Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
3 Jul 2020, 6:00 pmClosed
GE AF AMBALA
GE AF AMBALA
GE AF/AMB-19/2020-21 MANNING AND OPERATION OF 66KV SUB-STATION, MAFI SUB-STATION NOS. 1 AND 2 INCLUDING MISCELLANEOUS E/M WORKS IN TECHNICAL AREA AT AF STATION AMBALA UNDER GE AF AMBALA
2020_MES_352655_1
GE AF/AMB-19/2020-21
Open Tender
Civil Works
Item Rate
330 days
GE AF AMBALA
ALL AS PER TENDER DOCUMENTS
9 documents required · 9 mandatory
₹500
Yes
GE AF AMBALA
₹99,000
Yes
30 Jul 2020
13 Jun 2020
6 Jul 2020
13 Jun 2020
3 Jul 2020
27 Jun 2020
Amount
Manning & Operation of 66KV grid sub-station (comprising of different equipments viz. VCBs, transformer, SF6, LT panels, battery bank, isolators, etc.) in 66KV yard and control room with 66KV incoming and 11KV outgoing supply by providing 01 (one) qualified Diploma holder (with minimum 5years experience) in 03 (three) shifts of 8hours each (round the clock 24hrsx3 shifts = 3 Diploma holders) on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge
Manning & Operation of 66KV grid sub-station (comprising of different equipments viz. VCBs, transformer, SF6, LT panels, battery bank, isolators, etc.) in 66KV yard and control room with 66KV incoming and 11KV outgoing supply by providing 01 (one) qualified ITI holder (with minimum 2years experience) in 03 (three) shifts of 8hours each (round the clock 24hrsx3 shifts = 3 ITI holders) on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge
Manning & maintenance of 66KV grid sub-station, yard and control room with 66KV incoming and 11KV outgoing supply by providing 01 (one) male helper / mazdoor in 01 (one) shift of 8hours each (0900 to 1700hrs) on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge
Manning & Operation of MAFI sub-station 1 (PS-1) (comprising of different equipments) with 11KV incoming and 11KV/415V outgoing supply by providing 01 (one) qualified ITI holder (with minimum 2years experience) in 03 (three) shifts of 8hours each (round the clock 24hrsx3 shifts = 3 ITI holders) on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge
Manning & Operation of MAFI sub-station 2 (PS-2) (comprising of different equipments) with 11KV incoming and 11KV/415V outgoing supply including 160kVA DG set by providing 01 (one) qualified ITI holder (with minimum 2years experience) in 03 (three) shifts of 8hours each (round the clock 24hrsx3 shifts = 3 ITI holders) on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge
Manning & Operation of 601SU sub-station (comprising of different equipments) with 11KV incoming and 11KV/415V outgoing supply by providing 01 (one) qualified ITI holder (with minimum 2years experience) in 03 (three) shifts of 8hours each (round the clock 24hrsx3 shifts = 3 ITI holders) on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge
Manning & Operation of NGLGK substation with 1No. DG set 250kV including operation of LT panels, AMF panels by providing 01 (one) skilled ITI/FGM, in 02 (two) shifts of 8hours each (0800 to 1600hrs & 1600hrs to 2400hrs) = 2 ITI/FGMs on all days including Sundays and holidays complete all as specified, detailed hereinafter and as directed by the Engineer-in-charge .
Notes for serial item Nos. 1 to 7: (i) The timings for each shift shall be as decided by the Engineer-in-charge. No claim whatsoever on this aspect is admissible (ii) The minimum wages as derived by the Deartment including all statutory provision such as ESIC, Bonus, GST, taxes, etc. except the Contractor's profit for skilled person works out to Rs. 762/-per person per shift and for un-skilled person Rs. 597/- per person per shift (iii) Bidder has to upload an signed undertaking in firm's letter head confirming that he has not quoted his rates lower than the derived minimum rates of the Department. Bids not accompanied with such undertaking shall not qualify for opening of the price bids. As applicable, his tender will be treated as 'NON BONAFIDE' if found at any stage and will not be considered for acceptance. In such case, the lowest tender shall be determined by the lowest amount amongst valid / bonafide bids only.
(iii) However increased minimum fair wages as notified time to time by the Government of India / State Government / Local bodies / Labour Regulations whichever is higher including all statutory provisions such as EPF, ESI, Bonus, taxes, etc. as applicable, irrespective of derived minimum wages as above (v) Increased wages including all other benefits in compliance of statutory provisions shall be paid to the workers by the Contractor. No other claim whatsoever shall be admissible on this account and the bidders shall note this aspect and quote their rates accordingly. It must be noted that in compliance of all statutory provisions, the increase shall be passed over to the workers
Notes for serial item Nos. 4 to 7: (i) The operator placed shall be responsible to attent all complaints of LT/HT OH/UG lines, LT panels, VBCs, DG set, transformers, etc. concerned to the location as directed (ii) Conveyance/vehicle for moving around of the staff employed on such occassions shall be provided by the Contractor (iii) A penalty of Rs. 500/- per complaint shall be imposed on non-attending of such complaints as directed. Such penalties shall be recovered immediately from corrosponding RARs/FB of the Contractor. Notes for item No. 6: (i) The skilled trade men/electricians will be fully reponsible to attend all the complaint of electric of LT/HT OH/UG cables/ LT Panels/VCB/ DG set panel/VCB/Transformers, etc. repair of street lights of any type of 601SU/BD-III and 702SU. (ii) The skilled tradesmen / electricians will also be fully responsible to attend fault of HT OH line/under ground cable from ESC power house to 601SU sub station including minor item like siutable rating drop out fuse, jumpers, HT insulators (pin/disc type), required T&P (iii) The convenyance/ two wheeler will be arranged by the Contractor for to attending to complaints. In the event of the complaint remaining pending for more than 3hrs a penalty of Rs. 500/- per complaint will be imposed and this will be decided by the Engineer-in-Charge and his decision will be final and binding. In case of disputes the same shall be referred to the GE and his decision then will be binding and conclusive.
M&L for servicing & calibrating damaged / faulty (overload current/ earth fault, etc.) VCBs of any make, at site on location, immediately on situation of any fault, and restoring funcionality with and including replacing of minor parts viz. HRC fuses, indicator lamps, control wiring, etc. oiling, greasing, cleaning with blower from inner and outer sides, decarburizing of the links with CRC spray, etc. checking serviceability complete all as specified and as directed Notes: (i) Work of overhauling, servicing, testing, etc. shall be got done through Engineer/ Technician of manufacturer (ii) Overhauling & servicing shall be done to the tune of complete serviceability / functionality of the VCB (iii) All costs of technician/Engineer on hire, minor spares, any sort of conveyance of man and material, testing & calibrating equipment, etc. shall be deemed to be included in the quoted rate (iv) The job shall be done in periodicity of 6 months, i.e. 1st servicing shall be done within 3 months from the date of commencement of work
Supply, install, testing and commissioning 66kV class station heavy duty metal oxide gapless type LA for use with effective ground natural system with insulating base including surge monitors for 66kV with all accessories meeting and catering the requirement detailed as under complete all as specified and as directed (a) Nominal system voltage- 66kV (rms) (b) Highest system voltage - 72.5kV (rms) (c) MCOV 52kV (d) Nominal discharge current- 10KAP (e) Line discharge- Class 3 (f) High current discharge- 100KAP (g) Maximum residual voltage- 165KVP at 01KAP
Supply and filling up power transformer oil as per IS-335 suitable for 66KV transmission system including draining out and disposing off used oil complete all as specified and as directed Notes: (a) The Contractor shall produce necessary PVs and TCs from the manufacturer (b) Sample of sealed drum oil shall be got tested from state laboratry for tests as required for EHT system (c) The quoted rate shall be deemed to be inclusive of the above
S&F in repairs energy meter (WH meter) of 66KV C&R panel flush type digital and testing on installation complete all as specified and as directed
S&F in repairs voltmeter of 66KV C&R panel flush type digital meter and testing on installation complete all as specified and as directed
S&F in repairs DPR relay REL -511 suitable for 66KV and testing on installation complete all as specified and as directed
S&F in repairs male female contacts with set of isolators or earth line switches of 66KV capacity including aligning and testing complete all as specified and as directed
S&F battery maintenance free, 180AH 12V, set including initial charging, filling of distilled water, etc. including connecting lead and testing on installation and disposing off old battery complete all as specified and as directed
S&F in repairs battery charger 24V 50Hz charging range 6 to 24volt with trickle / boost charging mode with ammeter and voltmeter complete all as specified and as directed
Supply only silica gel in 5/10kg sealed packets complete all as specified
M&L for 11KV cluster with metal part, ampere rating suitable for existing VCB as per existing model, make and type including taking out old / unserviceable clusters and disposing off complete all as specified and as directed complete
S&F in repairs TNC switch as per existing make and specifications suitable for VCB 1250Amps, 11KV including all neccesarry connections and testing complete all as specified and as directed
S&F in repairs closing coil assembly as per existing make and specifications suitable for VCB 1250Amps, 11KV including all neccesarry connections and testing complete all as specified and as directed
S&F in repairs tripping coil assembly as per existing make and specifications suitable for VCB 1250Amps, 11KV including all neccesarry connections and testing complete all as specified and as directed
S&F in repairs digital ammeter with shunt suitable for VCB 11000V, 1250Amps including all neccesarry connections and testing complete all as specified and as directed
S&F in repairs digital frequency meter with shunt suitable for VCB 11000V,1250Amps including all neccesarry connections and testing complete all as specified and as directed
S&F in repairs master relay for VCB tripping system parallely to 3OC + 01 earth fault and high set instantaneous protection in single unit suitable for operation on 24V DC as per existing model including all necessary modification in the wiring and panel sheet enclosure, etc. as required complete all as specified and as directed
S&F in repairs epoxy resin cast CT dual core of ratio as per existing accuracy class 0.55, burden 200/100/05VA suitable for 11KV complete all as specified and as directed
Supplying, laying, jointing, testing & commissioning HT 11 KV (E) XLPE insulated cable, 3 core 240sqmm, sound compacted aluminium conductor, screened with extruded semi conducting layer, insulation screening with copper tape cover laid up with PVC (ST-2) extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7096 part-II with amendment, laid in pipes/ducts/along poles/wall/equipment, etc. including taking down old unserviceable cable / OH conductor complete all as specified and as directed
M&L for cable jointing kit for 11kV earthed grade cable for straight through heat shrink type joint with jointing material and accessories suitable for 3 core, 185 to 300mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed
M&L for cable jointing kit for 11kV earthed grade cable for straight through heat shrink type joint with jointing material and accessories suitable for 3 core, 95 to 120mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed
M&L for cable jointing kit, indoor termination type, for 11kV earthed grade cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, 95 to 120mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed
M&L for cable jointing kit, outdoor termination type, for 11kV earthed grade cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, 95 to 120mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed
M&L for cable jointing kit, indoor/outdoor termination type, for 11kV earthed grade cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core, 185 to 300mm², XLPE insulated armoured aluminium conductor cable including taking out and disposing off old joint complete all as specified and as directed
M&L for cutting of grass, small trees of girth upto 10cm, shrubs, bushes, etc. cleaning the entire area near fencing, main entrances, etc. including clearing off the premises and removing cut vegetation complete all as specified and as directed
M&L for spraying with suitable sprayers natural herbicides / chemicals viz. glyphosate, dicholorophenoxyacetic to stop / restrict grass and vegetative growth around installation, etc. complete all as specified and as directed
S&F in repairs IDMT relay with numerical relay for VCB tripping system for E/F (10% to 400% in step of 1%), O/C (1% to 20% in step of 1%), having ability to record 20 to 30 fault records and 200 to 250 events records with modbus protocol for communication operated on 24V DC/110V AC all as per per existing complete all as specified and as directed Note: Existing relays are IDMT electromagnetic type hence any modification in the wiring and panel sheet enclosure shall be done to get system operational. Cost for all such aspects shall be deemed to be included in the quoted rate
S&F lightening arrestor, expulsion type, 15KA discharge capacity transmission class, suitable for 11KV system including staging as required, testing on installation including taking down and disposing of old / damaged arrestors complete all as specified and as directed
M&L for servicing isolator or earth line switch including oiling, greasing, aligning, etc. complete all as specified and as directed
M&L for servicing, testing of oil temperature trip circuit of the power transformer 6.30/8MVA complete all as specified and as directed Note: (a) Work of servicing, testing, etc. shall be got done through Engineer/ Technician of manufacturer (b) All tests to prove functionality shall be got done from authorised testing agencies (c) Any testing equipment, etc. required shall be provided by the Contractor (d) Quoted rate shall be deemed to be inclusive of the same
M&L for servicing C&R (Control and Relay Panel) including checking the control wiring and maintaining it in control room and 66KV yard including marshelling box 200 TB (MK 03Nos) and all control panels of CT/PT/SF-06/Isolator /earth line switch, etc. complete all as specified and as directed Note: (a) All tests to prove functionality shall be got done from authorised testing agencies (b) Any testing equipment, etc. required shall be provided by the Contractor (c) Quoted rate shall be deemed to be inclusive of the same
M&L for calibrating and servicing SF-6 circuit breaker CBDC fail trip test of SF-6 breaker and making the CBDC tripping system serviceable, spring charge mechanism of SF-6 breaker of 66KV complete all as specified and as directed Notes: (i) Work of overhauling, servicing, testing, etc. shall be got done through Engineer/ Technician of manufacturer (ii) Overhauling & servicing shall be done to the tune of complete serviceability / functionality (iii) All costs of technician/Engineer on hire, minor spares, any sort of conveyance of man and material, testing & calibrating equipment, etc. shall be deemed to be included in the quoted rate (iv) The job shall be done in periodicity of 6 months, i.e. 1st servicing shall be done within 3 months from the date of commencement of work
M&L for servicing of ACB in 66KV sub-station, MAFI S/S and ESC power house including oiling, greasing, cleaning with blower from inner and outer sides,decarburizing of the links with CRC spray and checking serviceability of all mechanical parts and ensuring full serviceability complete all as specified and as directed Notes: (i) Work of overhauling, servicing, testing, etc. shall be got done through Engineer/ Technician of manufacturer. Overhauling & servicing shall be done to the tune of complete serviceability / functionality of the ACB (ii) All costs of technician/Engineer on hire, minor spares, any sort of conveyance of man and material, testing & calibrating equipment, etc. shall be deemed to be included in the quoted rate (iii) The job shall be done in periodicity of 6 months, i.e. 1st servicing shall be done within 3 months from the date of commencement of work
M&L for disconnecting electric connection of underground HT, XLPE cable, 11KV, 95sqmm to 300sqmm from both sides and locating faults therein with modern fault locating / detector machine/equipment in the entire length, removing moisture from HT cable charging the HT cable by expert technicians and reconnecting and commissioing and testing of cable complete all as specified and as dirtected Note: Work will be executed after obtaining proper shutdown from main power house with all safety measures as per requirements. Prior intimation for the same shall be given and permission shall be obtained from the Engineer-in-charge
Raman Electric Trading Co
R D Bansal
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .