| 1 | L1₹2.1 CrAccepted-AOC 36 E COCHIN FIRE TECH HOUSE VATTEKAT EAST ROAD KALOOR KADAVANTHARA ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | ₹2.1 Cr | L1 | Accepted-AOC Committee decision because of L1 bidder |
| 2 | L2₹2.3 Cr+₹14.1 L (6.62%)Rejected-Finance DOOR NO 32 939C 1ST FLOOR CITY SCAPE BUILDING CHANGAMPUZHA NAGAR P O SOUTH KALAMASSERY ERNAKULAM KERALA 682033 | ERNAKULAM | KERALA | 682033 | ₹2.3 Cr+₹14.1 L (6.62%) | L2 | Rejected-Finance Not the L1 bidder |
| 3 | Rejected-Technical | - | - | Rejected-Technical As per PQcommittee Decision |
Tender Value
₹2.4 Cr
EMD Value
₹1 L
Closing Date
18 Sept 2021, 5:00 pmClosed
Chief Engineer Gen and PED
Chief Engineer Gen and PED Vydyuthibhavan Pattom Thiruvananthapuram 695004
Supply,Installation,testing and commissioning of Fire Fighting and fire protection systems at Thottiyar HEP
2021_KSEB_428274_1
CEPED/06/2021-22 dated 01/07/2021
Open Tender
Electrical Works
Item Rate
90 days
Thottiyar HEP, Idukki Dist Kerala
Please refer Tender documents.
14 documents required · 14 mandatory
₹8,850
₹1 L
7 Nov 2022
1 Jul 2021
27 Sept 2021
1 Jul 2021
18 Sept 2021
7 Jul 2021
1 Jul 2021 - 4 Jul 2021
Amount
Schedule A1 - Supply
Supply of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN Make : Minimax/Gilpro /Warrior/Anzul /Equivalent
Supply of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring. Make: Minimax / Ravel /Gilpro/Warrior /Equivalent
Supply of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Probe type Heat detector 80 - 145 Deg Make : Tyco / s s sun controls / Agni conrols /Equivalent
Supply of Addressable type Abort Switch with suitable input module if required. Make Hochiki/Ravel/System sensor/Equvalant . Make: Shield / Hochiki / Ravel/Equivalent
Supply of Addressable type Emergency Release Switch (Electrical) with suitable input module if required. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Addressable type Hooter for First stage Alert. with suitable Sounder module power supply etc as required. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Addressable type Hooter cum Strobe for second stage Alert. with suitable Sounder module, power supply etc as required. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Addressable type Strobe for Released Alert. with suitable Sounder module, power supply etc as required. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Addressable type input / Monitor module with required accessories as required to monitor in the event if low pressure in a purticular module. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Addressable type Control module with required accessories as required to control /operate any 3rd party devices in the event fire if required. Make: Shield / Hochiki / Ravel/Equivalent
Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required. Make: Polycab/Hawells/Finolex/Equivalent
IR / UV TRIPLE SENSOR FLAME DETECTOR FOR A CABLE FLOORSupply of fladet series.. Triple Sensor - IR / UV Flame Detector with FM, ATEX & PESO approved Ex. Proof Enclosure. Flickering LED Indication for normal operation. 24 V DC, 4 wire system
Supply of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring. Make: Minimax / Ravel / Warrior/Equivalent
Supply of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Addressable type duel input / Monitor module with required accessories as required to monitor in the event if low pressure in a purticular module. Make: Shield / Hochiki / Ravel/Equivalent
Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required. Make: Polycab/Hawells/Finolex/Equivalent
SUPPLY OF MODULAR CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR BATTERY ROOMSupply of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN Make : Minimax/Gilpro /Warrior/Anzul/Equivalent
Sypply of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring. Make: Minimax / Ravel / Warrior/Gilpro/Equivalent
Supply of Battery 12V Dc x 12 Ah Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Conventional 2 Zone Fire Detection Extinguishant control panel. Suitable for cross zonning and reliable exhingushant system with battery charger. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Conventional Smoke detector/ heat detector with base. Make: Shield / Hochiki / Ravel / System sensor/Equivalent
Supply of Abort Switch. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Emergency Release Switch (Electrical). Make: Shield / Hochiki / Ravel
Supply of Hooter for First stage Alert. Make: Shield / Hochiki / Ravel/Equivalent
Supply of Hooter cum Strobe for second stage Alert. Make: Shield / Hochiki / Ravel
Supply of Strobe for Released stage Alert. Make: Shield / Hochiki / Ravel/Equivalent
Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required Make: Polycab / Hawells / Finolex/Equivalent
SUPPLY OF MODULAR CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR CONTROL ROOMSupply of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN Make : Minimax/Gilpro /Warrior/Anzul /Equivalent
Supply of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring. Make: Minimax / Ravel / Warrior/Anzul/Equivalent
Supply of Battery 12V Dc x 12 Ah Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Conventional 2 Zone Fire Detection Extinguishant control panel. Suitable for cross zonning and reliable exhingushant system with battery charger. Make: Hochiki / Kentec / Ravel/Equivalent
Supply of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Conventional Smoke detector/ heat detector with base. Make: Hochiki / Ravel / System sensor/Equivalent
Supply of Abort Switch. Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Emergency Release Switch (Electrical). Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Hooter for First stage Alert. Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Hooter cum Strobe for second stage Alert. Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Strobe for Released stage Alert. Make: Hochiki / Ravel / Kentec/Equivalent
Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
SUPPLY OF MODULAR CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR L T SWITCH GEAR ROOM Supply of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN Make : Minimax/Gilpro /Warrior/Anzul /Equivalent
Supply of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring. Make: Minimax / Ravel / Warrior/Anzul/Equivalent
Supply of Battery 12V Dc x 12 Ah Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Conventional 2 Zone Fire Detection Extinguishant control panel. Suitable for cross zonning and reliable exhingushant system with battery charger. Make: Hochiki / Kentec / Ravel/Equivalent
Supply of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Conventional Smoke detector/ heat detector with base. Make: Hochiki / Ravel / System sensor/Equivalent
Supply of Abort Switch. Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Emergency Release Switch (Electrical). Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Hooter for First stage Alert. Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Hooter cum Strobe for second stage Alert. Make: Hochiki / Ravel / Kentec/Equivalent
Supply of Strobe for Released stage Alert. Make: Hochiki / Ravel / Kentec/Equivalent
Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required/Equivalent
SUPPLY OF CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR LT PANEL-1 AND LT PANEL-2(4 KG type) Supply of the Fire Spot Panel Protection System, 4 kg type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. Portable Type. The tank is constructed of Mild Steel, grade CR1 of IS 513. Dip tube Container in 4 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar, Discharging % -minimum 95% of initial charge. The area coverage should be 9.03 cu.m ,The cylinder have Inbuild pressure gauge adaptor and Pressure Switch ,The cylinder included Polyimide Tube . The adaptor assembly includes a Stainless Steel adaptor, The Portable cylinder should have UL/EN and the entire system should have National Test House certification (NTH). Make: Warrior/ Gilpro/Tyco/ Minimax /Equivalent
Supply of Polymer tube for Fire Spot panel protection system –Designed with multi-layer polymids tube with internal dia meter 4mm and outer dia 6mm with maximum working pressure 20/ burst pressure 100 bar ,Burst Temperature 60digree.The tube should have UL/EN Approval and the entire system should have National Test House certification. Make: Warrior/Gilpro/Tyco/Minimax/Equivalent
Supply of power supply for Monitoring panel. Make : Gunnebo/Shield/Hochiki/Ravel/Zeta/Equivalent
Supply of Battery 12V Dc x 12 Ah Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Hooter cum Strobe for Notification. Make: Shield/Hochiki/Ravel/Kentec/Equivalent
Supply of Addressable type output module with required accessories as required to operatesounder, sounder strobe in the event of fire. Make: Hochiki / Ravel / kidde/tyco/Equivalent
Supply of Addressable type input / Monitor module with required accessories as required to monitor in the event if low pressure in a module. Make: Shield / Hochiki / Ravel/Equivalent
Supplying of 2C x 1.5 sqmm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required Make: Polycab / Hawells / Finolex/Equivalent
SUPPLY OF 2KG TYPE PANEL FIRE PROTECTION - CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR PANEL PROTECTION -2 : LT PANEL - 3, BC - 1, AND BC - 2 Supply of the Fire Spot Panel Protection System, 2 kg type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. Portable Type. The tank is constructed of Mild Steel, grade CR1 of IS 513. Dip tube Container in 4 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar, Discharging % -minimum 95% of initial charge. The area coverage should be 9.03 cu.m ,The cylinder have Inbuild pressure gauge adaptor and Pressure Switch ,The cylinder included Polyimide Tube . The adaptor assembly includes a Stainless Steel adaptor, The Portable cylinder should have UL/EN and the entire system should have National Test House certification (NTH). Make: Warrior/ Gilpro/Tyco/ Minimax /Equivalent
Supply of Polymer tube for Fire Spot panel protection system –Designed with multi-layer polymids tube with internal dia meter 4mm and outer dia 6mm with maximum working pressure 20/ burst pressure 100 bar ,Burst Temperature 60digree.The tube should have UL/EN Approval and the entire system should have National Test House certification. Make: Minimax / Cease Fire / Warrior/Equivalent
Supply of power supply for Monitoring panel. Make : Gunnebo/Shield/Hochiki/Ravel/Zeta/Equivalent/Equivalent
Supply of Battery 12V Dc x 12 Ah Make: Amaron / Star Dust / Powersonic/Equivalent
Supply of Hooter cum Strobe for Notification. Make: Shield/Hochiki/Ravel/Kentec/Equivalent
Supply of Addressable type output module with required accessories as required to operatesounder, sounder strobe in the event of fire. Make: Hochiki / Ravel / kidde/tyco/Equivalent
Supply of Addressable type input / Monitor module with required accessories as required to monitor in the event if low pressure in a module. Make: Shield / Hochiki / Ravel/Equivalent
Supplying of 2C x 1.5 sqmm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required Make: Polycab / Hawells / Finolex/Equivalent
SUPPLY OF FIRST AID FIRE FIGHTING EQUPMENTS FOR MAIN INLET VALVE FLOOR ,GENERATOR FLOOR ,- CLEAN AGENT FIRE SUPPRESSION SYSTEMSupply of Portable type High Pressure Water Mist CAFS Fire Extinguisher of 9 litre capacity, made using carbon composite Pet Liner material as fully charged backpack system with spare air cylinder.
SUPPLY OF FIRST AID FIRE FIGHTING EQUPMENTS FOR ALL FLOOR - CLEAN AGENT FIRE SUPPRESSION SYSTEMSupply of FIRE EXTINGUISHER - MAINTENANCE AND CORROSION FREE WITH MAGNET 2KG ABCPOWDER container shall be 3 layers -one layer HDPE 2nd Layer Kevlar and third layer HDPECasing .Ten Years Corrosion Free Guarantee. (Fire Rating 13A/55B), C Flammable Gas and can beused on live Electrical IS-15683-2018. - HSN Code - 8424 Make: Aska,Orbite ,Warrior , Cease fire /equivalent
Supply of FIRE EXTINGUISHER - MAINTENANCE AND CORROSION FREE WITH MAGNET 6KG ABCPOWDER container shall be 3 layer -one layer HDPE 2nd Layer Kevlar and third layer HDPE Casing,Ten Years Corrosion Free Guarantee. (Fire Rating 34A/183B), C Flammable Gas and can be used onlive Electrical IS-15683-2018 - HSN Code – 8424 Make: Aska,Orbite ,Warrior , Cease fire /Equivalent
SUPPLY OF FIRE PUMPS AND FIRE PUMP PANELS&FIRE PUMP ROOM RELATED EQUIPMENTS-FIRE PUMPS AND FIRE PUMP PANELS ELECTRIC PUMP 100 HP, 2850 LPM @ 88 MTR HEAD - SPRINKLER SYSTEM-Supply of Electrical Driven Fire Main Pump Horizontal Split Case Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal Rated Flow: 2280 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Motor: 100 HP, 2900 RPM, 3Phase, 50 Hz, TEFC. . The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.Make - LUBI/XYLEM/GRUNDFOSS/Equivalent
ELECTRIC PUMP 100 HP, 2850 LPM @ 88 MTR HEAD - HYDRANT SYSTEM-Supply of Electrical Driven Fire Main Pump Horizontal Split Case Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal.Rated Flow: 2280 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN, Motor: 100 HP, 2900 RPM, 3Phase, 50 Hz, TEFC. The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra. Make - LUBI/XYLEM/GRUNDFOSS/Equivalent
JOCKEY PUMP,12.5 HP 180 LPM @ 88 MTR HEAD - SPRINKLER SYSTEM-Supply of Electrical Driven Jockey Fire Pump Endsuction Close Coupled Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal Rated Flow: 180 @ 88 mtr Head,Suction x Discharge: DN 50 x 32 DN,Motor: 12.5 HP, 2900 RPM, 3Phase, 50 Hz, TEFC.The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.Make - UBI/XYLEM/GRUNDFOSS/Equivalent
JOCKEY PUMP 12.5 HP 180 LPM @ 88 MTR HEAD - HYDRANT SYSTEM-Supply of Electrical Driven Jockey Fire Pump Endsuction Close Coupled Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal Rated Flow: 180 @ 88 mtr Head,Suction x Discharge: DN 50 x 32 DN,Motor: 12.5 HP, 2900 RPM, 3Phase, 50 Hz, TEFC.The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra. Make - LUBI/XYLEM/GRUNDFOSS/Equivalent
DIESEL ENGINE PUMP -103 HP, 2850 @ 88 MTR HEAD - STANDBY- Supply of Diesel Engine Driven Fire Main Pump Horizontal Split Case PumpType: LHC , MOC: CI Casing , Bronze Impeller, Shaft - SS AISI 410, Mechnical Seal.Rated Flow: 2850 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Eicher Diesel Engine: 103 HP, 2150 RPM, With Coupling, Coupling Guard, Base Frame. includind [ 12V Battery, 200 ltr Fuel Tank, Anti Vibration Pads. Engine Driven Fire Pump Controller - Make - LUBI/XYLEM/GRUNDFOSS/Equivalent
Supply of Exhaust pipe of dia150mm MS medium grade for Diesel engine with mineral wool insulation with aluminum cladding including necessary supports through shaft up to terrace level
FIRE PUMPS - CABLING/GLANDING-Supplying, of FRLS,PVC outer sheathed, steel armored, aluminum conductor, 1100 Vgrade power cables with glands etc.The cables shall be laid in tray / Hume pipe / in trenches/on walls/ floor etc. as required. For cables laid out door the rate shall include earth excavation providing brick and sand protection, refilling and compacting the earth.The rate shall excludes tray.The minimum size & length of the cables shall be considered as required for the complete system.Make - Polycab/Havells/Finolex/Gloster/KEI/Equivalent. 12 C x 2.5 Sqmm. Copper cable Diesel engines
4 C x 25 Sqmm. Aluminum cable for Jockeypumps
2 C x 2.5 Sqmm.Copper cable for Instrumentation
3.5C x 95 sq.mm Aluminum cable for main pumps
Supply of materials for end Termination of 12 C x 2.5 Sqmm. Copper cable with suitable gland for Diesel engines
Supply of materials for end Termination of 4 C x 25 Sqmm. Aluminum cable with suitable gland for Jockey pumps
Supply of materials for end Termination of 2 C x 2.5 Sqmm.Copper cable with suitable gland for Instrumentation
Supply of materials for end Termination of 3.5C x 95 sq.mm Aluminum cable with suitable gland for main pumps
FIRE PUMPS - CABLE TRAY-Supply of perforated G.I.sheet 16 swg cable tray with necessary angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500 mm.Size / length of the tray shall be suitable for laying the above mentioned cables.Make - Fixotech/VA tech/Equivalent Size 200mmX50mm
Size 100mmX50mm
Size 50mmX50mm
FIRE PUMPS - EARTHING Supply of CU. Earthing strips shall be run on floor / ceiling / walls, from the MCC panel to all equipments as per standard with necessary accessories as required.Supply of Earth strip of 50mm x 6mm thick, complete as required
Supply of Earth pipe complete as required
Supply of 6 SWG copper as required
Supply of 6mm thick rubber mat of LT class and 1000mm wide (ISI - approved)
FIRE PUMP ROOM RELATED EQUIPMENTS-Y - STRAINER Supply of C.I.flanged "Y" type Strainer complete with SS mesh, suitable flanges, nuts, bolts and washers, rubber gaskets etc. complete as required.Make - EWAI/Normex/Upadhaya/Zoloto/Equivalent 250 mm dia
EXPANSION JOINTS - BELLOWS Supply of Expansion Bellows including rubber gasket, flanges, nuts, bolts and washers, complete as required.Make - Kanwal/easyflex/Equivalent 250 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia
SLUICE VALVE Supply of PN 16 C.I. sluice valve, FLANGED , WITH GUN METAL PARTS as per IS:1538 with non rising spindle type with flanges, bolts, nuts, washers, gaskets etc.Make - EWAI/Intervalve//Zoloto/Equivalent 250 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia
BUTTERFLY VALVE Supply of butterfly valve wafer type Stainless steel , lever operated (gear operated for 200 and above) as per IS:13095 in PN 1.6 , teflon or nylong bushing, nitrile O rings in standard mounting flanges with hand lever type with ISI mark.Make - EWAI/Intervalve//Zoloto/Equivalent 250 mm
NON RETURN VALVE Supply of Non Return Valve PN 1.6,with cast iron body , duel plate ( wafer type ) check valve with SS 304 disc and nitrile rubber lining , shell test presuure- 24.5 kg/cm2g, with required flanges, nuts, bolts and gaskets etc. complete.Make - EWAI/Intervalve//Zoloto/Equivalent 150 mm dia
100 mm dia
80 mm dia
PRESSURE REDUCING VALVE Supply of Bronze PRV reversible double reinforced food grade rubber diapragm pressure guage connections on both side of valves , SS non jamming steel bolts.Make - HAWA/HAWK/HONEYWELL/Equivalent-- -150 mm dia
BALL VALVE Supply of Ball Valve cast iron body, brass ball, as per IS 5312 with ISI mark Make-ZOLOTO/LEADER/Eqivalent 32 mm dia
20 mm dia
ALARM CHECK VALVE Supply of Alarm check valve, short pattern type with with ISI mark.Make-HD/TYCO/NEWAGE/Equivalent-- 150 mm dia
Pressure Switch Supply of pressure switch having 1/4" BSP (F) connection IP:32 enclosure protection, pressure rage 0 to 200 psi with necessary contactMake-INDFOSS/DANFOSS/Equivalent--
Pressure GuageMake-Pointer/H Guru/Equivalent Supply of pressure guage, 4 " dial, 0 - 200 psi range 3/8" BSP weatehr proof with stainles steel internals, inculding fittings etc.
Air Release Valve Make - ZOLOTO/LEADER/ATOM/Equivalent Supply of Air release valve gun metal body 25 mm dia
Air Vessel Supply of Air cushion vessel made out of 4mm MS sheet, 300 mm dia in 1000 mm height, with automaic air release cock, 25 mm drain valve and shutt off with all necessary attachments, duly painted inside with two coats of anticorrosive paint of approved synthetic enamel paint.
YARD HYDRANT - SUPPLY OF GI C CLASS PIPES & FITTINGS : From Sump Fire Water tank to Fire pump room and inside Fire Pump Room.Supply of G I Pipe Class ' C ' Heavy grade with ISI Mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. Piping shall have one coat of anticorrossive primer coat over which two coats of signal red paint. (Civil work, Core cutting required shall be done at extra cost) 250 mm
Above Ground Piping Supply of M S Pipe Class ' GI C ' medium grade with ISI Mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. Piping shall have one coat of anticorrossive primer coat over which two coats of signal red paint. (Core cutting required shall be done at extra cost) Make - JINDAL/equivalent 150 mm dia
80 mm dia
Core Cutting Marking and core cutting of walls ,concretes slabs and beams of following sizes and making them clear, in good condition. 200 mm dia
150 mm dia
Hydrant Valve Supply of Hydrant Valve- Single Headed, SS 316 -as per IS: 5290 , ISI Marked oblique pattern Hydrant Landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with pvc blank cap & chain .(min working pressure 16 bar). Make -Newage/Minimax/AAAG/Equivalent
Fire Hose (External) Supply of Fire Fighting Hose , Fire Hose - 63 mm ( 2 1/2") dia , 15 mtrs length bearing IS;636 type B, type III,,pyroprotected with ISI Marked duly bounded with SS 316 couplings, 63 mm size, pair of male & female parts, instantaneous type , heavy duty bearing IS:903 with ISI mark. Make -Newage/Minimax/AAAG/Equivalent
Branch Pipe Supply of Branch Pipe- SS 316, 63 mm dia short size branch pipe with 20 mm dia bore nozzle , as per IS:903 with -ISI Marked. Make -Newage/Minimax/AAAG/Equivalent
Hose Box (External) Supply of Hose Box (cabinet) to accommodate one piece of 63 mm dia fire hose along with one pair of 63 mm dia male & female couplings and one branch pipe. The cabinet is made of MS 16 SWG sheet with glass fronted hinged doors and lock.(550*600*250)Make-FRIENDS/AAAG/Equivalent
Fire Brigade Connection Supply of Fire brigade Inlet connection fabricated from 150 mm dia MS Class B medium grade pipe comprising of Four 63 mm dia SS 316, male threaded non return valve.Make -Newage/Minimax/AAAG/Equivalent
INTERNAL HYDRANT-Above Ground Piping-Supply of Pipe Class ' GI C ' medium grade with ISI Mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. Piping shall have one coat of anticorrossive primer coat over which two coats of signal red paint. (Core cutting required shall be done at extra cost)Make - JINDAL/Equivalent 150 mm dia
80 mm dia
Hydrant Valve Supply of Hydrant Valve- Single Headed, SS 316 -as per IS: 5290 , ISI Marked oblique pattern Hydrant Landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with pvc blank cap & chain .(min working pressure 16 bar).Make -Newage/Minimax/AAAG/equivalent
Fire Hose Supply of Fire Fighting Hose , Fire Hose - 63 mm ( 2 1/2") dia , 15 mtrs length bearing IS;636 type B, type III,,pyroprotected with ISI Marked duly bounded with SS 316 couplings, 63 mm size, pair of male & female parts, instantaneous type , heavy duty bearing IS:903 with ISI mark.Make -Newage/Minimax/AAAG/equivalent
Hose Reel Supply of Hose reel drum made of Miled Steel, Hose Reel Drum - as per IS:884 with 30 mtr length rubber hose of working pressure 7 kg/cm2 and shutt off nozzle rang of jet flow 24 ltr/min, range of jet throw 6 mtrs with ISI mark. Make -Newage/Minimax/AAAG/equivalent
Branch Pipe Supply of Branch Pipe- SS 316, 63 mm dia short size branch pipe with 20 mm dia bore nozzle , as per IS:903 with -ISI MarkedMake -Newage/Minimax/AAAG/equivalent
Hose Box Supply of Hose Box (cabinet) to accommodate one piece of 63 mm dia fire hose along with one pair of 63 mm dia male & female couplings and one branch pipe. The cabinet is made of MS 16 SWG sheet with glass fronted hinged doors and lock.(550*600*250)Make-FRIENDS/AAAG/equivalent
SIGNAGES-SIGNAGES -LED type- Make ProliteSupplying of LED E/M (S) Single Sided "EXIT" sign boards of with battery backup.
Supplying of LED E/M (S) Single Sided "FIRE EXIT" sign boards of with battery backup.
Supplying of LED E/M (S) Single Sided "FIRE DUCT" sign boards of with battery backup.
Supply of self glowing " FIRE PUMP ROOM" sign board of size 100mm x 300 mm made of luminescent safely, rigid sheet in green colour, photo luminescent rigid sheet with two each hanging chains & necessarry supports to hang it on ceiling. MAKE- AUTOGLO/equivalent
Supply of laminated sheet of " FIRE EVACUATION PLAN " of A3 size fixed on wall & necessarry accessories to fix the plan on wall.
FIRE ALARM DETECTION SYSTEM-Manual Call Point-Supply of Manual Call Point breack glass type red colour powder coated MS/ABS box fix on existing wall /frame,24/12 Volt DC operated push OFF/ON switching mechanisem with inner, outer frame, operation label and necessary attachments.Make-RAVEL/HONEYWELL/equivalent
Smoke / Heat Detectors-Supply of Conventional Smoke / Heat detectors with Base and necessary Fittings as required. Make-RAVEL/SYSTEM SENSOR/HONEYWELL/equivalent
Beam Detectors-Supply of Conventional Beam detectors, with 0 - 100 Mtr Range with required Power supply , interface unit and other required accessories and necessary Fittingsvfor a smooth function as required.Make-RAVEL/SYSTEM SENSOR/HONEYWELL/equivalent
Hooter-Supply of Audio alarm hooter ( sounder ) powder coated MS/ABS box fix on existing wall/frame, 24/12 Volt DC operated siren circuit with diaphram speaker, maxium sound 60 db intensity under stautory with necessary attachments.Make-RAVEL/HONEYWELL/equivalent
Fire Alarm Control Panel--Supply of 12 zone Automatic Fire Alarm Control panel conventional type micro processor based control made of MS sheet cabinet the powder coated, audio and digitel visual display, circuit open short functions, test/evaqvation mode, silience and reset options, common and zone wise hooter supply outputs, fault and fire mode auxilary contacts with 24 DC volt out put zone circuits, operating 230 / 50 Hz AC volts.Make-RAVEL/HONEYWELL/equivalent
Battery-Supply of Sealed Lead Acid Battery 12 V DC x 7 Ah Make- Stardust,Amaron, Powersonic/equivalent
Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required. Make-Polycab/Finolex/Havells/equivalent
P A and TALK BACK SYSTEM--P A PanelSupply of 10 zone , 2 way talk back communication / P A system with required console, Amplifier, Mic etc as required .Make-SECULITE/AHUJA/RAVEL/BOSCH/equivalent
Supply of 6 Watt Speaker / Talk Back Unit Make-SECULITE/AHUJA/RAVEL/BOSCH/equivalent
Supply of 12 w Wall Mounted SpeakerMake-SECULITE/AHUJA/RAVEL/BOSCH/equivalent
Supplying of 4C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required Make-Polycab/Finolex/Havells/equivalent
PVC Conduit Make-BALCO/ASIAN/A ONE/equivalent-Supply of 25 mm dia medium grade rigid PVC conduit ISI mark with elbow, tees, jn:boxes, saddle clip and with necessary fittings.
SUPPLY OF HIGH VELOCITY WATER SPRAY SYSTEM for OUT DOOR TRANSFORMERS ELECTRIC PUMP 100 HP, 2850 LPM - DELUGE SYSTEM-SUPPLY of Electrical Driven Fire Main Pump Horizontal Split Case Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal.Rated Flow: 2280 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Motor: 100 HP, 2900 RPM, 3Phase, 50 Hz, TEFC. The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.Make - LUBI/XYLEM/GRUNDFOSS/Equivalent
FIRE PUMPS - AUTOMATIC CONTROL PANEL SUPPLY of Electrical Driven Fire Main Pump.Horizontal Split Case Pump Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal,Rated Flow: 2280 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Motor: 100 HP, 2900 RPM, 3Phase, 50 Hz, TEFC. . The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.Make - UBI/XYLEM/GRUNDFOSS/Equivalent
Supply of High velocity water spray system for Transformer :Towards charges for Design ,detailed engineering ,Technical data sheets ,cost estimation ,4 sets of O&M manual and shop drawing
Deluge valve -H2 Model 150 mm dia wet pilot trimset with standard accessories ,Type A, UL Listed,and FM Approved Make: HD Fire/Tyco/equivalent
Gong bell Make: HD Fire/Tyco/equivalent
Pressure gauge Make: HD Fire/Tyco/equivalent
Butterfly valve lever operated PN16/Class150 150 mm dia Make: EWAI/Zolooto/Audco/equivalent
GI Pipe heavy class as per IS 1239 part1 upto 150 mm dia Make: JINDAL/equivalent 150 mm dia
65 mm dia
50 mm dia
25 mm dia
Painting (2 coat etch primer and 2 coat enamel paint)Make: ASIAN / BERGER/equivalent 150 mm dia
65 mm dia
50 mm dia
25 mm dia
80 mm dia
Quatzoid bulb detector standard response 79 deg c pendent Make: HD Fire/Tyco/Newage/equivalent
Spray Nozzle Make: HD Fire/Tyco/Newage/equivalent
Pylon foundation for pipes 250x250x650mm RCC
MS Pipes C'Class grade for pylon spray supportMake: JINDAL/equivalent-80mm dia
Deluge valve control panel Cum indication Make: Ravel/Hochiki/Shield/equivalent
Cables Supplying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required Make- Polycab/Finolex/Havells/equivalent
Solenoid valve Make: Rotex/ HD/equvalant
Flow switch Make: Honeywell/system sensor/tyco/equvalant
Electronic hooter Make: Ravel/Hochiki/Shield/equivalent
Wrapping and coating for underground pipes 4mm thick x150mm width
Strainer 150mm dia Y Type Make: EWAI/Normax/Zoloto/equivalent
Supply of Pipe Fittings : GI Elbow heavy grade as per IS 1239 PartII ,150 mm dia ,Butt welded type
GI Elbow heavy grade as per IS 1239 PartII ,65 mm dia ,Butt welded type
GI Elbow heavy grade as per IS 1239 PartII ,50 mm dia ,Butt welded type
GI Elbow heavy grade socket welded type ,25 mm dia
GI Flanges as per IS ,150 mm dia
GI Flanges as per IS ,65 mm dia
GI Flanges as per IS ,50 mm dia
GI Flanges as per IS ,25 mm dia
GI Tee 65x65x20 mm Butt welded
GI Tee 50x50x20 mm Butt welded
GI Coupling 20 mm dia
GI Coupling 15 mm dia Make:reputed /approved by client
Asbestos Gasket
GI Bolt nuts washer-2 nos
Mandatory Spares (As per Volume 4 Aneexure I)
Any Other Items for successful commissioning of the plant (Split-up as per Vol-4 Annexure-3 Other Items - Supply)(As per Volume 4 Aneexure II)
Description of Work / Item(s)
Amount
Schedule A2 - Service (Erection, Testing & Commissioning)
INSTALLATION OF MODULAR CLEAN AGENT ADDRESSABLE FIRE DETECTION CONTROL AND SUPPRESSION SYSTEM for Generator 30MW, Generator 10MW and Cable Gallery FIRE SUPPRESSION SYSTEM FOR STATOR - 1 & STATOR - 2 AND FLAME DETECTION SYSTEM IN A CABLE GALLARY Installation Testing & Commissioning of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN
Installation of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah. Make: Amaron / Star Dust / Powersonic
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah.
Installation Testing & Commissioning of Probe type Heat detector 80 - 145 Deg
Installation Testing & Commissioning of Addressable type Abort Switch with suitable input module if required. Make Hochiki/Ravel/System sensor/Equvalant .
Installation Testing & Commissioning of Addressable type Emergency Release Switch (Electrical) with suitable input module if required.
Installation Testing & Commissioning of Addressable type Hooter for First stage Alert. with suitable Sounder module power supply etc as required.
Installation Testing & Commissioning of Addressable type Hooter cum Strobe for second stage Alert. with suitable Sounder module, power supply etc as required.
Installation Testing & Commissioning of Addressable type Strobe for Released Alert. with suitable Sounder module, power supply etc as required.
Installation Testing & Commissioning of Addressable type input / Monitor module with required accessories as required to monitor in the event if low pressure in a purticular module.
Installation Testing & Commissioning of Addressable type Control module with required accessories as required to control /operate any 3rd party devices in the event fire if required.
laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required.
IR / UV TRIPLE SENSOR FLAME DETECTOR FOR A CABLE FLOORInstallation of fladet series.. Triple Sensor - IR / UV Flame Detector with FM,ATEX & PESO approved Ex. Proof Enclosure. Flickering LED Indication for normal operation. 24 V DC, 4 wire system with IHMB08 XY base
Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah.
Installation Testing & Commissioning of Addressable type duel input / Monitor module with required accessories as required to monitor in the event if low pressure in a purticular module.
laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required.
INSTALLATION OF MODULAR CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR - BATTERY ROOM Installation Testing & Commissioning of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN
Installation of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah
Installation Testing & Commissioning of Conventional 2 Zone Fire Detection Extinguishant control panel. Suitable for cross zonning and reliable exhingushant system with battery charger.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah.
Installation Testing & Commissioning of Conventional Smoke detector/ heat detector with base.
Installation Testing & Commissioning of Abort Switch.
Installation Testing & Commissioning of Emergency Release Switch (Electrical).
Installation Testing & Commissioning of Hooter for First stage Alert.
Installation Testing & Commissioning of Hooter cum Strobe for second stage Alert.
Installation Testing & Commissioning of Strobe for Released stage Alert.
laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
INSTALLATION OF MODULAR CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR CONTROL ROOM Installation Testing & Commissioning of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN
Installation of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah
Installation Testing & Commissioning of Conventional 2 Zone Fire Detection Extinguishant control panel. Suitable for cross zonning and reliable exhingushant system with battery charger.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah.
Installation Testing & Commissioning of Conventional Smoke detector/ heat detector with base.
Installation Testing & Commissioning of Abort Switch.
Installation Testing & Commissioning of Emergency Release Switch (Electrical).
Installation Testing & Commissioning of Hooter for First stage Alert.
Installation Testing & Commissioning of Hooter cum Strobe for second stage Alert.
Installation Testing & Commissioning of Strobe for Released stage Alert.
laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
INSTALLATION OF MODULAR CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR L T SWITCH GEAR ROOM Installation Testing & Commissioning of the Fire Spot Modular type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. The tank should constructed of Mild Steel, grade CR2 of IS 513,Internal and external surface of cylinder pure polyester powder coated for corrosion resistance,UV resistant Vinyl label, QR code for product traceability, CE marked solenoid valve fitted with pendent sprinkler, Pressure switch with NO-NC Contact Container in 10 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar. Area coverage 3 mtr x 3 mtr for one cylinder.The container includes pressure gauge adaptor, valve assembly and Pressure Switch. The adaptor assembly includes a Stainless Steel adaptor, Actuation valve and a Sprinkler valve. the entire systm should have national test house certification. anf the system shall be UL / EN
Installation of Contact Relay & Power Supply Unit - 24v DC/5 - 20 Amp with battery back up and fault monitoring.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah
Installation Testing & Commissioning of Conventional 2 Zone Fire Detection Extinguishant control panel. Suitable for cross zonning and reliable exhingushant system with battery charger.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah.
Installation Testing & Commissioning of Conventional Smoke detector/ heat detector with base.
Installation Testing & Commissioning of Abort Switch.
Installation Testing & Commissioning of Emergency Release Switch (Electrical).
Installation Testing & Commissioning of Hooter for First stage Alert.
Installation Testing & Commissioning of Hooter cum Strobe for second stage Alert.
Installation Testing & Commissioning of Strobe for Released stage Alert.
laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
INSTALLATION OF PANEL FIRE PROTECTION -(4Kg) CLEAN AGENT FIRE SUPPRESSION SYSTEM For LT PANEL - 1, AND LT PANEL- 2 Installation Testing & Commissioning of the Fire Spot Panel Protection System, 4 kg type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. Portable Type. The tank is constructed of Mild Steel, grade CR1 of IS 513. Dip tube Container in 4 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar, Discharging % -minimum 95% of initial charge. The area coverage should be 9.03 cu.m ,The cylinder have Inbuild pressure gauge adaptor and Pressure Switch ,The cylinder included Polyimide Tube . The adaptor assembly includes a Stainless Steel adaptor, The Portable cylinder should have UL/EN and the entire system should have National Test House certification (NTH).
Installation Testing & Commissioning of Polymer tube for Fire Spot panel protection system –Designed with multi-layer polymids tube with internal dia meter 4mm and outer dia 6mm with maximum working pressure 20/ burst pressure 100 bar ,Burst Temperature 60digree.The tube should have UL/EN Approval and the entire system should have National Test House certification.
Installation Testing & Commissioning of power supply for Monitoring panel.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah
Installation Testing & Commissioning of Hooter cum Strobe for Notification.
Installation Testing & Commissioning of Addressable type output module with required accessories as required to operatesounder, sounder strobe in the event of fire.
Installation Testing & Commissioning of Addressable type input / Monitor module with required accessories as required to monitor in the event if low pressure in a module.
laying of 2C x 1.5 sqmm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
INSTALLATION PANEL FIRE PROTECTION -(2KG) CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR LT PANEL -3 BC-1,AND BC-2 Installation Testing & Commissioning of the Fire Spot Panel Protection System, 2 kg type extinguishing agent is Hexafluoropropane, synonyms are HFC 236fa. Portable Type. The tank is constructed of Mild Steel, grade CR1 of IS 513. Dip tube Container in 4 kg capacity. The Container has a working pressure of 8 bar, a test pressure of 35 bar, and a minimum burst pressure of 80 bar, Discharging % -minimum 95% of initial charge. The area coverage should be 9.03 cu.m ,The cylinder have Inbuild pressure gauge adaptor and Pressure Switch ,The cylinder included Polyimide Tube . The adaptor assembly includes a Stainless Steel adaptor, The Portable cylinder should have UL/EN and the entire system should have National Test House certification (NTH).
Installation Testing & Commissioning of Polymer tube for Fire Spot panel protection system –Designed with multi-layer polymids tube with internal dia meter 4mm and outer dia 6mm with maximum working pressure 20/ burst pressure 100 bar ,Burst Temperature 60digree.The tube should have UL/EN Approval and the entire system should have National Test House certification.
Installation Testing & Commissioning of power supply for Monitoring panel.
Installation Testing & Commissioning of Battery 12V Dc x 12 Ah
Installation Testing & Commissioning of Hooter cum Strobe for Notification.
Installation Testing & Commissioning of Addressable type output module with required accessories as required to operatesounder, sounder strobe in the event of fire.
Installation Testing & Commissioning of Addressable type input / Monitor module with required accessories as required to monitor in the event if low pressure in a module.
laying of 2C x 1.5 sqmm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
INSTALLATION OF FIRE PUMPS, FIRE PUMP PANELS AND FIRE PUMP ROOM RELATED EQUIPMENTS,FIRE PUMPS AND FIRE PUMP PANELS ELECTRIC PUMP 100 HP, 2850 LPM @ 88 MTR HEAD - SPRINKLER SYSTEMInstallation of of Electrical Driven Fire Main Pump. Horizontal Split Case Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical SealRated Flow: 2280 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Motor: 100 HP, 2900 RPM, 3Phase, 50 Hz, TEFC.The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.
ELECTRIC PUMP 100 HP, 2850 LPM @ 88 MTR HEAD - HYDRANT SYSTEM-Installation of Electrical Driven Jockey Fire Pump Endsuction Close Coupled Pump Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical SealRated Flow: 180 @ 88 mtr Head,Suction x Discharge: DN 50 x 32 DN, Motor: 12.5 HP, 2900 RPM, 3Phase, 50 Hz, TEFC.The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.
JOCKEY PUMP,12.5 HP 180 LPM @ 88 MTR HEAD - SPRINKLER SYSTEM-Installation of Electrical Driven Jockey Fire Pump.Endsuction Close Coupled Pump Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical SealRated Flow: 180 @ 88 mtr Head,Suction x Discharge: DN 50 x 32 DN,Motor: 12.5 HP, 2900 RPM, 3Phase, 50 Hz, TEFC.The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.
JOCKEY PUMP 12.5 HP 180 LPM @ 88 MTR HEAD - HYDRANT SYSTEM-Installation of Electrical Driven Jockey Fire Pump Endsuction Close Coupled Pump Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical SealRated Flow: 180 @ 88 mtr Head,Suction x Discharge: DN 50 x 32 DN,Motor: 12.5 HP, 2900 RPM, 3Phase, 50 Hz, TEFC.The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.
DIESEL ENGINE PUMP -103 HP, 2850 @ 88 MTR HEAD - STANDBY-Installation of Diesel Engine Driven Fire Main Pump Horizontal Split Case Pump.Type: LHC , MOC: CI Casing , Bronze Impeller, Shaft - SS AISI 410, Mechnical Seal.Rated Flow: 2850 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Eicher Diesel Engine: 103 HP, 2150 RPM, With Coupling, Coupling Guard, Base Frame. included [ 12V Battery, 200 ltr Fuel Tank, Anti Vibration Pads. Engine Driven Fire Pump Controller -
Fixing , testing and commissioning of Exhaust pipe of dia 150mm MS medium grade for Diesel engine with mineral wool insulation with aluminum cladding including necessary supports through shaft up to terrace level
FIRE PUMPS - CABLING/GLANDING laying ,testing and commissioning of FRLS,PVC outer sheathed, steel armored, aluminum conductor, 1100 Vgrade power cables with glands etc.The cables shall be laid in tray / Hume pipe / in trenches/on walls/ floor etc. as required. For cables laid out door the rate shall include earth excavation providing brick and sand protection, refilling and compacting the earth.The rate shall excludes tray.The minimum size & length of the cables shall be considered as required for the complete system .12 C x 2.5 Sqmm. Copper cable Diesel engines
4 C x 25 Sqmm. Aluminum cable for Jockeypumps
2 C x 2.5 Sqmm.Copper cable for Instrumentation
3.5C x 95 sq.mm Aluminum cable for main pumps
End Termination of 12 C x 2.5 Sqmm. Copper cable with suitable gland for Diesel engines
End Termination of 4 C x 25 Sqmm. Aluminum cable with suitable gland for Jockey pumps
End Termination of 2 C x 2.5 Sqmm.Copper cable with suitable gland for Instrumentation
End Termination of 3.5C x 95 sq.mm Aluminum cable with suitable gland for main pumps
Any other work related to Cabling glanding earthing to fulfill the work
FIRE PUMPS - CABLE TRAY fixing , testing and commissioning of perforated G.I.sheet 16 swg cable tray with necessary angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500 mm.Size / length of the tray shall be suitable for laying the above mentioned cables. Size 200mmX50mm
Size 100mmX50mm
Size 50mmX50mm
FIRE PUMPS - EARTHINGfixing , testing and commissioning of perforated G.I.sheet 16 swg cable tray with necessary angle iron suspension supports, anchor fasteners etc. complete. Maximum height of suspension shall not exceed 500 mm.Size / length of the tray shall be suitable for laying the above mentioned cables. Installation of Earth strip of 50mm x 6mm thick, complete as required
Installation of Earth pipe complete as required
laying of 6 SWG copper as required
Providing ,fixing , testing and commissioning of 6mm thick rubber mat of LT class and 1000mm wide (ISI - approved)
FIRE PUMP ROOM RELATED EQUIPMENTS Y - STRAINER- Installation Testing and Commissioning of C.I.flanged "Y" type Strainer complete with SS mesh, suitable flanges, nuts, bolts and washers, rubber gaskets etc. complete as required. 250 mm dia
EXPANSION JOINTS - BELLOWS Installation Testing and Commissioning of Expansion Bellows including rubber gasket, flanges, nuts, bolts and washers, complete as required. 250 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia
SLUICE VALVE Installation Testing and Commissioning of PN 16 C.I. sluice valve, FLANGED , WITH GUN METAL PARTS as per IS:1538 with non rising spindle type with flanges, bolts, nuts, washers, gaskets etc. 250 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia
BUTTERFLY VALVE Installation Testing and Commissioning of butterfly valve wafer type Stainless steel , lever operated (gear operated for 200 and above) as per IS:13095 in PN 1.6 , teflon or nylong bushing, nitrile O rings in standard mounting flanges with hand lever type with ISI mark. 250 mm
NON RETURN VALVE Installation Testing and Commissioning of Non Return Valve PN 1.6,with cast iron body , duel plate ( wafer type ) check valve with SS 304 disc and nitrile rubber lining , shell test presuure- 24.5 kg/cm2g, with required flanges, nuts, bolts and gaskets etc. complete. 150 mm dia
100 mm dia
80 mm dia
PRESSURE REDUCING VALVE Installation of Bronze PRV reversible double reinforced food grade rubber diapragm pressure guage connections on both side of valves , SS non jamming steel bolts.--150 mm dia
BALL VALVE Installation Testing and Commissioning of Ball Valve cast iron body, brass ball, as per IS 5312 with ISI mark 32 mm dia
20 mm dia
ALARM CHECK VALVE Installation Testing and Commissioning of Alarm check valve, short pattern type with with ISI mark.--150 mm dia
Pressure Switch Installation Testing and Commissioning of pressure switch having 1/4" BSP (F) connection IP:32 enclosure protection, pressure rage 0 to 200 psi with necessary contact
Pressure Guage Installation Testing and Commissioning of pressure guage, 4 " dial, 0 - 200 psi range 3/8" BSP weatehr proof with stainles steel internals, inculding fittings etc.
Air Release Valve Installation Testing and Commissioning of Air release valve gun metal body 25 mm dia
Air Vessel Installation Testing and Commissioning of Air cushion vessel made out of 4mm MS sheet, 300 mm dia in 1000 mm height, with automaic air release cock, 25 mm drain valve and shutt off with all necessary attachments, duly painted inside with two coats of anticorrosive paint of approved synthetic enamel paint.
YARD HYDRANT-Installation of GI C CLASS PIPES & FITTINGS : From Sump Fire Water tank to Fire pump room and inside Fire Pump Room.Installation of G I Pipe Class ' C ' Heavy grade with ISI Mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. Piping shall have one coat of anticorrossive primer coat over which two coats of signal red paint. (Civil work, Core cutting required shall be done at extra cost) 250 mm
Above Ground Piping Installation of M S Pipe Class ' GI C ' medium grade with ISI Mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. Piping shall have one coat of anticorrossive primer coat over which two coats of signal red paint. (Core cutting required shall be done at extra cost) 150 mm dia
80 mm dia
Core Cutting Marking and core cutting of walls ,concretes slabs and beams of following sizes and making them clear, in good condition.200 mm dia
150 mm dia
Hydrant Valve Installation of Hydrant Valve- Single Headed, SS 316 -as per IS: 5290 , ISI Marked oblique pattern Hydrant Landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with pvc blank cap & chain .(min working pressure 16 bar).
Fire Hose (External) Installation of Fire Fighting Hose , Fire Hose - 63 mm ( 2 1/2") dia , 15 mtrs length bearing IS;636 type B, type III,,pyroprotected with ISI Marked duly bounded with SS 316 couplings, 63 mm size, pair of male & female parts, instantaneous type , heavy duty bearing IS:903 with ISI mark.
Branch Pipe Installation of Branch Pipe- SS 316, 63 mm dia short size branch pipe with 20 mm dia bore nozzle , as per IS:903 with -ISI Marked
Hose Box (External) Installation of Hose Box (cabinet) to accommodate one piece of 63 mm dia fire hose along with one pair of 63 mm dia male & female couplings and one branch pipe. The cabinet is made of MS 16 SWG sheet with glass fronted hinged doors and lock.(550*600*250)
Fire Brigade Connection Installation of Fire brigade Inlet connection fabricated from 150 mm dia MS Class B medium grade pipe comprising of Four 63 mm dia SS 316, male threaded non return valve.
INTERNAL HYDRANT Above Ground Piping -Installation of Pipe Class ' GI C ' medium grade with ISI Mark complete with all necessary fittings such as nuts & bolts, bends, flanges, tees etc. Piping shall have one coat of anticorrossive primer coat over which two coats of signal red paint. (Core cutting required shall be done at extra cost) 150 mm dia
80 mm dia
Hydrant Valve Installation of Hydrant Valve- Single Headed, SS 316 -as per IS: 5290 , ISI Marked oblique pattern Hydrant Landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with pvc blank cap & chain .(min working pressure 16 bar).
Fire Hose Installation of Fire Fighting Hose , Fire Hose - 63 mm ( 2 1/2") dia , 15 mtrs length bearing IS;636 type B, type III,,pyroprotected with ISI Marked duly bounded with SS 316 couplings, 63 mm size, pair of male & female parts, instantaneous type , heavy duty bearing IS:903 with ISI mark.
Hose Reel Installation of Hose reel drum made of Miled Steel, Hose Reel Drum - as per IS:884 with 30 mtr length rubber hose of working pressure 7 kg/cm2 and shutt off nozzle rang of jet flow 24 ltr/min, range of jet throw 6 mtrs with ISI mark.
Branch Pipe Installation of Branch Pipe- SS 316, 63 mm dia short size branch pipe with 20 mm dia bore nozzle , as per IS:903 with -ISI Marked
Hose Box Installation of Hose Box (cabinet) to accommodate one piece of 63 mm dia fire hose along with one pair of 63 mm dia male & female couplings and one branch pipe. The cabinet is made of MS 16 SWG sheet with glass fronted hinged doors and lock.(550*600*250)
SIGNAGES-SIGNAGES -LED type- Make Prolite Installing in position LED E/M (S) Single Sided "EXIT" sign boards of with battery backup.
Installing in position LED E/M (S) Single Sided "FIRE EXIT" sign boards of with battery backup.
Installing in position LED E/M (S) Single Sided "FIRE DUCT" sign boards of with battery backup.
Installation of self glowing " FIRE PUMP ROOM" sign board of size 100mm x 300 mm made of luminescent safely, rigid sheet in green colour, photo luminescent rigid sheet with two each hanging chains & necessarry supports to hang it on ceiling.
Installing in position laminated sheet of " FIRE EVACUATION PLAN " of A3 size fixed on wall & necessarry accessories to fix the plan on wall.
FIRE ALARM DETECTION SYSTEMManual Call Point Installation of Manual Call Point breack glass type red colour powder coated MS/ABS box fix on existing wall /frame,24/12 Volt DC operated push OFF/ON switching mechanisem with inner, outer frame, operation label and necessary attachments.
Smoke / Heat Detectors Installation of Conventional Smoke / Heat detectors with Base and necessary Fittings as required.
Beam Detectors Installation of Conventional Beam detectors, with 0 - 100 Mtr Range with required Power supply , interface unit and other required accessories and necessary Fittingsvfor a smooth function as required.
Hooter Installation of Audio alarm hooter ( sounder ) powder coated MS/ABS box fix on existing wall/frame, 24/12 Volt DC operated siren circuit with diaphram speaker, maxium sound 60 db intensity under stautory with necessary attachments.
Fire Alarm Control Panel Installation of 12 zone Automatic Fire Alarm Control panel conventional type micro processor based control made of MS sheet cabinet the powder coated, audio and digitel visual display, circuit open short functions, test/evaqvation mode, silience and reset options, common and zone wise hooter supply outputs, fault and fire mode auxilary contacts with 24 DC volt out put zone circuits, operating 230 / 50 Hz AC volts.
Battery Installation of Sealed Lead Acid Battery 12 V DC x 7 Ah
laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
Installation of 10 zone , 2 way talk back communication / P A system with required console, Amplifier, Mic etc as required
Installation of 6 Watt Speaker / Talk Back Unit
Installation of 12 w Wall Mounted Speaker
laying of 4C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
PVC Conduit Installation of 25 mm dia medium grade rigid PVC conduit ISI mark with elbow, tees, jn:boxes, saddle clip and with necessary fittings.
INSTALLATION OF HIGH VELOCITY WATER SPRAY SYSTEM for OUT DOOR TRANSFORMERS ELECTRIC PUMP 100 HP, 2850 LPM - DELUGE SYSTEM Installation of Electrical Driven Fire Main Pump.Horizontal Split Case Pump.Type: LHC , MOC: CI Casing – Bronze Impeller, Shaft : SS AISI410, Mechnical Seal,Rated Flow: 2280 @ 88 mtr Head,Suction x Discharge: DN 100 x 80 DN,Motor: 100 HP, 2900 RPM, 3Phase, 50 Hz, TEFC The quoted rate shall includes anti vibration pad, coupling, coupling guard, foundation bolts etc, complete as per the manufactures recommendations. Cost of pump shall be inlusive of RCC foundation.Cabling required for automation of pumps shall be measured extra.
Installation of High velocity water spray system for Transformer :Towards charges for Design ,detailed engineering ,Technical data sheets ,cost estimation ,4 sets of O&M manual and shop drawing
Installation of Deluge valve -H2 Model 150 mm dia wet pilot trimset with standard accessories ,Type A, UL Listed,and FM Approved
Installation of Gong bell
Installation of Pressure gauge
Instyallation of Butterfly valve lever operated PN16/Class150 150 mm dia
Installation of GI Pipe heavy class as per IS 1239 part1 upto 150 mm dia 150 mm dia
65 mm dia
50 mm dia
25 mm dia
Painting (2 coat etch primer and 2 coat enamel paint) 150 mm dia
65 mm dia
50 mm dia
25 mm dia
80 mm dia
Installation of Quatzoid bulb detector standard response 79 deg c pendent
Installation of Spray Nozzle
Installation of Pylon foundation for pipes 250x250x650mm RCC
Installation of MS Pipes C'Class grade for pylon spray support 80mm dia
Installation of Deluge valve control panel Cum indication
Cables laying of 2C x 1.5 sqmm fire alarm armoured copper cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath, with required accesssories complete as required
Installation of Solenoid valve
Installation of Flow switch
Installation of Electronic hooter
Wrapping and coating for underground pipes 4mm thick x150mm width
Installation of Strainer 150mm dia Y Type
Installation of Pipe Fittings :GI Elbow heavy grade as per IS 1239 PartII ,150 mm dia ,Butt welded type
GI Elbow heavy grade as per IS 1239 PartII ,65 mm dia ,Butt welded type
GI Elbow heavy grade as per IS 1239 PartII ,50 mm dia ,Butt welded type
GI Elbow heavy grade socket welded type ,25 mm dia
GI Flanges as per IS ,150 mm dia
GI Flanges as per IS ,65 mm dia
GI Flanges as per IS ,50 mm dia
GI Flanges as per IS ,25 mm dia
GI Tee 65x65x20 mm Butt welded
GI Tee 50x50x20 mm Butt welded
GI Coupling 20 mm dia
GI Coupling 15 mm dia
Installation of Asbestos Gasket
Fixing GI Bolt nuts washer-2 nos
Additional work - Excavation, back filling, structral work, structral materials like channel / Angle, RCC Hume pipe, etc
Testing and commissioning of Total HVWSS System
Any Other Items for successful commissioning of the plant (Split-up as per Vol-4 Annexure-4 Other Items - Service)
Description of Work / Item(s)
Amount
Abstract Schedule (A1 + A2)
Price Shedule Total - Supply (BoQ1)
Price Schedule Total - Service (BoQ2)
Allies Fire Systems Pvt Ltd
Allies Fire Systems Pvt Ltd
Allies Fire Systems Pvt Ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .