| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.5 LAccepted-AOC 7 32 1 PRASANTHI NAGAR GOPALAPATNAM VISAKHAPATNAM 530 027 | VISAKHAPATANAM | ANDHRA PRADESH | 530027 | L1 | Accepted-AOC Being Lowest Vendor | |
| 2 | L2₹39.9 L+₹5.4 L (15.7%)Rejected-Finance | L2 | Rejected-Finance Being Not L1 | |
| 3 | L3₹40.1 L+₹5.6 L (16.4%)Rejected-Finance | L3 | Rejected-Finance Being Not L1 | |
| 4 | L4₹40.3 L+₹5.8 L (16.9%)Rejected-Finance | L4 | Rejected-Finance Being Not L1 |
| Sl No | Description | Qty | Unit | MVV Prasad L1 | TETRI ENTERPRISES L4 | R AND A ASSOCIATES ENGINEERS CONTRACTORS L2 | Aziz Traders L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Material and labour for repair, servicing of automatic power factor corrction panel of capacity 100 kVAr to 400 kVAr taking out all doors covers from front and rear. Servicing comprising of thorough cleaning of complete inside cabinet with forced air and suitable cleaning agent, removing all dust/dirt, cleaning and servicing of all HRC fuses, contactors, AC input circuit breaker, all types of meter, indicator lamps, MCBs, PCBs, busbars, switchgears, automatic all cable terminals with CTC and clean dry cloth, cleaning of outside surface and dry cloth, tightening of all nuts, bolts & washers. Repair comprising of replacement of burnt copper cable lugs, burnt switchgear, non-functional capacitor , non-functional indicator lamps, | 7 | Each Job | 5,500 ₹38,500 | 2,000 ₹14,000 Lowest | 2,000 ₹14,000 Lowest | 2,000 ₹14,000 Lowest |
| 1.01nonfunctional contacts/fuses, damaged panel metering wirings, nonfunctional selector switches, damaged panel door/cover knobs & door locks, damaged door hinges. and testing of power factor as desired 0.9 at verious sub stations as follow all as specified and directed. Make of APFC panel Neptune Only Note:- Material shall be measured and paid separately as supply only items. Materials shall be recommended make of Neptune/ABB/L&T/schneider only | |||||||
| 2.00 | Supply only LTXL capacitor power heavy duty 10 kVAr 415 volts 50 Hz all as specified and directed. | 4 | Each | 5,897 ₹23,588 | 2,250 ₹9,000 Lowest | 3,100 ₹12,400 | 2,250 ₹9,000 Lowest |
| 3.00 | Supply only LTXL capacitor power heavy duty 20 kVAr 415 volts 50 Hz all as specified and directed. | 12 | Each | 12,525 ₹1,50,300 | 4,320 ₹51,840 Lowest | 6,500 ₹78,000 | 4,320 ₹51,840 Lowest |
| 4.00 | Supply only LTXL capacitor power heavy duty 25 kVAr 415 volts 50 Hz all as specified and directed. | 10 | Each | 15,904 ₹1,59,040 | 5,400 ₹54,000 Lowest | 8,500 ₹85,000 | 5,400 ₹54,000 Lowest |
| 5.00 | Supply only LTXL capacitor power heavy duty 40 kVAr 415 volts 50 Hz all as specified and directed. | 4 | Each | 26,046 ₹1,04,184 | 8,640 ₹34,560 Lowest | 12,500 ₹50,000 | 8,640 ₹34,560 Lowest |
| 6.00 | Supply only LTXL capacitor power heavy duty 50 kVAr 415 volts 50 Hz all as specified and directed. | 4 | Each | 19,000 ₹76,000 | 10,800 ₹43,200 Lowest | 15,000 ₹60,000 | 10,800 ₹43,200 Lowest |
| 7.00 | Supply only Capacitor microf 4.17 kVAr overpressure disconnector all as specified and directed | 15 | Each | 1,500 ₹22,500 | 450 ₹6,750 Lowest | 4,000 ₹60,000 | 450 ₹6,750 Lowest |
| 8.00 | Supply only Contact (Make ABB UA 30-30-10RA) ll as specified and directed | 8 | Each | 3,300 ₹26,400 | 900 ₹7,200 Lowest | 6,000 ₹48,000 | 900 ₹7,200 Lowest |
