
M10 Lifting Screw
Light, 30 mm wide, Φ 12.5 hole
M10 Hexagon flange nut
Expansion bolt
PERIODIC HEALTH AUDIT
Provision of Infrastructure Audit for main/ UPS Power, Equipment/ Comfort Cooling, safety security and monitoring system, network cabling, racks, DCIM System, Video wall, Air Quality and controller including all installation under this schedule once in every 6 months with required tools, Software, Protocols and expert technical staff of this field from recognised third party duly approved by Engineer-in-charge as per the specification etc. (Audit to be carried out once in every 6 months)
PACKAGE - OPERATION AND MAINTENANCE
LOCATION: SDC 3
Site engineers 2 per shift plus 1 Reliever
Site Supervisor for Day duty
Cost for the extra Items required for Project Execution (Details to be uploaded in the commercial bid letter)
Netcon Technologies India Pvt Ltd
Vertiv Energy Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid