REPAIR/MAINT OF HT ELECTRIC SUPPLY NETWORK AND MISC WORKS AT YOL CANTT
2022_MES_552465_1
CWE/Y-52/2022-23
Open Tender
Civil Works
Item Rate
180 days
YOL
AS PER NIT
9 documents required · 9 mandatory
₹500
Yes
GE (KH) YOL
₹30,000
Yes
25 Nov 2022
16 Sept 2022
17 Oct 2022
16 Sept 2022
15 Oct 2022
1 Oct 2022
Amount
Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 Sqm on plan and not exceeding 1.5 mtr in depth and getting out in any type of soil, complete all as specified and directed.
All as per Srl Item No 1.00 above but depth exceeding 1.5 mtr and not exceeding 3.0 mtr.
Returning filling in (soil) including spreading, levelling, watering and well ramming in layers n.exc 25cms thick in any type of soil complete all as specified and directed.
Removing excavated materials/ soils, not exceeding 50mtrs and depositing where directed at a level not exceeding 1.50mtrs, complete all as specified and directed.
PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed.
PCC 1:4:8 (nominal mix) type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed.
Plain cement concrete 1:2:4 ( nominal mix ) type B-1 (using 20 mm graded crushed stone aggregates) as in in lintels upto 1.5m clear span, cills, steps; seismic and other similar ands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs , water troughs and the like including weathering, slightly rounded or chamfered angles and throating, including necessary formwork where required complete all as specified and directed.
Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cms thick, complete all as specified and directed Note: Punned thickness shall be measured.
Sub class ‘B brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick including taking out old bricks, complete all as specified and directed.
Laying only retrived bricks as cable protection cover, laid dry, flat, transversally along the length of cable, on sand cushioning, with width equal to the length of the brick, complete all as specified and directed.
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 80mm size fixed with MS clamps, nuts and bolts as required including cutting of road or hardstanding by manual complete all as specified and directed.
Supply, jointing, fixing or passing through pipe, trenches or ducts, commissioning and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (Heavy duty) with aluminium conductor, 11000 Volts grade, cross sectional area 95Sqmm, 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part-2 for insulation and for conductors Class 2 to IS 8130-84, in trenches, floors, ducts passing through pipe for road crossing etc,including connecting & testing and disconnecting and taking down of old unserviceable HT cable complete all as specified and directed. (Note : Excavation, earth work, brick protection, sand cushioning and GI pipe etc shall be measured &paid for separately).
Material and labour for servicing /testing and calibration of breaker/control panel including CT, PT and relays in control panel of VCB of capacity 630/800 Amps and rating 11 KV complete as details mentioned as under:- (a) Details of servicing of breaker :- (i) Adjustment of mechanism if required. (ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth. (iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts. (iv) Check for rust and wear. (v) Check Spring Tension and pitting of the Cluster Contacts. (vi) Visual check for rust and deformation. (vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc. (viii) Check for loosened connections, rust, damaged lead wires. (ix) Check whether the contacts are damaged by arcing. (x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil. (xii) Checking of Jaw Contacts Conditions and repair/adjust. (xiii) Replace the jaw contacts,If required. (xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish. (xv) Replacement of Dashpot/shock absorbers . (xvi) Replacement of carbon brush of spring charging motor
(b) The following test shall be carried out:- (i) Primary Injection Test of CT / PT (ii) Closing & Opening Timing Test for all three poles. (iii) IR Test with megger in open and closed condition. (iv) Contact resistance test for all three poles (v) Closing coil resistance (vi) Tripping coil resistance. (c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :- (i) Over current and earth fault relay (d) Testing of followig Aux relay (i) DC Supply supervision relay. (ii) Master trip relay Note:- Test report shall be laminated to control panel of respective breaker.
Supply and fix in replacement of unservicable relay any type and make with Numerical relay microprocesser based model including retrofiting to the existing panels and programming the relays for overlaod and earthfault setting with respect to trip settings of HT panels installed at Power House 33KV/11KV Sub station in such a way that fault are arrested locally complete all as specified and directed.
HRC fuse of rating 2 to 6 Amp any type to suit existing system complete all as specified and directed.
Supply and fix including Taking down Epoxy/ resin cast CT of dual core dual ratio 100-50/5+5A with 5 P 10 for protection and class-I accuracy having 15 VA burden complete all as specified and directed.
Supply and fixing in replacement of Vacuum interrupter 630 A suitable for existing HT VCB complete all as specified and directed.
Supply and fixing in replacement of Trip coil with plunger with working voltage 24 volts DC suitable for existing panel complete all as specified and directed.
Supply and fixing in replacement of Closing coil with working voltage 24 volts DC suitable for existing panel complete all as specified and directed.
Supply and fixing in replacement of Auxilliary contact of suitable for existing VCBs complete all as required or directed.
Supply and fixing in replacement of Isolating contact suitable for existing VCBs complete all as specified and directed.
Supply and fixing in replacement of Charging Spring motar of VCB trolley complete all as specified and directed.
Supply and fixing in replacement of Motor with gear assembly for spring mechanism charging suitable for HT VCB any make and type complete all as specified and directed. Make of Motor :Bosch or recommended by manufacturer
Taking down old UNSV insulator and Supply and fixing in replacement Epoxy resin cast insulator suitable for 11 KV VCB of Complete in all respect all as specified and directed
Testing of tripping mechanism and callibration of over current and earth fault IDMT/Numerical relay of HT 11KV rating VCB through primary & secondary injection machine and placement of setting data on a laminated print stickers on the VCB complete all as directed by Engr-in-Charge.
Material and labour for servicing of battery charger system installed at Main power house for 12 Nos 2 volt battery each (12 Nos x 2 volts = 24 volts) used for proper funcitoning of relays.Removing all electrical and control coneection and up to existing socket for charging and DC Supply to existing VCBs up to 12 Nos and the connection of incoming and outgoing battery bank to VCBs will be made including replacement of supply and fixing of 4 nos 24 volt battery by stranded copper conductor size not less than 2.5 sqmm for each core in case of multi core cable or single core cable PVC inculated unsheathed cable duly drean into medium grade PVC condult on floor/wall making proper functional and as directed by Engr - in - charge.
M & L for Butane Gas net weight not les than 250 Grams bottle and pressure 0.2 MPa for purpose of removing of moiture from RMU and PSS all as specified & directed by Engr-in-Charge.
Supply only insulation Tape for HT for (electro maintenance and protection) , each peice 5 mtr long complete all as specified and as directed in Engr-in Charge
Material and labour for detection of any type of fault in HT underground Line (laid in soil at plane area or forest area) with the help of Cable fault locator machine. Cable fault locator with carring vehicle will be brought by the cable fault detection agencies. faulty cable will be trace out by the agencies by meggering HT cable.
Renewal of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm with suitable clamps made out of flat iron 50X6mm including nuts, bolts and washers, complete all as specified.
Renewal of cable jointing kit for 11 KV (Earthed) grade cable for straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, complete all as specified.
Renewal of cable jointing kit for 11 KV (Earthed) grade cable for straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm, complete all as specified.
Supply, installation, testing and commissioning gang operated air break off load connecting switch HT, 11KV, tripple pole, each plate consisting galvanised steel base, verticle type mounted on 15 No's post insulators and steel frame, non ferrous knife and spring loaded contacts, arcing horns complete with dropout fuse element assembly, operating rod of GI pipe, medium grade, 20 mm dia (without joint) of suitable size and locking arrangement, connections, mild steel frame with PG clamps and sleeves etc required for current rating 200 amps capacity including taking down unservicable GOD of any type, shape & size with steel frame and removing from site all as specified and directed.
Steel tubular swaged poles complete with base plate 8mm thick welded with pole, finial taper plug, bolt, nut and screws as specified type 410 SP-55 (11m long) including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with yellow and black paint alternately on external surface above PCC benching including numbering with black paint and painting with bituminous paint internally complete and externally for portion embedded in PCC including dismantling of old type of poles any length, complete all as specified and directed. Note:- Earth work & excavation and PCC shall be measured and paid under respective Items of BOQ.
Galvanized steel wire 4mm dia for earth wire/ guard wire onHT/ LT poles stretched without kinks, bend and binding with wire including fabrication of cradles hexagonal/ rectangular guards, spacers, road crossing etc., including taking down old wire of any type shape , size and removing from site, complete all as specified & directed .
Renewal of disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, 'Two-in-series' assembly for tension with tension clamps for conductors working pressure 11000 Volts complete all as specified and directed.
Supply and fixing of Male Contact / moving contact blade with arching horn having brass contacts suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing on post insulator or any other indicated situation all as required at site or directed by Engr In charge. Make : Jaipuria brothers/Rashtriya/BHEL
Supply and fixing of Female contact spring loaded having brass contacts suitable for 11 KV GOD, including galvanised iron bolts, nuts and washers for fixing on post insulator or any other indicated situation all as required at site or directed by Engr In charge. Make : Jaipuria brothers/Rashtriya/BHEL
Trimming up of tree branches upto 3 mtr all around HT overhead lines, removing cut branches from site as directed, Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 3 mtr all around the line. Necessary permission will be obtained from department by contractor one day prior to trimming in particular area and shut down of that area will be arranged by department. (ii) Total length of line from supply point to load end will be measured for the purpose of payment, irrespective of the No of trees required to be trimed.
Unbinding from insulators ACSR conductor any size of HT over head line for repairs, restretching of ACSR conductor to achieve proper sag and rewinding to the insulators using aluminium/ GI wire all as required at site or directed. Note:- Distance between two poles irrespective of distance and no of lengths of conductor shall be considered as a single span.
Cleaning of installation area from inside and outside by removing the vegetation, cleaning the fungus formation and nearby growth of wild vegetation, bushes to a distance of 50 metres complete all as specified and directed.
Disconnecting electrically & mechanically outdoor transformers upto 400 KVA capacity, lowering down/getting out from plinth carefully for repairing /making of plinth of transformer and re-connecting electrically and mechanically after repairing/making of plinth , testing and commissioning complete all as specified and directed. Note:- (a) The rates quoted is deemed to be included for hydra, men power and other items required for temp energization of transformer.
Disconnecting electrically & mechanically indoor/outdoor transforemrs upto 400 KVA capacity, lowering down/getting out from plinth, 4/6 pole Structure carefully for prevednt/stoping for leakage of transformer oil (at site/sub station) including opening of top cover, draining out transformer oil and other items and storing the oil in suitable container (container to be provided by the contractor to keep aside for re -use) including replacement of all unserviceable gasket, after repairing/stoping of oil leakage the same re-connecting electrically and mechanically, testing complete all as specified and directed Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, T&P, hydra, gasket, opening/closing of top cover by unscrewing nut, bolts washers etc.
M&L for draining out complete transformer oil from transformer of upto 400 KVA capacity at site which found major repair and storing the oil in suitable container (container to be provided by the contractor to keep aside for re-use (after repair) and lifting of core assembly by opening of top cover and other items for inspection/examination of core assembly, after mainor repairs its fixing in original position, or for major repairs transformer to make it ready for transportation to carry out rewinding work in workshop
Dehydration, filtration, heating and refilling of old transformers oil after testing the same for dielectric strenghth not less than 45 KV (RMS). Note:- (a) Dehydration and filtration can be carried out at site by dehydration machine otherwise the same shall be got done from the manufacturing workshop of transformers complete all as specified.(b) Contractor shall ensure no wastage of transformer oil.(c) Safety of transformer during filteration shall solely be the responsibility of contractor and any damaged caused to transformer during the operation of filteration shall be made good by contractor at his own and no claim for any expanditure on this account shall be entertained during execution of work or later stage.(d) Contractor shall ensure that the conservator tank are full before starting the dehyderation.(e) Testing of transformer oil for BDV and acidity as per IE rules all as specified and directed.(f) Test results shall be submitted to Engineer-in-Charge equipment wise.
Supply and top up of transformer insulating oil HV grade having die-electric stength not less than 45 KVA (RMS) at 2.5mm gap. Make: Transoil/Power Oil Savita
Shifting of transformer trolley mounted upto 400 KVA from one Substn to other distance not more than 5 Kms carefully with tractor/ Crane including all Towing arrangement and taking out HT/LT connections of defective transformer and connecting carefully HT / LT connection including temporary earthing all as specified.
M&L labour for alternative arrangement by hiring, transportation of transformer of capacity upto 400 KVA in place of unserviceable copper /aluminium wound from transformer of capacity upto 400 KVA, opening top cover, and carrying out the following work complete all as specified and directed :- (a) Dismantling of all attachment viz breather assembly, conservator, oil temperature gauge, HT/LT bushing minor repairs etc. as required and directed and keeping aside for reuse. (b) Taking out the core with winding assembly. (c) Removing of complete winding from core and dismantling the core, cleaning of core laminate sheet and keeping aside for reuse (d) Cleaning of complete transformer tank oil fins, removing of sludge, and making the inside surface of tank dry by blowing of hot air as directed and specified. (e) Painting of outside surfaces of transformer complete by means of spray machine as directed. Note :- The contractor shall give written warranty of one year from the certified date of completion for the repaired transformer. HT/LT leg coils and transformer oil required for top up shall be measured and paid separately under relevant items of this Schedule here-in-after as supply only.
(f) Rewinding of HT/LT leg coil complete using copper wire /strip of appropriate gauge, size and turn as per existing with double paper coated insulation including all requisite insulating materials like packing sleeves, separator, tapes etc. heating, varnishing the core and winding assembly after framing up top and bottom steel structure of transformer all as specified and directed. (g) Replacement of all insulating materials other than incorporated for rewinding of HT/LT coils as per existing. (h) Fixing only HT procelain bushing with studs, nuts, washers 3 Nos. and LT procelain bushing with studs, nuts, and washers 4 Nos. and connection with primary and secondary windings and reconnecting with the main terminals as required and directed. (j) Replacement of all unserviceable gasket from top cover, HT/LT bushing with new one by using rubberised gasket sheet 4.0mm/6.0mm thick duly pasted with suitable adhesive . (k) Replacement of unserviceable bolts with new one and fixing of existing serviceable bolts, nuts, washers of different sizes and tightening properly.
Supplying and fixing in replacement (at site/workshop), Porcelain Transformer bushing on LT (440 Volt) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 400 KVA and re-connecting electrically and mechanically, testing complete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and suitable size pad type bus bar almuminium and nut bolt washers etc.
Supplying and fixing in replacement (at site/workshop), Porcelain Transformer bushing on HT (11 KV) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 400 KVA and connecting electrically and mechanically, testing complete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and suitable size pad type bus bar almuminium and nut bolt washers and reconnection.
Supplying and fixing in replacement, Silica Gel Breather assembly including vent pipe and Silica Gel for indoor/outdoor transformers, capacity upto 400 KVA complete all as specified and directed.
Supply and fixing Thermometer of transformer capacity upto 400 KVA complete all as specified and directed.
Material and labour in repair for handle suitable for GOD operation complete all as specified and as directed.
Supply only rubber hand gloves (ISI Marked) suitable for working with 11 KV HT lines complete all as specified and directed.
M&L for rewiding of HT/LT coils of transformer of capacity 25 KVA to 400 KVA with super enamelled copper winding wire of appropriate gauge and proper number of turns alongwith insulating material eg leatheroid, paper insulation, cotton tapes, Empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , heating/drying etc complete all as specified and directed by Engr-in-Charge.
M&L for rewiding of HT/LT coils of transformer of capacity 25 KVA to 400 KVA with super enamelled Aluminium winding wire of appropriate gauge and proper number of turns alongwith insulating material eg leatheroid, paper insulation, cotton tapes, Empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , heating/drying etc complete all as specified and directed by Engr-in-Charge.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of plate not less than 1.5 metre below ground level, connecting to galvanised iron strip 32X6 mm size (as earth lead strip), by means of bolt, nuts, check nuts and washer of galvanised and earth wire protected by provision of galvanised iron pipe light grade, 40 mm bore including provn of concrete pit in plain cement concrete M-15 type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of rainforced cement concrete M-15 reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia mild steel bar handle made to shape, galvanised iron medium grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorous bronze with fixing arrangement, funnel, wire mesh and including earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No. 3 of SSR 2009 Part-I and connection to earth test point all as specified and testing on completion.
Deduct Credit Amount as per Schedule of credit as details given on Srl Page No 26 of tender doucments.
dinesh enterprises
M/S MALHI CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .