SE, Central Electrical Circle, PWD
Office of the SUPERINTENDING ENGINEER, Central Electrical Circle 184, C.R.Das Road, Berhampore, Murshidabad, PIN-742101
Proposed G3 Construction of Mother and Child Hub at Anupnagar Block PHC in the district of Murshidabad Fire Detection System
2019_WBPWD_262937_1
WBPWD/CEC/NIT/39/Q/19-20
Open Tender
FIRE FIGHTING ORG
Item Rate
45 days
Murshidabad
Please refer Tender documents.
5 documents required · 5 mandatory
₹30,000
Berhampore
20 Sept 2020
30 Dec 2019
28 Jan 2020
31 Dec 2019
27 Jan 2020
8 Jan 2020
6 Jan 2020
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, addressable 6 Loops fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable with each loop capable of taking minimum 120 devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. ( Approved Make: Esser/Cerberus Pro/Secutron/ Securiton/ Notifer / Edward / Bosch / Apollo / Morley / System Sensor / Johnson Controls ).
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with two inbuilt optical smoke sensors with backward & forward scattering light angles as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supplying, installation, testing and commissioning of Addressable Heat Detector (Fixed temperature cum rate of rise) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost)...(Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Addressable transponder/ Monitor Modules ( VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply, Installation, Testing & Commissioning of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required.
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe(Make: Precision/AKG/ATUL/VIP/Universal/BEC/Polypack) on the surface of the wall.
Supply and Fixing of 19mm PVC Conduit complete with all accessories (Make:-precision-Medium/Polycab-M)
Supply and fixing of 20 mm GI conduit complete with all accessories (Make:-Jindal, Bansal)
TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
Terms and condition The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect liability period - 5 year after commissioning
GLYPTIC
Greentech Solution
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .