Loading…
Loading…
Tender Value
₹50 L
EMD Value
₹50,000
Closing Date
3 Sept 2026, 6:00 pm
The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Erection &labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under CFC Piplod Division as well as in jurisdiction of ICHCHHAPORE sub division under Piplod Division or within the jurisdiction of Surat City Circle.
336340
DGVCLDPPL/0397/08/2026 Approved Date: 17-08-2026 08:29
Open
Electrical
Works
Surat
1 document required · 1 mandatory
₹1,180
SURAT DGVCL
₹50,000
18 Aug 2026
18 Aug 2026
18 Aug 2026
3 Sept 2026
18 Aug 2026
Sub:-Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end
termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under CFC under Piplod Division as well as in jurisdiction of
Ichchhapore sub division under Piplod Division or within the jurisdiction of Surat City Circle.
Item Code DETAILS OF WORKS Qty Unit Rate Amount
1 9925000001 Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any Meter
type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm
additional width shall be considered i.e. half trench length is to be considered)
2 9925000002 Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any Meter
type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm
additional width shall be considered i.e. half trench length is to be considered)
3 9925000003 Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any Meter
type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm
additional width shall be considered i.e. half trench length is to be considered)
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & preparation Meter
of sand layer 100mm thick, in the cable trench & covering the cable with 150 mm dia
(Inner), thickness 25 mm, 1.0 meter long RCC half round muffs and providing and fixing
of 4inch width yellow colour polyethylene tape with printing "CAUTION ELECTRIC CABLE
BELOW" at 0.75 m depth from ground surface after laying cable in trench. This will
provide indication that electric cable is passing underground so as to protect cable from
mechnical injuries, refilling the same, as per Instruction of Engineer in Charge (EIC).
5 9925000005 Labour charge for horizontal drilling using Auger machine without damage to surface Meter
road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D.
8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size up to 300 mm2 in HDPE pipe, as
per Site Condition (excluding cost of pipe). The detail map obtained from HDD machine
and excell sheet(hard and soft copy) indicating the respective depth and distance from
adjacent landmark for each segment for HDD is must required to be submitted. HDD to
be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as per instruction
6 9925000006 Labour
of EIC. charge for horizontal drilling manually without damage to surface road at max Meter
2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D., 8.5mm
thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS certification and
laying of 11KV/22KV XLPE cable of size up to 300 mm2 size, as per Site Condition
(excluding cost of pipe). The detail map and excell sheet(hard and soft copy) indicating
the respective depth and distance from adjacent landmark for each segment of cable to
be submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per
site conditions as per instruction of EIC.
7 9925000007 Supply of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5 mm thickness H.D.P.E. pipe Meter
confirms to IS 4984 and BIS certification for laying of underground 11KV / 22KV XLPE
cable up to 300 mm2 size.
8 9925000008 Labour work for RCC concreting on disputed location and repairing of damage portion of CMT
road crossing for the work carried out for roads crossing as well as concreting & muffing
of ploes including all materials (1:2:4)
9 9925000009 Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x 650 No
mm height embedded in earth at least 300 mm below & 350 mm above ground level
respectively at distance approx 50 meters along the length of cable. The RCC concreting
(1:2:4)(all necessary maeterials will be in bidder's scope) of route marker is to be carried
out 300 mm width x 150 mm thick x 300 mm below ground level as per instruction of
EIC. The route marker should be with name of company with approved yellow colour-
DGVCL. The distance from marker to cable and cable depth with feeder name etc.,
marked with arrow sign is to be painted on it.The route marker is to be fixed at location
near to any fixed permanent location (not necessary to fix exact on top of cable) as per
instruction of EIC.
10 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 300 mm 2 on DP Per Job
Structure with fixing of 02 Nos polymer cleats on top and middle part. Polymer cleats,
nut bolts etc. fixing material to be provided by contractor.
11 9925000015 Providing & fixing of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5mm thickness Per Job
H.D.P.E. pipe confirms to IS 4984 and BIS certification on the erected DP structure for the
mechanical protection of cable by inserting the cable inside HDPE pipe. The HDPE pipe
shall be erected in such a way that 300mm shall be below the ground level and the rest
2700 mm shall be supported on the DP Structure with 01 No Polymer cleat. All
materials including polymer cleat and Nut bolt to be provided by contractor.
12 9925000016 Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be No
filled with salt & coke and construction of chamber as per DGVCL Drg. No. dg /100 for DP
and cable. The earthing pit should be joined with cable by G.I. strip of size 1” width &
mm thick. All material GI pipe, Coke, Salt etc will be supplied by bidder.
13 9925000017 Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x 185 No
mm2 size XLPE cable as per DGVCL technical specification.
14 9925000018 Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV 3C x 185 No
mm2 size XLPE cable as per DGVCL technical specification.
15 9925000019 Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C x 185 mm No
size XLPE cable as per DGVCL technical specification.
16 9925000020 Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV 3C x 185 No
mm2 size XLPE cable as per DGVCL technical specification.
17 9925000021 Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x 185 mm2 size No
XLPE cableas per DGVCL technical specification.
18 9925000022 Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x 185 mm No
size XLPE cable as per DGVCL technical specification.
19 9925000023 Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint No
pits for installation of 11kV/22kV Straight through joints as per instruction of engineer-
in-charge & covering the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter
long RCC half round muffs & refilling same as per instruction of EIC .
20 9925000024 Providing and fixing of insulating bus bar , made from 11KV/22KV XLPE cable after No
removal of semi conducting layer and applying of PVC heat shrinkable anti-tracking core
insulating tubing (1.1KV), on both end terminal using Aluminium long barrel heavy duty
up to 240 sq mm lugs, Aluminium bus connector. Taping with PG- clamp for bus
conductor as per drawing and as per instruction of EIC. The Alluminium lugs and PG
clamp shall be covered with 11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable will be
in scope of DGVCL while all other materials will be in bidder's scope)
21 9925000025 Testing of cable at various points and commissioning the feeder as per instruction of No
engineer-in-charge. Test result shall be submitted by contractor with bill.
22 9925000026 Preparation and submission of 6 (six) copies , of complete layout drawings with GIS Set
mapping as per actual cable routing showing road crossing, HDPE pipe sleeving, jointing
locations, markers etc.
23 9925000027 Providing and fixing of Sign Board at junction point Made out of 2 mm aluminium sheet No
size 750x300 mm (2.5 x 1ft) rectangle, as per design, pre treated with phosphate process
and acid etching coated with one coat of epoxy primer and two coats of best quality
paints, refloctrorised with Hi-Intensity retro – reflective sheeting as per the latest and
frame fabricated from suitable size iron angle. The Sign Board is to be fixed on the base
prepared from channel and bracing angles which is grouted by means of cement
concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm to be grouted in
ground). The details to be displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
24 9925000028 Providing and fixing of Sign Board (Danger Board) on Distribution Transformer Centers No
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design, pre treated
with phosphate process and acid etching coated with one coat of epoxy primer and two
coats of best quality paints, refloctrorised with Hi-Intensity retro-reflective sheeting as
per the latest and frame fabricated from suitable size iron angle. The Sign Board (Danger
Board is to be fixed at the location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
25 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm No
aluminium sheet along with 1.0 mm dia aluminium binding wire for fixing of aluminium
tag near end termination joint at DP structure for identifyng the cable. The details of
feeder i.e. 11 / 22 KV with feeder name shound be punched on the tag by letter punch of
size 16 mm as per instruction of In-charge Engineer.
26 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 mm2 Nos
size XLPE cable as per DGVCL technical specification.
27 9925000031 Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C x 240 mm2 Nos
size XLPE cable as per DGVCL technical specification.
28 9925000032 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2 size Nos
XLPE cable as per DGVCL technical specification.
29 9925000033 Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x 240 mm2 Nos
size XLPE cable as per DGVCL technical specification.
30 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 size XLPE Nos
cableas per DGVCL technical specification.
31 9925000035 Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x 240 mm2 size Nos
XLPE cable as per DGVCL technical specification.
32 9925000038 Installation, Testing and commissioning of 11 KV, 630 A SCADA Compatible, RRL type- 3 Nos
Way RMU including Two numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
33 9925000039 Installation, Testing and commissioning of 11 KV, 630 A SCADA Compatible, RRLL type- 4 Nos
Way RMU including Two numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
34 9925000040 Installation, Testing and commissioning of 22KV, 630 A SCADA Compatible, RRL type-3 Nos
Way, RMU including Two numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
35 9925000041 Installation, Testing and commissioning of 22KV, 630 A SCADA Compatible, RRLL type-4 Nos
Way, RMU including Two numbers of earthings as per Drawing (material is in bidder's
scope) and as per DGVCL Technical specification.
36 9925000042 Construction of plinth for 11KV, RRL type- 3 Way (i.e Two numbers of Isolator & One Nos
number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned in
drawing no: Drg. 11kv-01. All required material will be supplied by contractor.
37 9925000043 Construction of plinth for 11KV, RRLL type- 4 Way (i.e Two numbers of Isolator & Two Nos
number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned in
drawing no:Drg. 11kv-02. All required material will be supplied by contractor.
38 9925000044 Construction of plinth for 22KV, RRL type- 3 Way (i.e Two numbers of Isolator & One Nos
number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned in
drawing no: Drg. 22kv-01. All required material will be supplied by contractor.
39 9925000045 Construction of plinth for 22KV, RRLL type- 4 Way (i.e Two numbers of Isolator & Two Nos
number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned in
drawing no:Drg. 22kv-02. All required material will be supplied by contractor.
40 9925000046 Modifications e.g.Providing and fixing of Terminal protectors i.e. Re-use able boot (HT Side Nos
11/22KV, LT Side 1.1KV) including 11/22 KV insulating taps and L.T.(1.1 KV) insulating taps
,Busbar, Tapping from Bus Bar (11/22 KV XLPE cable) through P.G. Clamp for H.T. Jumper to
D.O. Fuse to bushings of Transformer Center, providing & Fixing of jumper and providing &
fixing of Heat Shrinkable Anti Tracking Core Insulating Tubing (Insulation Level 11/22 KV) in H.T.
jumper , Clamping arrangement of cable support frame on both side of existing Over Head type
Distribution Transformer to utilize in Under Ground cable network as per drawing & as per
instruction of Engineer incharge. All live parts i.e. PG-Clamp, connections of D.O.fuses, HT
bushings etc . shall be covered with fixinng of 11/22 KV HT insulating tapes. ( 11/22 KV XLPE
cable will be in scope of DGVCL while all other materials will be in bidder's scope ) .
Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in open space
33 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole per
34 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round pipe NO.
35 9925000010 Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable connection NO.
arrangement along with fitting of necessary fabrication for 11KV cable including
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
36 9925000011 Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection NO.
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable including
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
37 9925000012 Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable connection NO.
arrangement along with fitting of necessary fabrication for 11KV cable including
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
39 9925000013 Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection NO.
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable including
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
40 Laying (including installation, testing and commissioning) of various size of mtr 335 as per rate derived by
Single circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable in ground UGVCL letter no
1200 mm deep and 300 mm wide trench, providing sand cushioning below (75 mm thick ugvcl/r&c/ug/Cost Data-
layer of sand) and above (75 mm thick layer of sand) of the cable and covering it with 2022-23/816 Date:-27-01-
RCC half round hume pipe (150 mm inner
diameter with thickness of 30 mm and One meter in length) before refilling
pre-bonding tap/warning tap should provide below 700 mm from the
ground level and back filling the same to make ground level as per original.
As per specification and drawing of DGVCL. ( RCC half round pipe should be
provide throughout on cable without gap).
41 Laying (including installation, testing and commissioning) of various size of mtr 468 as per rate derived by
Double circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable in ground UGVCL letter no
1200 mm deep and 500 mm wide trench, providing sand cushioning below (75 mm thick ugvcl/r&c/ug/Cost Data-
layer of sand) and above (75 mm thick layer of sand) of the cable and covering it with 2022-23/816 Date:-27-01-
RCC half round hume pipe (150 mm inner diameter with thickness of 30 mm and One
meter in length) before refilling pre-bonding tap/warning tap should provide below
mm from the ground level and back filling the same to make ground level as per original.
As per specification and drawing of DGVCL. ( RCC half round pipe should be provide
throughout on cable without gap).
42 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 300 mm2 size No 5549 as per rate derived by
XLPE cable as per technical specification. UGVCL letter no
ugvcl/r&c/ug/Cost Data-
43 Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x 300 No 6676 as per rate derived by
mm2 size XLPE cable as per technical specification. UGVCL letter no
ugvcl/r&c/ug/Cost Data-
44 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 300 mm2 size XLPE No
8040 as per rate derived by
cableas per L technical specification. UGVCL letter no
ugvcl/r&c/ug/Cost Data-
Rate as per SOR 2023 50,00,000/-
Executive Engineer (O&M)
DGVCL, Division Office,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. Tender Notice Ichchhapore 50 L.pdf
2. BID DOCUMENT.pdf
3. Detail Technical Specification.pdf
SCHEDULE B UG Ichchhapore.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].