| 9.00 | Supply only HBC fuse link model No. ISHTIS0063(A3) make Standard 63 Amps 415 Volts 50 Hz 80 kA suitable for 125 kVAr capacitor bank Make Standard ll as specified and directed | 12 | Each | 2,200 ₹26,400 | 95 ₹1,140 Lowest | 800 ₹9,600 | 95 ₹1,140 Lowest |
Tender Value
₹41.0 L
EMD Value
₹81,900
Closing Date
23 Dec 2024, 6:00 pmClosed
GE (I) DM, Visakhapatnam
GE (I) DM, Visakhapatnam
SERVICING, REPAIR AND PERIODICAL MAINTENANCE OF LT APFC PANELS AND ALLIED WORKS AT VARIOUS SUBSTATIONS AT NAVAL DOCKYARD, VISAKHAPATNAM UNDER GE (I) DM VISAKHAPATNAM
2024_MES_655540_3
8041/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naval Dockyard Visakhapatnam
As per tender documents
8 documents required · 8 mandatory
₹500
GE (I) DM, Visakhapatnam
₹81,900
Yes
23 Sept 2026
26 Nov 2024
25 Dec 2024
26 Nov 2024
23 Dec 2024
3 Dec 2024
Amount
Material and labour for repair, servicing of automatic power factor corrction panel of capacity 100 kVAr to 400 kVAr taking out all doors covers from front and rear. Servicing comprising of thorough cleaning of complete inside cabinet with forced air and suitable cleaning agent, removing all dust/dirt, cleaning and servicing of all HRC fuses, contactors, AC input circuit breaker, all types of meter, indicator lamps, MCBs, PCBs, busbars, switchgears, automatic all cable terminals with CTC and clean dry cloth, cleaning of outside surface and dry cloth, tightening of all nuts, bolts & washers. Repair comprising of replacement of burnt copper cable lugs, burnt switchgear, non-functional capacitor , non-functional indicator lamps,
Supply only LTXL capacitor power heavy duty 10 kVAr 415 volts 50 Hz all as specified and directed.
Supply only LTXL capacitor power heavy duty 20 kVAr 415 volts 50 Hz all as specified and directed.
Supply only LTXL capacitor power heavy duty 25 kVAr 415 volts 50 Hz all as specified and directed.
Supply only LTXL capacitor power heavy duty 40 kVAr 415 volts 50 Hz all as specified and directed.
Supply only LTXL capacitor power heavy duty 50 kVAr 415 volts 50 Hz all as specified and directed.
Supply only Capacitor microf 4.17 kVAr overpressure disconnector all as specified and directed
Supply only Contact (Make ABB UA 30-30-10RA) ll as specified and directed
Supply only HBC fuse link model No. ISHTIS0063(A3) make Standard 63 Amps 415 Volts 50 Hz 80 kA suitable for 125 kVAr capacitor bank Make Standard ll as specified and directed
Supply only APFC relay advance range VPL06N all as specified and directed
Supply only (reactive power management) Relay automatic C/k setting of over voltage, over compensation, make Neptune RM-8 for 125 kVAr capacitor bank all as specified and directed
Supply only indication lamp for Phases (RYB) all as specified and directed
Supply only indication lamp (Red) for 25 kVAr capacitor bank all as specified and directed
Supply only indication lamp (Green) for start suitabnle for 125 kVAr capacitor bank ll as specified and directed
Supply only indication lamp (red) for stop suitable for 125 kVAr capacitor bank II all as specified and directed.
Supply only Ameter meter make Neptune all as specified and directed
Supply only tharmostate all as specified and directed
Supply only contactors Telemecooique LC1 D.K all as specified and directed
Supply only HRC fuse HN size 160 Amps 415 volts 100 kA all as specified and directed. Make :- L&T
Supply only metering current transformer of 630/5 Amps for RYB phase all all as specified and directed.
Supply only Contact 32 Amps Telemecanique LC1-DGK11.C 32 Amps model A012851 make Schneider electric all as specified and directed
Supply only Contact 80 Amps Telemecanique LC1-DGK11.C 32 Amps model A012851 make Schneider electric all as specified and directed
Supply only Contact 60 Amps Telemecanique LC1-DGK11.C 32 Amps model A012851 make Schneider electric all as specified and directed
Supply only Space heater 415/220 volt suitable for 100 to 500 kVAr capacitor bank all as specified and directed
Supply only (reactive power management) Relay suitable for automatic C/k setting controll of over voltage compensation insufficient compensation 200 kVAr capacitor bank make & model Schneider electric Varlogic RT-8 all as specified and directed
Supply only HBC back up protection by suitable HRC fuse units along with HRC fuse 6 Amps alll as specified and directed. Make :- Standard
Supply only MCB Tp D-50 all as specified and directed. Make :- Schneider
Supply only MCB Tp D- 25 all as specified and directed. Make :- Schneider
Taking down old one and Supply, installation, testing and commissioning of floor mounted cubical/trunk type indoor made out of 2 mm thick CRCA steel sheet chemically threated and powder coated, prewired, factory made , dust and vermin proof, double door with wather proof rubber gaskets and with Godrej type lock, cable gland etc. and consisting of the following all as specified and directed (a) Electrolytic aluminium bas bar of capacity 800 Amps for phases and 400 Amps for neutral . (b) ACB 630 Amps 50 kA mauual draw out type -01 No (incoming). (c) MCCB 4 pole 315 Amps rating, 35 kA breaking capacity with adjustable thermal & adjustable magnetic setting- 02 Nos. (d) MCCB 4 pole 200 Amps rating 35 kA breaking capacity with adjustable thermal & adjustable magnetic setting-01. Nos.
Supply and fix Air circuit Breaker (ACB) 4 pole 415 volt, with thermal magnetic release mannual draout type of capacity 1600 Amps 50 kA including required necessary addition/altration all as specified and directed Make- Schneider Cat no MVS16N4MW6Lor equivalent to L&T/Indo Asian
All as per item No. 31 above, but capacity of 1250 Amps all as specified and directed. Make- Schneider Cat No. MDO MYS12N44MW6L or equivalent to L&T/Indo Asian
Supply, install, test and commissioning MCCB with fixed thermal maganetic relase for 415 V, 50 Hz AC supply of 400 Amp, 4 pole 50 KA rated capacity by taking out old unserviceable MCCB's all as specified and directed. Make : Make : Indo Asian /L&T/ABB
All as per item No 33 above, but of capacity 250 Amps, breaking capacity 36 kA
All as per item No 33 above, but of capacity 200 Amps, breaking capacity 36 kA
All as per item No 33 above, but of capacity 160 Amps, breaking capacity 16 kA
All as per item No 33 above, but of capacity 25 TO 100 Amps 3 POLE , breaking capacity 16 kA
(ix) -ditto- but for 20 Amps - 03 Nos (x) -ditto- but for 16 Amps - 02 Nos (xi) Power contactors suitable for 25 KVAR capacitor bank -02 Nos (xii) -ditto- but for 20 KVAR - 04 Nos (xiii) -ditto- but for 15 KVAR - 02 Nos (xiv) -ditto- but for 10 KVAR - 03 Nos (xv) -ditto- but for 5 KVAR - 02 Nos (xvi) Switch fuse unit 315 TPN 415 V, with HRC fuses -01 Set
(ix) -ditto- but for 20 Amps - 01 No (x) -ditto- but for 16 Amps - 04 Nos (xi) Power contactors suitable for 25 KVAR capacitor bank -01 No (xii) -ditto- but for 20 KVAR - 01 No (xiii) -ditto- but for 15 KVAR - 01 No (xiv) -ditto- but for 10 KVAR - 02 Nos (xv) -ditto- but for 5 KVAR - 04 Nos (xvi) Switch fuse unit 315 TPN 415 V, with HRC fuses -01 Set
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 240 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 300 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 400 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
M & L for Earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised iron strip 32 x 6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical Plate No. 2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2 with RCC precast pit cover slab 80mm thick with handle for lifting made out of 8mm dia MS rod, Funnel with watering pipe, wiremesh, charcoal and salt in alternate 150mm thick layers around earth plate including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion after dismentling taking out unserviceable one complete all as specified and directed.
R AND A ASSOCIATES ENGINEERS CONTRACTORS (BID ID -3195717)
Aziz Traders (BID ID -3187450)
TETRI ENTERPRISES (BID ID -3192883)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
Tender Document • 0.30 MB
8041TENDER.pdf
Tender Document • 0.97 MB
BOQ_745979.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .