Regional project director
Kerala Rural Water Supply and Sanitation Agency, Regional Project Management Unit, Malappuram, MMC.X/108-112, UMK Tower, Uphill, Jubilee Road, Near Passport Office, Malappuram P.O. - 676 505
Sustainability Support to Community Managed Water Supply Schemes - 2025-26 -Rehabiltation and renovation of Kanakkankkad WSS and Thonippara challapotta in Elevencherry Grama Panchayath, Palakkad District.- General Civil Work
2026_KRWSA_835680_1
KRWSA/MPM/SUS/ELV/25-26/06
Open Tender
Civil Works - Water Works
Item Rate
120 days
Elavanchery GP palakkad district
As per tender document
7 documents required · 7 mandatory
₹2,500
₹32,855
11 Feb 2026
11 Feb 2026
21 Apr 2026
11 Feb 2026
20 Apr 2026
11 Feb 2026
11 Feb 2026 - 20 Apr 2026
APPENDIX A - KANAKKANKKADU WSS
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared
Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Hard rock (blasting prohibited)
DOWEL BARS - Supplying and providing MS dowel bars of size 16 mm dia of 2m long (1m in rock and 1m in concrete ) including drilling holes of 20mm dia to a depth of 1m in rock and filling the gap with cement grout( 0.10kg/each) etc complete
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand (zone-III)derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up tot floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size derived from natural sources)
Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) derived from natural sources: 3 graded stone aggregate 20 mm nominal size derived from natural sources).
Supplying and fixing C.I with out frame for manholes:500 mm diameter C.I. (medium duty) the weight of the cover to be not less than 58 kg
Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)
Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
Lettering with black Japan pint of approved brand and manufacture
Providing and fixing G.I. pipes complete with G.I fittings including trenching and refilling etc. External work50 mm dia nominal bore (medium)
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work- Exposed on wall50 mm dia nominal bore (medium)
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :50 mm nominal bore
Engaging Coolie
Engaging Fitter ( grade 1)
Replacing of 15 mm (1/2 inch) old/non functional water meter from existing water meter connection system by providing brand new Water Meter, Indian Standard, Class B, Multijet, 15mm ( 1/2 inch ).up to a length of 4 m using 20 mm Indian Standard Class 6 uPVC pipe and uPVC / GM / Brass specials viz. , Ball Valve, uPVC, 12.5kg/cm2, Elbow, MTA, FTA, couplers, etc. and connecting with the mains, testing the joints etc. complete connection pipe and service pipe,including cost of material, consumable, hire charges for tools and labour charge etc. but excluding charges for cutting the concrete / tarred / bituminous roads etc., and as per the direction of the departmental officers
Providing 20mm (3/4 inch) house connection with 15mm (1/2 inch) water meter from existing PVC / HDPE mains up to 110 mm dia., up to a length of 5 m using 25mm Indian Standard Class 6 uPVC pipe and uPVC / GM / Brass specials viz. brass ferrule, GM full way wheel valve, Elbow, MTA, FTA, couplers, PVC Service Saddle of suitable size etc. and connecting with the mains, testing the joints etc. complete including trenching and refilling in all kinds of soil up to a depth of 1.50m for main line tracing and trench of average cross section 0.3m x 0.75m for laying connection pipe and service pipe, fixing water meter, lighting, watching, providing caution boards, traffic control etc. complete including cost of materials, hire for tools, cost of consumables and labour charges, including the cost of tested Class B Multijet water meter with ISI mark and weather resistant PP / PE meter box of minimum size 300mm x 200mm x 150mm, but excluding charges for cutting the concrete / tarred / bituminous roads etc, and as per the direction of the departmental officers.
Providing and laying D.I specials of class K - 12 suitable for push - on jointing as per IS : 9523 :Upt 600 mm dia
Testing water sample from the source of scheme at any Government laboratory and submitting the report - both physical and bacteriological parameters
Appendix B :THONIPPARA CHALLAPOTTA WSS
Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
Lettering with black Japan pint of approved brand and manufacture
Providing and fixing G.I. pipes complete with G.I fittings including trenching and refilling etc. External work32 mm dia nominal bore (medium)
Providing and fixing G.I. pipes complete with G.I fittings including trenching and refilling etc. External work40 mm dia nominal bore(medium)
Providing and fixing G.I. pipes complete with G.I fittings including trenching and refilling etc. External work50 mm dia nominal bore (medium)
Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in all kinds of soil.
Supply of PVC Pipe, 10kg/cm2, 50mm Dia
Laying uPVC pipes of class 2 to class 6 and specials, lowering to the trenches already made, placing in position aligning the pipeline to the lines and levels and jointing the pipes and specials with solvent cement and testing the pipeline with water to the required test pressure (excluding cost of pipes and specials): 50 mm nominal outside diameter pipes.
Replacing of 15 mm (1/2 inch) old/non functional water meter from existing water meter connection system by providing brand new Water Meter, Indian Standard, Class B, Multijet, 15mm ( 1/2 inch ).up to a length of 4 m using 20 mm Indian Standard Class 6 uPVC pipe and uPVC / GM / Brass specials viz. , Ball Valve, uPVC, 12.5kg/cm2, Elbow, MTA, FTA, couplers, etc. and connecting with the mains, testing the joints etc. complete connection pipe and service pipe,including cost of material, consumable, hire charges for tools and labour charge etc. but excluding charges for cutting the concrete / tarred / bituminous roads etc., and as per the direction of the departmental officers
Testing water sample from the source of scheme at any Government laboratory and submitting the report - both physical and bacteriological parameters
Supplying and Laying UPVC pipe specials for 50mm dia UPVC pipe with class 10kg/cm2 or higher at 3% rate of cost of pipe
Percentage of applicable GST
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_1406153.xls
BOQ • 0.31 MB
Tenderdocumentelv.pdf
Tender Documents • 3.51 MB
Formatselv.pdf
Other Document • 0.25 MB
corri70426.pdf
PDF • 0.44 MB
corri310326.pdf
PDF • 0.44 MB
corre23326.pdf
PDF • 1.15 MB
corri16march.pdf
PDF • 0.45 MB
corri2.pdf
PDF • 0.44 MB
corri.pdf
PDF • 0.27 MB
corri.pdf
PDF • 0.09 MB
corregendumtimeextension.pdf
PDF • 0.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .