| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹92.3 CrAccepted-AOC 216 C SIVA COLONY MAYO LINK ROAD AJMER RAJASTHAN 305007 | AJMER | RAJASTHAN | 305007 | ₹92.3 Cr Quoted ₹92.4 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹96.8 CrRejected-Finance D 7 7431 VASANT KUNJ NEW DELHI 110070 | NEW DELHI | NEW DELHI | DELHI | 110070 | ₹96.8 Cr | L2 | Rejected-Finance Not being lowest |
| 3 | L3₹97.8 CrRejected-Finance MANATHA ENCLAVE 3RD FLOOR OLIMUGAL KAKKANAD P O KOCHI 682 030 KERALA | ERNAKULAM | KERALA | 682030 | ₹97.8 Cr | L3 | Rejected-Finance Not being lowest |
| 4 | L4₹100.0 CrRejected-Finance 610B NILGIRI BLOCK ADITYA ENCLAVE AMEERPET HYDERABAD 500038 | HYDERABAD | TELANGANA | 500038 | ₹100.0 Cr | L4 | Rejected-Finance Not being lowest |
| 5 | L5₹104.0 CrRejected-Finance PREMISES NO 5 30 5 N C SENGUPTA SARANI GROUND FLOOR MALL ROAD KOLKATA WEST BENGAL INDIA 700 080 | KOLKATA | KOLKATA | WEST BENGAL | 700080 | ₹104.0 Cr | L5 | Rejected-Finance Not being lowest |
| Sl No | Description | Qty | Unit | Sri Avantika Contractors (I) Limited L4 | C S CONSTRUCTION COMPANY PVT. LTD. L2 | CHERIAN VARKEY CONSTRUCTION CO PVT LTD L7 | JAIN BUILDER L1 | PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED L5 | Mecone Construction Contractors L3 | REPLAJCC JV L6 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Total amount of Sch 'A' Part-I : (Buildings/ Structures) | 1 | LUMPSUM | 50,15,66,740 ₹50.2 Cr | 53,25,76,300 ₹53.3 Cr | 47,58,00,922 ₹47.6 Cr | 37,41,04,179 ₹37.4 Cr | 56,48,00,000 ₹56.5 Cr | 48,05,85,000 ₹48.1 Cr | 52,65,54,000 ₹52.7 Cr |
| 2.00 | Total amount of Sch 'A' Part-II : (Site clearance and site development) | 1 | LUMPSUM | 2,50,000 ₹2.5 L | 3,13,315 ₹3.1 L | 3,90,000 ₹3.9 L | 2,00,000 ₹2 L | 3,07,500 ₹3.1 L | 2,94,209.52 ₹2.9 L | 2,67,463.2 ₹2.7 L |
| 3.00 | Total amount of Sch 'A' Part-III : (Earthwork) | 1 | LUMPSUM | 76,33,235 ₹76.3 L | 64,75,300 ₹64.8 L | 84,00,000 ₹84 L | 64,44,444 ₹64.4 L | 88,17,797 ₹88.2 L | 92,43,064.03 ₹92.4 L | 84,02,785.48 ₹84.0 L |
| 4.00 | Total amount of Sch 'A' Part-IV : (Internal Water Supply) | 1 | LUMPSUM | 17,23,860 ₹17.2 L | 20,12,000 ₹20.1 L | 25,00,000 ₹25 L | 15,00,000 ₹15 L | 21,97,050 ₹22.0 L | 21,11,014.31 ₹21.1 L | 34,54,387.06 ₹34.5 L |
| 5.00 | Total amount of Sch 'A' Part-V : (Internal Electric Supply) | 1 | LUMPSUM | 20,30,875 ₹20.3 L | 19,10,000 ₹19.1 L | 32,00,000 ₹32 L | 15,00,000 ₹15 L | 23,26,440 ₹23.3 L | 27,28,410.3 ₹27.3 L | 25,33,523.85 ₹25.3 L |
| 6.00 | Total amount of Sch 'A' Part- VI : (External Water Supply) | 1 | LUMPSUM | 1,04,783.73 ₹1.0 L | 1,05,925 ₹1.1 L | 2,00,000 ₹2 L | 70,000 ₹70,000 | 1,31,250 ₹1.3 L | 1,53,836.69 ₹1.5 L | 1,67,821.85 ₹1.7 L |
| 7.00 | Total amount of Sch 'A' Part-VII : (External Electric Supply) | 1 | LUMPSUM | 14,41,222.6 ₹14.4 L | 18,11,875 ₹18.1 L | 28,00,000 ₹28 L | 13,00,000 ₹13 L | 23,90,588 ₹23.9 L | 22,60,437.55 ₹22.6 L | 24,94,275.92 ₹24.9 L |
| 8.00 | Total amount of Sch 'A' Part-VIII : (Lightning Protection) | 1 | LUMPSUM | 14,636.17 ₹14,636.17 | 1,78,900 ₹1.8 L | 2,70,000 ₹2.7 L | 1,20,000 ₹1.2 L | 2,43,900 ₹2.4 L | 1,86,465.12 ₹1.9 L | 2,33,081.4 ₹2.3 L |
| 9.00 | Total amount of Sch 'A' Part-IX : (Area Drainage) | 1 | LUMPSUM | 22,00,000 ₹22 L | 21,95,500 ₹22.0 L | 35,00,000 ₹35 L | 18,00,000 ₹18 L | 27,98,663 ₹28.0 L | 25,92,176.76 ₹25.9 L | 27,04,880.1 ₹27.0 L |
| 10.00 | Total amount of Sch 'A' Part-X : (Sewage Disposal) | 1 | LUMPSUM | 3,25,977.45 ₹3.3 L | 3,90,250 ₹3.9 L | 6,00,000 ₹6 L | 2,50,000 ₹2.5 L | 3,15,504 ₹3.2 L | 3,91,310.86 ₹3.9 L | 4,08,324.37 ₹4.1 L |
Tender Value
₹110 Cr
EMD Value
₹15 L
Closing Date
15 Jul 2025, 6:00 pmClosed
CE (NW) KOCHI
CHIEF ENGINEER NAVAL WORKS KOCHI MILITARY ENGINEER SERVICE NAVAL BASE POST KATARIBAGH KOCHI-682004
PROVISION OF DEFICIENT SINGLE LIVING ACCN FOR 800 JUNIOR SAILORS AT NAVAL BASE, KOCHI
2025_MES_704632_1
891063
Open Tender
Civil Works
900 days
KOCHI
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,000
Yes
GE (P) KOCHI
₹15 L
Yes
11 Sept 2025
17 Apr 2025
17 Jul 2025
17 Apr 2025
15 Jul 2025
7 Jul 2025
17 Apr 2025 - 10 May 2025
Amount
Total amount of Sch 'A' Part-I : (Buildings/ Structures)
Total amount of Sch 'A' Part-II : (Site clearance and site development)
Total amount of Sch 'A' Part-III : (Earthwork)
Total amount of Sch 'A' Part-IV : (Internal Water Supply)
Total amount of Sch 'A' Part-V : (Internal Electric Supply)
Total amount of Sch 'A' Part- VI : (External Water Supply)
Total amount of Sch 'A' Part-VII : (External Electric Supply)
Total amount of Sch 'A' Part-VIII : (Lightning Protection)
Total amount of Sch 'A' Part-IX : (Area Drainage)
Total amount of Sch 'A' Part-X : (Sewage Disposal)
Total amount of Sch 'A' Part-XI (Road/ Path/ Hardstanding )
Total amount of Sch 'A' Part-XII : (Lift)
Total amount of Sch 'A' Part-XIII(Demolition)
Sch 'A' Part- XIV : (Miscellaneous B/R & E/M Items (BOQ) (Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.)
Pile foundation on DMC pile in M35 concrete
Boring for cast-in-situ bored piles of 600mm dia to any depth through any type of soil/strata by DMC method using bentonite slurry including removal of bored materials to place outside MD land all as directed. Note: The rate shall include mobilisation, erection, dismantling and demobilisation of equipment for pile boring including all labours and material. Nothing extra shall be payable for mobilisation of equipment separately all as specified and shown on drawing.
Material and labour for RCC with ready mix concrete(RMC) M35 grade in cast in situ bored pile with minimum cement content 400kg/cum of any length/any sections complete all as specified and as shown on drg including non-destructive integrity test on all pile as per IS 2911-part IV all as specified and shown on drawing. Note:(i) Reinforcement will be measured and paid separately under relevant items.
Material and labour for RCC with ready mix concrete(RMC) M35 grade in pile cap, raft, grade/ grid beam & tie beam, foundation beam etc complete all as specified and shown on drawing Note: Reinforcement will be measured and paid separately under relevant items.
Material and labour for TMT bars (CRS/HCRM/CRM) in reinforcement 10mm dia and over for bored piles, grid beam, raft and pile cap of any length and any dia FE 500D grade all as shown on drawings including cut to length bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
Material and labour for TMT bars (CRS/HCRM/CRM) in reinforcement 5mm dia and over up to and including 10mm dia as in stiffeners and helical bars and geared beams FE 500D grade including cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
PCC (1:2:4) type B2 using 40mm graded stone aggregate for concrete layer below raft and foundation complete all as specified and shown on drgs.
M&L for providing 150mm thick stone dust layer in foundation, filling etc all as directed.
Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams, and similar work; vertical or to batter Flat Rough finished surfaces of concrete
Testing of piles (Initial Vertical Load Test) all as per IS including mobilizing and removing the testing equipment from site after testing is completed all as specified and directed for cast in situ 600 mm dia piles
Testing of piles (Initial Load Test) for Lateral Load Test all as per IS including mobilizing and removing the testing equipment from site after testing is completed all as specified and directed for 600mm, dia cast in situ pile.
Testing of piles (Routine Vertical Load Test) all as per IS including mobilizing and removing the testing equipment from site after testing is completed all as specified and directedfor cast in situ 600 mm dia piles
Testing of piles (Routine Load Test) for Lateral Load Test all as per IS including mobilizing and removing the testing equipment from site after testing is completed all as specified and directed for 600mm, dia cast in situ pile.
Internal water supply
S&F Chromium plated long body Bib Cock with wall flange and aerator make Jaquar CON-107 KN GA or equivalent in Marc or Kohler etc all as specified and directed.
S&F Chromium plated short Bib Cock Make Jaquar CON-047 KN GA or equivalent in Marc or Kohler etc. all as specified and directed.
S&F Chromium plated brass concealed stop cock heavy body with cap size 20mm Make Jaquar FUS-29139GA or equivalent in Marc or Kohler etc. all as specified and directed.
S&F Chromium plated brass Angle valve (Angle stop cock) Make Jaquar CON-059 KN GA or equivalent in Marc or Kohler etc. all as specified and directed.
Internal electric supply
M&L Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 1.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and sheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty steel conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 1.5 Sqmm nominal cross sectional area single core F.R.L.S cable as earth continuity conductor to common earth and connecting to earth dolly and cutting chases for steel conduits/ boxes etc complete all as specified and directed at site for the following:-
(a) One light point controlled by one 5/6 amps one way switch.
(b) One Ceiling fan point controlled by one 5/6 amps one way switch.
(c) One exhaust fan point controlled by one 5/6 amps one way switch.
(d) One Socket outlet, three/five pin, 5 Amp, independent controlled by one 5/6 amps one way switch or switch/socket combination 5 amps, 5 pin.
(e) One Socket outlet, three/five pin, 5 Amp, same board controlled by one 5/6 amps one way switch
(f) One light point controlled by 2 Nos, 2 Way switches 5/6 Amps.
Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 2.5 Sqmm nominal cross-sectional area, single core, PVC insulated and sheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty, steel conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) , including PVC insulated multi-stranded copper conductor 2.5 Sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly and cutting chases for steel conduits/ boxes etc complete all as specified and directed at site for the one 3/5 pin 15/16 amps socket outlet independent
M&L Modular Switch single pole, one way 6 Amps all as specified and directed
M&L Modular Switch single pole, two way 6 Amps all as specified and directed
M&L Modular Switch single pole, one way 16 Amps all as specified and directed
M&L Modular socket outlet 3 pin 5 Amps flush type all as specified and directed
M&L Modular socket outlet 2 in 1, 3 pin 6 and 16 Amps flush type all as specified and directed.
Supply and fixing Ceiling rose, three terminals,230V (ISI marked) surface bakelite suitable for batten fitting complete all as specified.
S&F modular electronic type fan regulator switch & step type 240 V, AC double mode all as specified and directed.
Supply and fixing ceiling fan 1200mm sweep copper wound having Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) as per IS 374:2019 including fixing of down rod and connecting up complete with and including three core flexible PVC insulated multi stranded copper conductor cable of size 0.5 Sq mm from connector to fan all as specified and directed.
Supply and fix exhaust fan made of sturdy engineering plastic complete with louvers shutter voltage 230V, 50 Hz, RPM 1200 of sweep 250mm complete including making necessary provisions for mounting on walls all as specified and directed.
Supply and fix exhaust fan made of sturdy engineering plastic complete with louvers shutter voltage 230V, 50 Hz, RPM 1200 of sweep 300mm complete including making necessary provisions for mounting on walls all as specified and directed.
S&F LED Tube light fitting 1X20 Watt 4' universal batten type with and including connecting 3 core 1sqmm PVC insulated multi stranded copper conductor's sleeve colour matching to fitting and connecting up complete all as specified and directed.
S&F LED Light fittings mirror type with high output diffuser 2 feet 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with 3 core multi stranded copper conductor's sleeve colour matching to fitting and connecting up complete all as specified and directed.
S&F LED Study Lamp wall mounting 1x9 watt 220 V AC with driver LED luminaire complete including connecting up with 3 core multi stranded copper conductor's sleeve colour matching to fitting and connecting up complete all as specified and directed.
S&F LED light 1X10 Watt 2' with and including connecting 3 core 1.0 Sqmm PVC insulated multi stranded copper conductor colour of sleeve matching to fitting and connecting up complete all as specified and directed.
S&F building LED security light 1x35W new generation energy saving and environmental friendly long life made of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP OPENING separate driver compartment with IP66 protection and impact resistance of IK 07 complete with and including wall mounted bracket fabricated out of 40mm GI pipe light grade bend to shape1.5 mtr long and two nos wall mounting clamps using 25x4mm thick MS strip bend to shape and welded with pipe to form solid structure and one run of 1sqmm PVC insulated multi stranded copper conductor wire connecting pvc terminal to fitting all as specified and directed.
Supply and fix LED bulk head fittings 10W with IP-65 protection suitable for surface and wall mounting applications complete all as specified and as directed by the Engineer-in-Charge.
Supply and fix Tele socket 1 module complete with GI metal flush box 1 or 2 module, inner & outer modular cover plate suitable for 1 module all as specified and directed.
S&F Sheet metal enclosure distribution board MCB DB SPN 6 way with metal double door 240 Volts with IP-43 protection including door earthing complete all as specified and directed.
S&F Sheet metal enclosure distribution board MCB DB SPN 8 way with metal double door 240 Volts with IP-43 protection including door earthing complete all as specified and directed.
S&F Sheet metal enclosure distribution board MCB DB SPN 12 way with metal double door 240 Volts with IP-43 protection including door earthing complete all as specified and directed.
S&F Sheet metal enclosure distribution board MCB DB TPN 4 way with metal double door 415 Volts with IP-43 protection including door earthing complete all as specified and directed.
S&F of RCBOs for earth leakage, overload and short circuit protection double pole 30mA 16 A all as specified and directed.
S&F of RCBOs for earth leakage, overload and short circuit protection four pole 30mA 40- 63 A all as specified and directed.
Taking down Service connection 2X6/2 X 10 Sqmm UG Cable complete all as specified and directed.
External water supply
Supply and lay CPVC shedule 80 pipe and plain schedule 80 fittings, 75mm inner dia all as specified and directed.
Supplying and laying of CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings 50 mm outer dia on walls/ceiling or laying in floors complete all as specified and directed.
Supply and fix Sluice Valves, flanged of class 1.6 PN, 150 mm dia (6" ) dia incl cap and hand wheel complete all as specified and directed.
Supply and fix Butter fly Valve of 150 mm dia all as specified and directed.
Supply and fix Butter fly Valve of 80 mm dia all as specified and directed.
Supply and fix non return sluice Valves of 80 mm dia all as specified and directed.
Supply and fix PPR Gate Valves (Brass insert) of 63 mm all as specified and directed.
Cutting existing 200 mm bore DI water mains and inserting Tee of size 200x200x150 mm dia or suitable sie for taking branch connection including all fittings and joints complete all as specified and as directed.
Supply and laying Ductile Iron pipes 150 mm dia centrifugally cast (spun), Class K-9, with spigot and socket ends conforming to IS 8329/2000 in any length suitable for push-on joints , laid in trenches complete all as specified and as directed.
Supply and laying Ductile Iron pipes 100 mm dia centrifugally cast (spun), Class K-9, with spigot and socket ends conforming to IS 8329/2000 in any length suitable for push-on joints , laid in trenches complete all as specified and as directed.
Supply and fixing DI fittings such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs suitable upto 150 mm dia, class K-12 complete all as specified and directed.
Supply and fixing DI fittings such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs suitable upto 100 mm dia, class K-12 complete all as specified and directed.
M & L for Construction of brick masonry valve chamber of internal dimensions 900 x 900 x 900 mm, bottom floor of the pit shall be constructed in PCC (1:3:6) 15 cm thick with 20 mm stone aggregate, inner and exposed surfaces and bottom floor of the pit should be plastered in CM (1:4) 15 mm thick. The top cover of the pit shall be made out of MS sheet min 3 mm thick with angle iron frame made out of MS angle 40 mm x 40 mm x 6 mm with 02 nos steel hinges and locking arrangements duly painted with two coats of synthetic enamel paint over one coat of red oxide primer all as shown in CE(NW) TD/A/169 sht 1/1 and as directed.
supply and install Pumping sets, centrifugal, electric driven , 63 M Head 925 LPM , ISI marked, including PCC foundation, adequate length of medium grade GI suction pipe, CI foot valve, air release cock, priming valve and suitable size 3 core armoured copper cable connection from motor to starter terminals complete all as specified and as directed.
S&F LT panel board cubicle type, indoor panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Copper bus bar of rating 200 Amps for phases & neutral mounted on porcelain/epoxy insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2 mm CRCA sheet duly powder coated after nine tank process. The panel shall be front openable type adequate space all around cessories such as LT switchgear and metering instruments including internal wiring in the panel with FRLS non flamable insulated multi stranded/ solid copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessories.
(i) INCOMING (a) MCCB 415 Volts,100 Amp rating 25 KA, 4 Pole . 1 Nos. (b) Digital volt meter -01 (c) Digital Ampere meter with and including CTs-01 No (d) Phase indicating lamp(set of 3). (II) OUTGOING (a) MCCB 415 Volts,63 Amp, 3 Pole, 25 KA - 02 No.; (b) 02 Nos automatic star delta starters (as per pump set capcity) (c) MCB SPN 16 Amps-2 Nos (d) Single phase preventor 2 Nos
Supply, Installation, Testing and Commissioning of indoor type power coated PLC (Programmable Logic Controller) based 2 Nos PUMP AUTOMATION PANEL Slave Monitoring / Annunciating Control Panel made out of 1.6mm thick CRCA sheet for control and monitoring of 20 Nos of Magnetic Level Sensor, 8 Nos of motorised valves.
The panel shall consist of the following equipments; (i) PLC with suitable Digital and analog Inputs / outputs, expansion modules, RTC . (ii) 4" LCD HMI (iii) Transformer with regulated output voltage of 230V +5%, (iv) SMPS of Suitable rating (v) Set of Control Relays and suitable MCB (vi) Audio visual generator (vii) Suitable No. of LED Indicators for easy visualisation (viii) Selecetor Swtiches (ix) Push Buttons / Illuminated Push Buttons (x) 0.5 sqmm multistrand internal wiring with ferruling and suitable lugs. (xi) Ethernet card (xii) Media Converter (xiii) Ethernet Switch (xiv) LIU(Light Interface Unit)box patch chord and mounting accessories with following specification. Communication: Primary- OFC, Stand by: GPRS Make of Control Panel: PSEC / JSP/RKOM/MARSH AUTOMATION
Up-gradation of the existing SCADA software to incorporate management and control of various OHTs and pump house , developing and adding the additional features as described below by altering the existing SCADA software a) Development of libraries and screens for display of the schematic of the remote motorized valves b) Creation of additional soft keys for remote / manual operation of the motorized valves in the OHTs. c) Modification of the Main SCADA screen to create a link to easily navigate to the newly developed OHTs and Pump schematic screen etc. as required. at Kataribag main pump house SCADA room all as specified and as directed.
Supply & fixing on wall/ laying in trench 2 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed.
Supply & fixing on wall/ laying in trench 4 x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed.
Supply & fixing on wall/ laying in trench 6x 1.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed. (for motorised valve)
Supply & fixing on wall/ laying in trench 5 pair 0.5 sq mm PVC sheathed and PVC insulated, armoured, FRLS, copper cable all as specified and as directed. (for magnetic senser)
Supply, Installation, Testing and Commissioning of Magnetic Level Sensor with the following specifications; Type: Magnetic Make : Rkom/JSP/PSEC
Supply and Laying / fixing on wall GI pipe light grade of 50 mm dia including all necessary fittings like nipples, bends, sockets, elbows etc. for cable protection all as specified and as directed.
Supply and Fixing UPS / Inverter along of capacity 1.0 KVA with suitable battery bank with weatherproof enclosure with locking arrangement complete including electric connection from tapping and to PLC based control panel with armoured copper wire. Note: i) The scope of work includes integrating the UPS with the PLC based Panel so as to ensure that the Motorised valves are functional even in case of a power failure for a minimum of 6 hours all as specified and as directed. Make: APC / Luminous / Numeric/ V Guard
Supply, Installation Testing & Commissioning of pressure Transmitter with following specification including necessary power pack for supply of DC : Power supply: 10-36 V DC Process connection: G ½ “ Enclosure: weather proof IP 65 Process temperature: -30 to 120 celcius Accuracy: 0.25 % Make: Danfoss / Siemens / E & H
Supply, Installation Testing & Commissioning of Solenoid valve Suitable for 25 mm pipe for priming of pump including all necessary GI fittings with following specifications: Size: 25 mm Pressure rating: 10 kg / sq. cm. Make for Valve: L&T / Honeywell / Siemens / Kirloskar / Schneider / Emtork.
Supply, Installation Testing & Commissioning of direct acting type release solenoid valve for air release during priming; with following specifications : Size: 10 mm Pressure rating: 10 kg / sq. cm. Type: Normally closed Make for Valve: L&T / Honeywell / Siemens / Kirloskar / Schneider / Emtork.
Supply, Installation Testing & Commissioning of Motor Actuated Butterfly Valve made of SS- 304 , stem material SS-410, EPDM seat in butterfly valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 50/65/80/100 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications & Features Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos.For open and close status Mounting :InDirect on valve Make for Actuator :Rotork / Honeywell / Rotex / Siemens/Schneider /Emtork (The torque of actuator shall be atleast 25% higher than the valve). Make for Valve: L&T / Honeywell / Siemens / Kirloskar / Schneider / Emtork.
Supply, Installation Testing & Commissioning of Motor Actuated Butterfly Valve made of SS- 304 , stem material SS-410, EPDM seat in butterfly valve consisiting of Quarter turn single phase Actuator and Wafer type butterfly valve of size 150 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications & Features Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating Limit Switches : 02 Nos.For open and close status Mounting :InDirect on valve Make for Actuator :Rotork / Honeywell / Rotex / Siemens/Schneider /Emtork (The torque of actuator shall be atleast 25% higher than the valve). Make for Valve: L&T / Honeywell / Siemens / Kirloskar / Schneider / Emtork.
External electric supply
Ring Main Unit indoor type 11 KV, 630 A, 20 KA, Motor operated, complact, both side extensible type, non drawout type, +CV+(01 No load breaker switch(OD) incommer and 01 No fixed type motor operated vaccum circuit breaker (VL) outgoing safeplus compact gas insulated ring main unit, all live parts enclosed in a robotically welded stailess stell tank of IP 67 class of protection with battery and battery charger including coupling accessories and extension of existing HT panel with necessary addition/alteration and providing additional busbar of suitable size complete all as specified and directed.
Supply, install, testing & commissioning of 11 KV, 630A, 21 KA 3 second, outdoor, both side extensible, non drawout type, fixed type motor operated Vaccum Circuit Breaker (1 No) with over load and earth fault protection, CTs, Battery and Battery Charger, compact gas insulated ring main unit all live parts enclosed in a robotically welded stainless steel tank of IP 67 class of protection with necessary arrangements / module attachements of OEM for incoming cable connection and outgoing cable connection (Two bottom cable entry) including foundation, including extention of existing HT panel and including foundation near VCB/RMU. Make : should be the same make of the existing panel or suitabe for extending the existing panel in the make of list.
Supply, install, testing and commissioning distribution transformer of capacity 400 KVA step down, outdoor type ( mounted on PCC plinth) complete with standard fittings, HT 11 KV 3 phase, LT 433 volts, 3 phase 4 wire with off load tappings on HT side to vary secondary voltage, as per IS 1180:2014 level - 2 including comprising of following (a) No load voltage ratio 11 KV/433V (b) Vector Group DYN 11 (c) core type copper wound (d) temperature rise 45/50 degree centigrade (oil / winding) (e) tap changer on HT side with + 7.5% in steps of 2.5% each (f) cable end box on HT and LT side to accommodate cables (g) conservator with drain valve (h) explosion vent with diaphram and sighting glass (j) air release plug (k) earthing terminals 02 Nos for body and 02 Nos for neutral (l) lifting lugs (m) flanged rollers (n) silica gel breather with transparent body and oil seal (o) radiator with top and bottom shut off brass gate valves (p) brass/ gun metal drain valve (q) first filling of transformer oil at desired level (r) cooling ONAN (s) inspection cover (t) danger notice board (u) cable entry box (v) Bucholz relay and marshelling box with OTI & WTI complete with all necessary control cables connections up to VCB, necessary civil works for making foundation for transformer mounting etc complete all as specified and as directed. Note: Transformer HT Cable/LT Cable to be drawn through suitable GI grade pipe with supporting structure
Supply,laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 volts grade Earthed with stranded aluminium conductor of size 185 Sq.mm 3 core
Supply, install, testing and commissioning of factory made out door type LT Panel, double door, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Aluminium bus bar of rating of 1200 Amps for phases and suitable Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 3 mm CRCA sheet duly powder coated after seven tank process including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties (Main LT panel)
Supply, install, testing and commissioning of factory made out door type pedestal, LT panel board cubicle type double door suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Aluminium bus bar of rating of 200 Amps for phases and 200 Amps for neutral fixed on porcelain insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 3.0 mm CRCA sheet duly powder coated after seven tank process . The panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties :Essential panel
Supply, install, testing and commissioning of factory made indoor type, pedestal / floor mounted LT panel board cubicle type suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Aluminium bus bar of rating 400 Amps for phases and 400 Amps for neutral fixed on porcelain/ epoxy insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties :-(Location: Building panel- 1&2)
Supply, install, testing and commissioning of factory made indoor type, pedestal / floor mounted LT panel board cubicle type suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Aluminium bus bar of rating 100 Amps for phases and 100 Amps for neutral fixed on porcelain/ epoxy insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2.0 mm CRCA sheet duly powder coated after seven tank process and MS angle iron frame work. the panel shall be both front and back openable type adequate space all around acessories sucxh as LT switchgear and measuring instruments on both sides including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessorties :-(Location: Building Essential panel )
Supply and install hot dip galvanised octagonal poles of height 7 Mtr with 1 mtr single arm bracket 40 mm dia for fixing of street light fitting with camauflaged weather proof junction box with MCB SP 6 Amps, electrical control gears,inside cable termination and earth connection. Pole top dia shall be 70 mm and bottom dia 130 mm,sheet thickness 3 mm and base plate dimension 225x225x12 mm incl foundation bolts alll as specified and directed.
Supply and fix LED Street light 35 W IP 65 for street lights fitted on the octagonal poles arm brackets all as directed.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm all as specified and directed.
Supply and fixing of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm all as specified and directed.
Supply and fixing of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm all as specified and directed.
M & L 100 mm bore High density polyethylene pipes (HDPE) PN 10 laid in trenches/Wall/road crossing for suitable length as per sire requirement all as specified.
Supply and spread riddled soil in trenches for cable cushioning by using IS sieve to seperate the composite particle and refilling in trenches as cushioning and rammed down to form a solid bed all as specified and directed. Note : Punned thickness shall be measured for payment purpose.The mesh of the screen through which the soil is riddled shall not exceed 12.5 mm IS sieve.
Supply and laying cables in trenches, or fixing on walls or passing through cable duct / pipe XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavyduty) with aluminium conductor, 11000 volts, grade having cross sectional area 3 core 185 sqmm all as directed.
Supply and fixing , cable straight through jointing kit for 1.1 KV (Earthed) grade cable, heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 sqmm to 240 sqmm all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fixing , cable straight through jointing kit for 1.1 KV (Earthed) grade cable, heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 to 95 sqmm all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fixing , cable straight through jointing kit for 1.1 KV (Earthed) grade cable, heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fixing , cable straight through jointing kit for 1.1 KV (Earthed) grade cable, heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 50 sqmm all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fixing , cable straight through jointing kit for 1.1 KV (Earthed) grade cable, heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 35 sqmm all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fixing , cable straight through jointing kit for 1.1 KV (Earthed) grade cable, heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 10 to 25 sqmm all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fixing of HT/LT Cable route indicators of material Cast iron incl PCC foundation (1:3:6) type C1 all as directed
Taking down old HT 11 KV XLPE UG Cable of any size from existing location and making good of existing surface after removing old cable including Earth work such as Excavation, Returning filling during taking down and making good of existing surface after removing old cable all as specified and as directed.
Taking down old LT 1.1 KV XLPE UG Cable of any size from existing location and making good of existing surface after removing old cable including Earth work such as Excavation, Returning filling during taking down and making good of existing surface after removing old cable all as specified and as directed.
M & L for Relaying old HT cable (removed from SI.No.139 above of any depth carefully) in new route all as directed by Engineer-in-charge. Note:- (a) Earth work will be measured and paid separately. (b) Any damage to the cable caused during the earth work is complete responsibility of the contractor and to be repaired at his own cost.
M & L for Relaying old LT cable (removed from SI.No.140 above of any depth carefully) in new route all as directed by Engineer-in-charge. Note:- (a) Earth work will be measured and paid separately. (b) Any damage to the cable caused during the earth work is complete responsibility of the contractor and to be repaired at his own cost.
Cutting into existing bituminous carpet road/PCC hard standing/tiles for laying of pipes/UG cables, re filling, ramming and making good the disturbed surfaces replacing road with cold bitumen mix/new PCC hard standing/new tiles to match with the existing complete all as directed.
Fire fighting
Supply and fixing MS pipe heavy duty 100 mm dia in any lengths with all fittings like elbow, Tee, flange, short piece, nut, bolt, gasket etc. including fixed on walls floors/roof etc by providing fixing arrangement by means of suitable MS clamps and welding of pipes andduly paintedwith two coats approved synthetic enamel paint fire red colour over one coat of zinc chromateprimer complete all as specified and directed.
Supply and fixing MS pipe heavy duty 150 mm dia in any lengths with all fittings like elbow, Tee, flange, short piece, nut, bolt, gasket etc. including fixed on walls floors/roof etc by providing fixing arrangement by means of suitable MS clamps and welding of pipes and duly paintedwith two coats approved synthetic enamel paint fire red colour over one coat of zinc chromate primer/ polythene based coating and wrapping when laid in ground complete all as specified and directed.
Supply and fix fabricated hose cabinet of size 800x600x250 mm wall mounted type made out of 18 guage MS steel sheet with double door with 4 mm thick glasses and door frame made of 16 guage MS sheet painted fire red colour outside and brilliant white inside with mechanical locking arrangement suitable for internal/ inside yard use complete all as specified and directed.
Supply and fix synthetic reinforced rubber cotton synthetic fibre circular oven jacketed fire delivery hose 63 mm dia treated against rot/moistex having 30 Kg/cm2 working pressure bearing IS 636 - 68 type A 15 Mtrs length with Gun metal male and female coupling conforming to IS 903 complete all as specified and directed.
Supply and fix hose reel swinging wall mounted type comprising rubber hose 19/20mm dia 30m long high pressure double braided bearing IS-5132 type `A' 5mm bore shut off nozzle of stainless steel and 25mm gun metal inlet valve conforming to IS-884 and connected to down comer complete all as specified and directed.
Supply & fix landing valve single headed gun metal bearing ISI marke grade 63 mm female instantaneous outlet complete wit PVC blank cap and chain and having suitable flanger for 100 mm dia wet riser complete all as specified and directed.
Supply and fix gun metal branch pipe 63 mm dia male instanteneous inlet threaded outlet fitted with hexagonal based nozzle of 12.5 mm dia heavy duty conforming to IS-903 complete all as specified and directed.
Supply and fix 100 mm bore hand operated CI butterfly valve (ISI maked) of pressure not less than 15 KG/Cm2 complete with fixing arrangement by providing gasket, nut, bolts and washers etc complete all as specified and directed.
Supply and fix 150 mm bore hand operated CI butterfly valve (ISI maked) of pressure not less than 15 KG/Cm2 complete with fixing arrangement by providing gasket, nut, bolts and washers etc complete all as specified and directed.
Supply and fix 150 mm bore CI Non return valve (dual plate) complete with fixing arrangement by providing gasket, nut, bolts and washers etc complete all as specified and directed.
M & L Gun metal fire brigade in let connection 2 way complete with fixing arrangement by providing gasket, nut, bolts and washers etc complete all as specified and directed
Supply and fix CI valve, reflux 100 mm (4") dia complete with fixing arrangement by providing gasket, nut, bolts and washers etc complete all as specified and directed
Supply and fix pressure switch universal type all as specified and directed
Supply and fix pressure guage 100 mm dia with ball valves of pressure 0-14 Kg/cm² rating all as specified and directed
Supply, install, commissioning and testing of single loop addressable type fire alarm control panel with 99 detectors and 99 modules complying with BS EN 54 and up to 200 detectors and modules per loop, the panel is to be installed and commissioning with all necessary wiring, connections, testing etc. The panel is to be installed in non air conditioned environment. The equipment shall be suitable for the atmosphere with humid condition all as specified and directed.
Supply, install, commissioning and testing of Addressable type manual call point re-settable type with relay module incl all acessories like junction box, glands etc all as specified and directed.
Supply and fix Addressable electronic sounder cum strobe all as specified and directed.
S&F of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI 32 X 6 MM strip all as specified and directed.
S&F of Tubes, 'light grade' galvanised, with all fitting and fixed complete tin trenches, walls and ceilings or laid in floors of size 40 mm dia all as specified and directed.
Supply, installation, testing & commissioning fire pump with common base frame(fabricated mild steel channel frame or cast iron type) placed on RCC 1:2:4 type B1 including foundation bolt and nut, including foot valve, air release cock, priming valve, armoured copper cable from pump to panel through PVC conduit electrically driven horizontal end suction, centrifugal type confirming to IS- 12469 :1988 with CI Casing , bronze impeller and Stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with 'range of operation' 0 % to 150 % of rated capacity for 440 V, 3 Phase. 50 Hz 70 mtr head, 2850 LPM discharge all as specified and directed
Supply, install, testing & commissioning Jockey pump with common base frame(fabricated mild steel channel frame or cast iron type) placed on RCC 1:2:4 type B1 including foundation bolt and nut, including foot valve, air release cock, priming valve, armoured copper cable from pump to panel through PVC conduit horizontal end suction centrifugal type Confirming to IS- 12469: 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for automatic operation with nonover loading power characteristics for frequent start / stop operations for 440 V , 3 phase, 50 Hz 70 m head 180 LPM discharge all as specified and directed
Supply, install, testing & commissioning Fire pump diesel engine driven horizontal end suction, centrifugal type confirming to IS- 12469 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with 'range of operation' 0 % to 150 % of rated capacity for 440 V , 3 phase, 50 Hz AC supply 70 mtr head, 2850 LPM discharge Including diesel tank of capacity suitable for 90HP pump with common base frame(fabricated mild steel channel frame or cast iron type) placed on RCC 1:2:4 type B1 including foundation bolt and nut, including foot valve, air release cock, priming valve, armored copper cable from pump to panel through PVC conduit all as specified and directed
Fabricate, supply and connect air cushion tank (air vessel) 250mm dia 1000 mm height with dished top made out of 6mm thick MS plate suitable for floor mounting including 01 No 20 mm dia wet riser including GI Tee of size 100 x 100 x 20 mm and drain valve 20mm dia all as specified and directed
Supply, install, testing & commissioning booster pumps for 440 V, 3 Phase, 50 Hz Confirming to IS- 12469 :1988 With CI Casing bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 440 volts, 3 phase, 50 Hz 36 mtr head, 450 LPM discharge all as specified and directed
Supply, laying and testing of Flanged type Ductile Iron pipes 150 mm dia centrifugally cast (spun), Class K-9, with flanged ends conforming to IS 8329, in any lengths laid in trenches complete all as specified and as directed.
Supply and fix synthetic reinforced rubber cotton synthetic fibre circular oven jacketed fire delivery hose 63 mm dia treated against rot/moistex having 30 Kg/cm2 working pressure bearing IS 636 - 68 type A 30 Mtrs length with Gun metal male and female coupling conforming to IS 903 complete all as specified and directed.
Supply and fix automatic spring loaded gunmetal air release valve 50 mm dia complete all as specified and directed
Supply, lay, testing and commisioning of flexible 2 core 1.5 sqmm copper conductor, pvc insulated ,cross laid up,overall aluminium Mylar tape shielded along with ATC drain wire PVC Outer sheated cable laid in existing complete as required and as directed (for MCP) all as specified and directed.
S&F wall mounted LED emergency Exit signage luminaire Lit up using regular mains supply comes with a unique rechargeable Ni-Cd battery capable of emergency back up upto 05 hours all as specified and directed.
Supply and installation, testing and commissioning of Analog Addressable type Active Loop Repeater (Loop power/external power) Fire terminal with inbuit turbo isolator, Backlit LCD Display 6x40 characters display,having Controls For Reset, Mute, Accept , Silence alarms and Self Test, with programmable free keys and Duly Approved by EN54/LPCB/VDS/FM , all as specified and directed .
Earthing for Ext water supply, Ext elect, Lightening Protection, Fire fighting, Lift and DG set
M &L for earthing complete with galvanised steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by alternate layer of common salt and charcoal 15 cm thick, connected to and including galvanised iron earth lead 32x6 mm GI strip by means of bolts, nuts, check nuts and washers of galvanised iron or steel and earth strip protected by GI pipe 40 mm dia light grade and connected from earth plate electrode to main switch board/ earthing test point or upto 7.5 mtr whichever is less including watering arrangement using 20mm GI pipe light grade, MS funnel with wire mesh, PCC chamber pit in PCC 1:3:6 type C-1, 40 mm thick pre-cast RCC cover re-inforced with 8mm dia TMT bars @ 10cm C/C on both sides and handle, excavation and earth work in any type of soil and removal upto 50 mtr complete including mentioning of earth value & name of earth pit cover with paint and handle shall be above chequered tiles. all as specified and shown in electrical plate No 03 of SSR Part-I, all as specified and directed including testing on completion.
Aviation obstruction light
Supply and fix avaition obstruction light LED type comprising of aluminium housing with polycarbonate enclosure (Make Bajaj Cat No BGAV 302 LED or equivalent) all as specified and as directed.
S&F sheet metal enclosure for MCB DB SPN 2 way, single door, 240 volts without bus bar all as specified and as directed.
Supply and fix MCB SPN 6 Amps, 10 KA, 'C' curve all as specified and as directed.
Supply, laying and testing cable XLPE insulated , screened, PVC bedded galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 6 Sqmm 2 core all as specified and as directed.
DG Set
Supply ,installation ,testing &commissioning , Out door type, Accoustic enclosed silent type diesel engine driven generating set comprising of capacity 125 KVA / 100 KW, 415 volts, 3 phase 4 wire, 1500 RPM 0.8 Power factor, 50 Hz directly coupled with diesel engine capable of taking 10% overload for one hour for every 12 hours (as per BS-5514/649) coupled directly to alternator mounted on a rigid bed plate with suitable acoustic enclosure as per latest CPCB IV norms and complete with standard control panel ,battery and battery lead and fuel tank of suitable capacity with flexible coupling mounted on common base plate on vibration pads , foundation as recommended by manufacturer including AMF panel alongwith connected accessories with relay panel for automatic starting on main electric supply failure, control panel having meters, AVR control excitation. Genset Controller consists of Engine parameters like R.P.M, Liquid / Cylinder Temperature, Oil Pressure, Fuel level indication, Engine Hours run & Alternator parameters like Voltage, Frequency, Amps, KW, KVAR, PF etc. The DG set shall comprise of electric starter motor, turbo charger, water cooled and comprising all standard fittings/fixtures, first fill of Lube oil, coolent, fuel for testing and all piping etc as below:-
Alternator :- self - excited, self- regulated, screen protected, drip proof alternator with static excitation system, capable of developing rated output at 415V, 0.8 p.f, 50Hz when running at 1500 RPM ,3 ph in SPDP enclosure at tropical conditons and conforms to the IS 4722 standards, BS EN 60034-1 Acoustic Enclosure :- Acoustic enclosure is of modular construction,industrial locking sytem is provided,shall be polyster based powder coated and fabricated as per CPCB-IV+ norms as amended upto date, sound level 75 dB (A) at 1 mtr from enclosure in free field conditions as per ISO 8528 part 10 AMF PANEL : OEM factory made, out door type ,double door, cubicle made micro processor based AMF panel shall be with AMF controller suitable to start the engine on main failure after 10-15 second time delay and to switch off engine only after 60-90 seconds after the main supply restored. The AMF controller shall have under/ over voltage, over load protection, coolant temp cut off, fuel control upto 10% tank capacity. Amf panel including all relays and suitable rated four pole power contactors and complete electrical connections and control wirings comprising the followings also.
Note : The following are included in the scope of work :- (a) The panel will be complete with internal wiring with suitable size of multi stranded copper cable. The suitable control of AMF panel with all meters, control wires. (b) Tools as supplied by the manufacturer (c) Fuel tank shall be provided inside canopy (d) thermostat switch inside the acoustic enclosure shall be provided to shut off the DG set incase of temperature increases beyond its rated temperature inside the acoustic enclosure (e) there shall be proper air circulation and windows with glass in the acoustic enclosure suitably located to read the meters of various controls from outside (f) Necessary grouting including mild steel work and anti vibration pad shall be provided (g) necessary foundation of installation and plinth protection of the DG set shall be provided as per manufactuers recommendation (h) necessary 10% overload test shall be carried out in the presence of testing officer nominated by Accepting Officer. (j) Shifting of DG set from showroom/factory to the site by means of truck/crane is the responsibility of the contractor.
Water cooler
Supply and fix water cooler electric driven (single phase), having approx storage capacity of 40 litre and nominal cooling capacity of 40 Litres per hour with Microprocessor based ozone venturi purification all as specified and directed By Engr-in-charge.
Supply and fixing Voltage stabilizer for auto operation ,single phase ,naturally air cooled indoor type and designed for input variation between 170V to 250V with out put voltage stablizer at 230V with accuracy with in +/- 2.5% and speed of corrrection 8 volts per second and of capacity 2.0 KVA capacity all as specified and as directed. Make : V-Guard or equivalent
Designing, supply, erecting, commissioning and testing of STP of capacity 130 KL per day including tertiary treatment capable of treating raw sewage of characteristics as per Appx `A' in to treated water suitable for Arboriculture all as per Col 4 Appx `B' of E-in-C's Branch MES New Delhi letter No 86435/Misc/E4 (U) dt 19 May 2017, consisting of all Civil, Mechanical & Electrical work based on principle of aerobic attached growth non clogging randomly Moving Bed Bio-reactor (MBBR) having capacity 130 KLD, including required foundations and the following as per the specifications given in particular specification. Rate quoted shall deemed to be included for all the accessories and equipments mentioned aganist item 1.1 to 1.20 & Note below.
One no. Fine bar screen of MSEP construction as per given minimum specifications, to be installed in Fine Bar screen chambers at an angle of 60° to prevent floating objects passing through it and subsequently removing manually and dumped for further disposal.
One lot of air grid for equalization tank for providing aeration in the tank, as specified in PS
Two nos. raw sewage pumps complete with motor and all necessary accessories and fittings, to be installed for transferring sewage from equalization tank to process. Level sensor should be provided in the tank and interlinked with pumps for ON-OFF operation as per water level in the tank. One pressure gauge for each pump has to be provided to measure pressure at the outlet
Two nos. Twin lobe Air blower complete with motor and all necessary accessories & fittings, for providing air in equalization tank, MBBR reactors & Sludge holding tank. One no. Air rotameter is to be provided in each line to MBBR reactor 1 & 2/ EQT for measurement of quantity of air.
One Anoxic Chamber in MS FRP construction with Mixer.
Two Set of MBBR tank in MS FRP construction with all internals comprising of media, SS air grid & SS rise pipe, media retaining sieves, etc
One Set of Tube settler tank in MS FRP construction with all internals comprising of media, supporting structure & collection trough.
Two nos. sewage centrifugal monobloc self priming sludge transfer pumps complete with motor and timer based operation for set time after every set interval of time, with all necessary accessories and fittings for transferring sludge from bottom of the Tube settler to the sludge bag unit. One pressuregauge for each pump has to be provided to measure pressure at the outlet.
One no. Chlorine Contact cum Filter feed tank in MS FRP construction as per given specifications.
One set of chlorine dosing system comprising of solution tank and dosing pumps, as specified in PS, with necessary connection for dosing of solution in chlorine contact tank.
Two nos. filter feed centrifugal monobloc pumps complete with motor and all necessary accessories and fittings for feeding tertiary unit, Level sensor should be provided in the chlorine contact cum filter feed tank and interlinked with pumps for ON OFF operation as per level in the sump. One pressure gauge for each pump has to be provided to measure pressure at the outlet.
One no. Dual Media filter complete with media, frontal piping, valve and pressure gauges to measure pressure across the filter.
One no. Activated Carbon Filter complete with media, frontal piping, valve and pressure gauges to measure pressure across the filter.
One lot of suitable size Piping & valves of suitable material to interconnect various units as per site layout
One lot of Power & control cables to interconnect various drives and instrumentations with STP panel.
One no. Fine Bar screen chamber cum collection chamber of suitable capacity in RCC construction with design mix concrete of grade M-30, to be constructed below ground for fine Bar screen, as per given specifications
One no. Oil & Grease removal chamber in RCC construction with design mix concrete of grade M-30, to be constructed below ground, as per given specifications.
One no. Equalisation tank in RCC construction with design mix concrete of grade M-30, to be constructed below ground, as per given specifications, to cater for the peak discharge including provision of diffused air to ensure that septic conditions do not occur in tank at all.
One lot of foundations in PCC for all E&M equipment, as required
NOTE: Rate quoted against item No 105 above shall deemed to be included for the following:-
STP system followed by Supervisory control and data acquisition (SCADA) and Automation including OCEMS technology in sewage treatment schemes vide letter NoA/95533/SCADA Sewage/Pol/E2W(PPC) dt 210Jul 2023 (a) SCADA and Automation in Sewage Treatment system (b)Software Management ©Particular Specification and Tendering for SCADA,Automation and its O&M. (d)Training of MES perosonnel and Quality Assurance
(i). Installation, commissioning & testing of the complete package type STP of capacity 130 Cum per day including any item which is essential for satisfactory working of the STP but either not mentioned here-in-before or capacity, rating, Nos of items are not correctly mentioned here-in-before.
(ii).Before commence of work contractor shall submit Design & layout plan from reputed OEM and duly vetted from IIT / NIT for approval of Accepting Officer.
(iii).All civil mechanical,electrical work shall be carried out as per relevant BIS/IS equivalent standard norms only and also in accordance with the latest edition of Indian electricity act/ rules formed there under and as amended from time to time.Any other works( civil mechanical and electrical) connected to installation,testing functional requirement of package type STP of capacity 130 cum per day all as mentioned above and which is not mentioned or included in this schedule but necessary shall be carried out by contractor against the rate quoted for item number 183 above.
(iv).Yardstick for payment shall be approved by accepting officer (based on this schedule and rates given by the contractor).
(v).Entire plant shall be tested after successful commissioning by rep of accepting officer and contractor Shall make all arrangement without extra cost.
(vi).Contractor shall arrange training of MES staff for operating of this STP without extra cost
(vii) All consumables including chemicals required for testing commissioning will be supplied by the contractor for this item and rate is deemed to be included in the rate quoted.
(viii) Rate included for electrical wiring for control panel to pump sets everything etc.
(ix) Contractor shall obtain Consent to operation clearance from Kerala Polution Control Board and Annual fee required for the same shall be deemed to be included in the rate quoted STP
(x) Contractor shall collect sample in presence of GE for inlet raw sewage of characteristics all as directed by GE and design of the STP accordingly. The inlet parameters given in Appx 'A' is tentative and minimum.
(xi) Pressure gauges, electromagnetic flow meter,level control switch,liquid buoyancy, air rotometer etc as required at site for auto functioning of STP.
(xii) A lot of piping for inter connection all as recommended by OEM
(xix) Input / Output Modules consist of a) Standard rack mounted I/O modules with plug-in cards shall be provided. Field wiring shall be terminated in screwed terminal and interconnected to the processor I/O system with pre-fabricated cables with plug-in type connectors. b) 20% extra points of installed capacity for each type of input shall be provided as spares and shall be wired to the terminal block of the control panel. Provision shall be made for future expansion of extra I/O modules. c) Some of the common features of the I/O modules shall be as follows : i. All inputs shall be terminated with input protective network and necessary isolation barriers. ii. Filters for noise rejection. iii. Provision for isolation of faulty channels. iv. Protection for continuous overload up to 200% of all input ranges. v. Test points and fault indication LEDs shall be provided to carry out module testing. vi. Surge withstands facility as per IEEE standards. vii. All the modules shall be of addressable type. viii. Fuse protection and fuse failure detection. ix. Internal battery backup.
Supply and laying Ductile Iron pipes 150 mm dia centrifugally cast (spun), Class K-9, with spigot and socket ends conforming to IS 8329/2000 in any length suitable for tyton / push-on joints , laid in trenches complete all as specified and as directed.(Ref site plan drg STP plant)
Material and labour for cutting/ breaking of cement concrete or bituminous road/ hard standing of any thickness with or without reinforcement for laying up/down of DI pipes and connection making good all distributed surfaces by using cold bituminous mix up to existing ground level (Irrelevant of depth of existing ground level) all as specified and directed.
S&F 3- layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain & brass threaded polypropylene random fittings laid in trenches-50mm Outer diameter all as specified and directed.
All as per item No 223 but of 25 mm dia all as specified and directed.
Supplying and laying of CPVC Schedule 80 pipes & plain CPVC Schedule 80 fittings 75 mm inner dia all as specified and directed.
Supplying and laying of CPVC Schedule 80 pipes & plain CPVC Schedule 80 fittings 62.5 mm inner dia all as specified and directed.
supply, install and testing Pumping sets 3HP,230V single phase, centrifugal, electric driven suction head 80mm and delivery head 65 mm, complete including suitable capacity of DOL Stater with suitable enclosure with connected circuit, mounted on wall and PCC foundation (for pumping treated water 2 pumpset) all as specified and directed.
S&F Non clog vertical submersible pumps of capacity 5 HP with chrome steel impeller and cutter, non-clog to pass 50 mm size particles including supply, installation with guide rail and lifting chain, cables, earthing, testing complete with 2 years maintenance ( Flow and head= 700 lpm x 40 M) all as specified and directed.
S&F LT panel board cubicle type, indoor panel board suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with air insulated PVC sleeved with heat shrink of colour code on Aluminium bus bar of rating 200 Amps for phases & neutral mounted on porcelain/epoxy insulators. The panel shall be weather proof, dust and vermin proof IP-54 class protection and fabricated out of 2 mm CRCA sheet duly powder coated after nine tank process. The panel shall be front openable type adequate space all around cessories such as LT switchgear and metering instruments including internal wiring in the panel with FRLS non flamable insulated multi stranded/ solid copper conductor cable 1100 Volt grade IS 694 marked or PVC sleeved copper strips of appropriate size as per standard is practices and comprising of followings acessories (Non Clog Pumps) all as specified and directed.
(i) INCOMING (a) MCCB 415 Volts,100 Amp rating 25 KA, 4 Pole . 1 Nos. (b) Digital volt meter -01 (c) Digital Ampere meter with and including CTs-01 No (d) Phase indicating lamp(set of 3). (II) OUTGOING (a) MCB TP 415 Volts,63 Amp, 3 Pole, 25 KA - 03 No.; (b) 03 Nos DOL starters (as per pump set capcity) (c) MCB SPN 16 Amps-2 Nos (d) Single phase preventor 3 Nos
Supply and fix Gun metal gate valve 50mm bore with iron wheel head, screwed both ends all as specified and directed.
Arboriculture
Supply only moorum for filling using moorum brought from out side MD land for forming embankments including raising or lowering spreading in layers n exc 30 cm thick watering and finishing to required size and shape n exc 1.5 m height from base complete all as specified and as directed.
Labour only for mixing, spreading, levelling, watering approved earth and sand in required proportion in layers not exceeding 25cm thick as directed for planting of grass including supply and mixing of 0.50 kg/Sqm of cow dung, 0.25 Kg/Sqm of powdered coco peat, 0.25 Kg/Sqm of powdered bone meal and 15 mg/sqm of insecticides complete all as specified and as directed.
Supply and planting red palm sapling having 45 cm height including excavation of pits of size 30cmx30cmx30cm in loose soil ,supply and filling the pit with mixture of approved earth and river sand in the proportion of 1:3 by volume, supply and mixed with 1 Kg cowdung powder, 100 g bone meal and 10 g of insecticide (furadan) and removal of excavated soil to a distance n exc 50 m complete all as specified and as directed.
Supply and planting flower plants sapling having 10 cm minimum height (Plant should be of Dahlia, Anthurium Red, Priyathams rose nine, Cineraria etc) including excavation of pits of size 30cmx30cmx30cm in loose soil ,supply and filling the pit with mixture of approved earth and river sand in the proportion of 1:3 by volume, supply and mixed with 1 kg cowdung powder, 100 g bone meal and 10 g of insecticide (furadan) and removal of excavated soil to a distance n exc 50 m complete all as specified and as directed.
Supply and planting coloured flower plants sapling having 15 to 30 cm height(Plant should be of Dracena flower, Phyllanthus, Aster Formula (mixed) etc including excavation of pits of size 30cmx30cmx30cm in loose soil ,supply and filling the pit with mixture of approved earth and river sand in the proportion of 1:3 by volume, supply and mixed with 1 kg cowdung powder, 100 g bone meal and 10 g of insecticide (furadan) and removal of excavated soil to a distance n exc 50 m complete all as specified and as directed.
Supply and planting flower plants sapling having 15 to 30 cm height, Song of India including excavation of pits of size 30cmx30cmx30cm in loose soil ,supply and filling the pit with mixture of approved earth and river sand in the proportion of 1:3 by volume, supply and mixed with 1 kg cowdung powder, 100 g bone meal and 10 g of insecticide (furadan) and removal of excavated soil to a distance n exc 50 m complete all as specified and as directed.
Supply and planting buffalo grass complete all as specified and directed.
COMPREHENSIVE MAINTENANCE OF LIFTS AFTER DEFECT LIABILITY PERIOD
Note :- (a) Replacement of sheeve and steel ropes, if required during this period, will be carried out by the contractor but material shall be provided by the department for fixing only. (b) :- The comprehensive maintenance shall be done through OEM of the lift. (c) :- The Contractor shall enter into an MOU (Memorandum of Understanding) with the OEM or their authorised agency for maintenance of the lift. The above comprehensive AMC certificate shall be provided by the Contractor in favour of GE (NW) before commencement of work, after acceptance of CA. (d) :- The parts shall be genuine and shall be from original equipment manufacturer (OEM) and shall be approved by GE. (e) :- All stainless steel parts such as lift car enclosure, opening doors, jamps, cills etc shall be thoroughly cleaned to remove rust, stains etc with suitable solution. The Contrator shall also be clean and properly maintain machine rooms, machineries and lift well as directed by EIC. The rates quoted for respective items shall be deemed to include for the same. (f) :- No spare parts and consumables shall be supplied by the Department. (g) :- The rate of maintenance, service and repair including all the material and labour for the satisfactory functioning of the lifts.
All as per Item No 241 here-in-before but for the second year after completion of defect laibility period.
All as per Item No 241 here-in-before but for the third year after completion of defect laibility period.
C S CONSTRUCTION COMPANY PVT. LTD. (BID ID -3355106)
Mecone Construction Contractors (BID ID -3359672)
Sri Avantika Contractors (I) Limited (BID ID -3355019)
PUSHKARRAJ CONSTRUCTION PRIVATE LIMITED (BID ID -3358690)
REPLAJCC JV (BID ID -3355751)
CHERIAN VARKEY CONSTRUCTION CO PVT LTD (BID ID -3356096)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid