Vadodara Division: Electrical works in connection with improvement to Admin, General Services, TRD and Hostel buildings at ZETC - Vadodara Yard and improvement of Running Rooms at Bharuch, Miyagam Karjan and Anand.
BRC-EL-P-19-2552-80-26-27~WR
BRC-EL-P-19-2552-80-26-27
Open
Works - General
6 Months
Vadodara, Gujarat
₹0
₹1.5 L
5 Aug 2026
5 Aug 2026
13 Aug 2026
146 items across 3 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ Below/Par | ||
| — | — | — | 50,16,211 | ||
| — | 350.00 | — | — | ||
| Wiring of light/fan/exhaust fan points in concealed manner with modular accessories - The price shall cover for concealed wiring of light/fan/exhaust fan point with 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. | — | — | — | 1,42,800 | |
| — | 70.00 | — | — | ||
| Providing plug point 6 Amp in concealed manner in existing board with modular accessories - The price shall cover for providing plug point with modular type universal 5 pin socket and switch, 6 Amp, 230 Volt, AC on existing board. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/ Siemens/Anchor/ Legrand/Havells/Luminous make. | — | — | — | 16,590 | |
| — | 70.00 | — | — | ||
| Providing board with four switches and four sockets, 6 Amp in concealed manner with modular accessories - The price shall cover for providing multi-plug point board (switch, 6 Amp - 4 Nos and universal socket, 6 Amp - 4 Nos) with modular type universal five-pin socket and switch, 6 Amp, 230 Volt, AC with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/ Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of board with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.0 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/ Prestoplast/Gerard make. | — | — | — | 31,570 | |
| — | 70.00 | — | — | ||
| Providing plug point 16 Amp in concealed manner on separate board with modular accessories - The price shall cover for providing power plug point with modular type universal 5 pin socket and switch, 16 Amp, 230 Volt, AC on separate board with modular accessories. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. The price shall also cover for concealed wiring of plug point with 2.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with 1.5 sq. mm, PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 as earthing wire with all accessories in concealed type of wiring in medium grade PVC conduit and accessories of Precision/Modi/Prestoplast/Gerard make. | — | — | — | 31,220 | |
| — | 800.00 | — | — | ||
| Concealed wiring of sub-main with 2.5 sq. mm in PVC conduit - The price shall cover for concealed wiring of sub main with two-wire single core 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 71,200 | |
| — | 500.00 | — | — | ||
| Concealed wiring of sub-main with 2.5 sq. mm copper wire, single-core in existing PVC conduit - The price shall cover for wiring of two wire sub-main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner in existing PVC conduit. | — | — | — | 38,000 | |
| — | 500.00 | — | — | ||
| Concealed wiring of sub-main with 4.0 sq. mm in PVC conduit - The price shall cover for concealed wiring of sub main with two-wire single core 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 54,500 | |
| — | 450.00 | — | — | ||
| Wiring of light/fan/exhaust fan point in PVC casing-capping/conduit - The price shall cover for wiring of light/fan/exhaust fan point with 1.5 sq. mm, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS and 1.0 sq. mm, single-core, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping double lock type, ISI marked of make Modi/Precision/Gerard/Prestoplast or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions with surface mounted molded polypropylene switch board with modular cover plate of suitable size including switches/angular holders/ceiling rose. Space shall be kept on board to accommodate modular electronic fan regulator. Molded polypropylene switch board shall be as per IS: 14772. The accessories shall be of modular type of C&S/MK/ North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. | — | — | — | 1,64,250 | |
| — | 70.00 | — | — | ||
| Providing plug point, 6 Amp in existing board - The price shall cover for providing plug point with modular type universal 5 pin socket and switch, 6 Amp, 230 Volt, AC on existing board. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. | — | — | — | 6,790 | |
| — | 300.00 | — | — | ||
| Wiring of sub-main with copper wire, single-core, 2.5 sq. mm in casing-capping/conduit - The price shall cover for wiring of two wire sub- main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 33,300 | |
| — | 300.00 | — | — | ||
| Wiring of sub-main with copper wire single-core 2.5 sq. mm in existing casing capping/ conduit - The price shall cover for wiring of two wire sub-main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in existing PVC casing-capping or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 25,500 | |
| — | 400.00 | — | — | ||
| Wiring of sub-main with copper wire single-core 4.0 sq. mm in casing-capping/conduit - The price shall cover for wiring of two wire sub- main with 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 46,800 | |
| — | 310.00 | — | — | ||
| Providing electronic fan regulator, modular type - The price shall cover for supply, fixing, testing and commissioning of hum-free modular type electronic fan regulator suitable for 80/100-Watt ceiling fan of step type with 'OFF' position, surface/flush type on existing board and its connection from existing supply. Miniature switch type regulators shall not be accepted. The regulator shall be of Anchor-Roma/Cona/ Leader/Crabtree/Legrand/C&S/HPL/Indo Asian/Havells/Standard/Bentec/Elleys/Precision make. | — | — | — | 86,490 | |
| — | 310.00 | — | — | ||
| Fixing, testing and commissioning of ceiling fan - The price shall cover for fixing, testing and commissioning of ceiling fan on existing hook and its connection by FRPVC insulated, flexible copper cord, 1100Volt grade, 24/0.20mm from existing ceiling rose with earth connection. A suitable suspension clamp made from G.I. flat of 40 x 6 mm with MS 'S' shaped hook of diameter not less than 10 mm shall be provided as per site requirement if fan hook is not available and this is included in the scope of work. The ceiling fans shall be supplied by railways at site engineer's office/store. | — | — | — | 53,630 | |
| — | 25.00 | — | — | ||
| Providing heavy-duty Exhaust fan 150 mm sweep, metallic body with louver/bird guard - The price shall cover for supply of heavy duty, Exhaust Fan of metallic body, 150 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of Crompton Greaves/GEC/ Almonard/Usha/Bajaj make. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 32,550 | |
| — | 41.00 | — | — | ||
| Providing heavy-duty Exhaust fan, 300 mm sweep with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 300 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of Crompton Greaves/GEC/ Almonard/Usha/Bajaj make. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 59,778 | |
| — | 10.00 | — | — | ||
| Providing industrial heavy duty Exhaust Fan, 380/400 mm sweep with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 380/400 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of Crompton Greaves/ GEC/Almonard/Usha/Bajaj make. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 20,500 | |
| — | 10.00 | — | — | ||
| Providing industrial heavy duty Exhaust Fan, 450 mm sweep with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 450 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of Crompton Greaves/GEC/ Almonard/Usha/Bajaj make. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 39,630 | |
| — | 20.00 | — | — | ||
| Providing decorative wall bracket fan, 400 mm sweep - The price shall cover for supply of decorative wall mounted bracket fan, 400 mm sweep, operating on 230 Volt, 50 Hz AC supply, oscillating type, 90° swing with three-speed regulator, three aerodynamically balanced blades made of aluminium and base made of MS pipe/plate. The decorative wall bracket shall be of Crompton Greaves/Usha/Orient/Bajaj/ GEC/Almonard make. The price shall also cover for fixing, testing and commissioning of bracket fan on wall by suitable size of MS clamps and its connection from existing socket/supply point as per site requirement. The wall bracket fan shall be got approved from site engineer before supply. | — | — | — | 38,440 | |
| — | 15.00 | — | — | ||
| Supply of energy efficient, BLDC pedestal fan, 400 mm sweep - The price shall cover for supply of energy efficient, BLDC pedestal fan, 400 mm sweep, operating on 230 Volt, 50 Hz AC supply. The pedestal fan should offer high air delivery (75 CMM), speed of 1500 RPM, low noise level ( 57dB) and aerodynamically balanced blades. The fan should be supplied with IR remote control for effortless control, allowing to adjust speed, activate boost mode, set timers, enable sleep mode with a single click or enable oscillation/swing mode. The remote control shall be universal across all the pedestal fans and not needed to be paired, allowing easy operation. The fan should feature 90 degree swing (controlled by remote control/button) to ensure higher coverage across the room. Additionally, it should be manually tilted up to 30 degree allowing directing the airflow precisely for maximum comfort. The pedestal fan shall be of ATOMBERG/HAVELLS/ORIENT/CROMPTON/USHA or any other make approved by Sr. DEE (Power) Vadodara. | — | — | — | 56,940 | |
| — | 3.00 | — | — | ||
| Providing Ray Roll plug and socket, 20 Amp with MCB DP, 16/20 Amp in weather proof box for water cooler - The price shall cover for supply, erection, testing and commissioning of power plug board with one MCB DP 16/20 Amp, ray-roll socket 16/20 Amp and LED indication lamp in weather proof MS enclosure. The MCB shall be of ABB/L&T/GE/MDS/Siemens/BCH/C&S/HPL/Schneider/Havells make. The colour of MS enclosure should be in sync with the decor of the room and as decided by site engineer. The MS enclosure shall be properly earthed. | — | — | — | 2,733 | |
| — | 22.00 | — | — | ||
| Providing MCB and starter with three-pin plug point for Air Conditioner unit for surface wiring - The price shall cover for supply, erection, testing and commissioning of power unit for Air Conditioner in enclosure with MCB DP 20/25 Amp, 3 KA breaking capacity, DOL starter of 16 - 25 Amp capacity suitable for 1.5/2.0 TR A.C. unit, one No 16/20/25 Amp socket and three-pin plug top, 16/25 Amp of ANCHOR-ROMA/CRABTREE/NORTH-WEST make with 4.0 sq. mm single core multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 2.5 sq. mm single core multi-stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping, double lock type, ISI marked of Modi/Precision/Gerard/Prestoplast make at an approximate distance up to 3 meter or as per site requirement. | — | — | — | 20,636 | |
| — | 1.00 | — | — | ||
| Providing MCB and starter with three-pin plug point for Air Conditioner unit in concealed manner with modular accessories - The price shall cover for supply, erection, testing and commissioning of power unit for Air Conditioner in concealed type modular enclosure with MCB DP 20/25 Amp, 3 KA breaking capacity, DOL starter of 16 - 25 Amp capacity suitable for 1.5/2.0 TR A.C. unit, one No 16/20/25 Amp socket and three-pin plug top, 16/25 Amp of ANCHOR-ROMA/CRABTREE/NORTH-WEST make with wiring of sub-main of two-wire, single core, 4.0 sq. mm PVC insulated, unsheathed, multi- stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 and one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in concealed manner as per site requirement in PVC conduit of Modi/Precision/Gerard/ Prestoplast make at an approximate distance up to 3 meter or as per site requirement. | — | — | — | 1,191 | |
| — | 230.00 | — | — | ||
| Providing four-core, multi-stranded, flexible copper cable, 2.5 sq. mm from indoor to outdoor unit - The price shall cover for supply, fixing, testing and commissioning of PVC insulated, multi-stranded, four-core, copper conductor cable, 2.5 sq. mm, 1100 Volt grade, ISI marked, conforming to IS: 694 or latest of make Neocab/Polycab/Finolex/R.R. Cable. The cable shall be connected from the indoor and outdoor units of split A.C. along with 8 SWG earth wire in PVC sleeve of good quality for earthing the equipments from existing nearby earth point/electrode. The copper wire and earth wire shall be laid in PVC conduit of suitable size and properly fixed. | — | — | — | 36,110 | |
| — | 452.00 | — | — | ||
| Providing copper piping for suction and discharge lines of Air Conditioner unit - The price shall cover for supply, fixing, testing and commissioning of refrigerant copper piping suitable for R-22, R-134 A, R-407 refrigerant and conforming to IS: 10773/2006 (latest) from indoor unit to outdoor unit. The copper piping shall be insulated with polyurethane foam tubing duly covered with weather protection. The copper refrigerant pipe shall be suitable for bearing 350 PSI pressure and the thickness should be 19 SWG and diameter should be suitable for handling of refrigerant for capacity 3.5 TR of refrigerant quantity without creating any extra pressure due to quantity of refrigerant and as per manufacturer's recommendations. The exposed copper piping shall be suitably concealed as per site requirement. | — | — | — | 1,39,216 | |
| — | 452.00 | — | — | ||
| Providing rigid PVC drain pipe - The price shall cover for supply and fixing of rigid uPVC pipe medium grade of required diameter from indoor unit to main drain hole for draining of condensed water from cooling coil (Indoor unit) to main drain discharge point. | — | — | — | 18,080 | |
| — | 23.00 | — | — | ||
| Providing M.S. stand for outdoor unit of Split Air Conditioner - The price shall cover for fabrication, supply, fixing and commissioning of MS angle frame/stand made from MS angle for outdoor unit of split AC. The size of angle shall be 40 x 40 x 6 mm painted with two coats of red oxide primer and finished with one coat of black enamel paint. The angle stand shall be fixed at site with anchor bolts. Necessary civil works involved are included in the scope of work. | — | — | — | 9,867 | |
| — | 23.00 | — | — | ||
| Installation, testing and commissioning of Split Air Conditioner - The price shall cover for installation, fixing, testing and commissioning of the split AC as per the site-engineer's instructions/requirements with all associated wiring, copper piping, existing drain piping, existing MS outdoor stand. This shall also cover for making a hole of suitable diameter in the existing brick masonry/RCC wall for laying of cables, pipes etc from indoor to outdoor unit in a neat and aesthetic manner. The hole shall be sealed with plaster of Paris to prevent entry of insects, rain water, lizards etc. Manufacturer's recommendations/instructions shall be strictly followed. Split Air Conditioners shall be supplied by railways from the site engineer's office/stores. | — | — | — | 33,028 | |
| — | 56.00 | — | — | ||
| Supply, fixing, testing and commissioning of five-star rated, storage geyser of 10.0 liter capacity - The price shall cover for supply of energy efficient, five-star BEE rating, storage type geyser, ten-liter capacity, heating element of 2000 Watt, having inner tank material of mild steel with glass lined coating and outer body of ABS + PP (rust proof), adjustable stem type thermostats, fusible safety plug operating on pressure of 8 Bar and 4 in 1 multifunctional safety valve. The geyser shall be ISI marked with inlet and outlet hoses of suitable diameter and length and gun metal inlet stop valve. The geyser shall be supplied complete with three-core, PVC insulated, copper wire, ISI marked and 15 Amp plug top. The geyser shall be of VENUS/RACOLD/SPHEREHOT/BAJAJ/CROMPTON GREAVES make.The price shall also cover for fixing, testing and commissioning of instantaneous type geyser of ten-liter capacity. The scope of work includes supply and fixing of Anchor fasteners, nut bolts, supply of accessories, modification/rectification of civil works such as inlet-outlet water connection pipes of suitable capacity and size, plumbing, wiring etc. required to install the Geyser at desired location. | — | — | — | 4,18,544 | |
| — | 6.00 | — | — | ||
| Providing fly catcher unit, 230 Volt - 20 Watt complete with all accessories - The price shall cover for supply, fixing, testing and commissioning of fly catcher having stainless steel enclosure with high voltage transformer and twin two-feet, Ultraviolet fluorescent tube, 20 Watt to work on 230 Volt, 50 Hz, single phase AC supply. Approximate size of complete assembly shall be - 25" (L) x9.5" (B) x16" (H) of make AVRO FLYKIL-LITE model Killer 1000 or equivalent of Shree Aerodynamic products/TECHNOCRAFT. The flycatcher shall be fitted by suitable size of clamps as per the instructions of site in-charge and shall be connected by three- core, PVC insulated, flexible copper wire of size 48/0.20 mm from existing catenaries/ light point as per site requirement through flexible PVC conduit. | — | — | — | 17,328 | |
| — | 10.00 | — | — | ||
| Providing PVC Junction box with four-way connector of 16 Amp rating and MCB DP, 6/10/16 Amp - 1 No - The price shall cover for supply and fixing of PVC junction box with four-way connector of 16 Amp rating and MCB DP, 10 KA breaking capacity, 6/10/16 Amp. The MCB shall be of ABB/ L&T/GE/MDS/Siemens/BCH/C&S/HPL/Schneider/Havells make. The connector shall be of reputed make and quality, ISI marked in existing sub-main and its connection from existing sub-main with 1.5 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 1.0 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS. | — | — | — | 12,900 | |
| — | 6.00 | — | — | ||
| Providing lighting control board with MCB DP, 32 Amp - 2 Nos, Time Switch, 16 Amp - 2 Nos and Single Phase Contactor, 32 Amp - 2 Nos - The price shall cover for supply, fixing, testing and commissioning of lighting control board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The board shall be equipped with MCB DP, 10 KA breaking capacity, 32 Amp rating - 2 Nos, Time switch, 16 Amp - 2 Nos and Single phase contactor of rating 32 Amp - 2 Nos. The MCB shall be of ABB/L&T/HPL/GE/ MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make, the contactor shall be of L&T/BCH/C&S/CGL/ Schneider/Siemens make and Digital Time Switch "CRONO" of L&T make or similar of Siemens/Minilec make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 31,314 | |
| — | 30.00 | — | — | ||
| Providing Distribution Board with incomer MCB DP, 16/32 Amp - 1 No, RCBO, two-pole, 25 Amp - 1 No and outgoing MCB DP, 6/10/16 Amp - 4 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB DP 16/32 Amp - 1 No, RCBO, two-pole, 30 mA sensitivity, 25 Amp - 1 No and outgoing MCB DP, 6/10/16 Amp - 4 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The Distribution Board shall be suitable for concealed/surface installation as per site requirement. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 1,67,100 | |
| — | 15.00 | — | — | ||
| Providing Distribution Board with incomer MCB TPN, 32 Amp - 1 No, RCBO, four-pole, 32/40 Amp - 1 No and outgoing MCB DP, 10/16 Amp - 6 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer MCB TPN 32 Amp - 1 No, RCBO, four-pole, 30 mA sensitivity, 32/40 Amp - 1 No and outgoing MCB DP, 10/16 Amp - 6 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/Schneider/CGL/Havells make. The Distribution Board shall be suitable for concealed/surface installation as per site requirement. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. | — | — | — | 1,55,580 | |
| — | 6.00 | — | — | ||
| Providing Distribution Board with incomer MCB TPN, 63 Amp - 1 No, RCBO, four-pole, 63 Amp - 1 No and outgoing MCB DP, 10 to 32 Amp - 12 Nos with indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre-fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories -(a) Incomer - MCB TPN, 10 KA breaking capacity, 63 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 1 NoRCBO four-pole, 30 mA sensitivity, 63 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 1 No(b) Outgoing - MCB DP, 10 KA breaking capacity, 10 to 32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 12 Nos(c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set(d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set(e) Cable glands of required sizes --- LOT(f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom.(g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 84,906 | |
| — | 2.00 | — | — | ||
| Providing Distribution Board with incomer MCB TPN, 63 Amp - 1 No, RCBO, four-pole, 63 Amp - 1 No and outgoing MCB DP, 16/20/32 Amp - 6 Nos with Time Switch, 16 Amp - 2 Nos and Single-Phase Contactor, 32 Amp - 2 Nos with indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre-fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories -(a) Incomer - MCB TPN, 10 KA breaking capacity, 63 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 1 NoRCBO four-pole, 30 mA sensitivity, 63 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 1 No(b) Outgoing -MCB DP, 10 KA breaking capacity, 16/20/32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 6 Nos(c) Time switch, 16 Amp and Single phase contactor of rating 32 Amp. The contactor shall be of L&T/ BCH/C&S/CGL/Schneider/Siemens make and the Digital Time Switch "CRONO" of L&T make or similar of Siemens/Minilec make --- 2 sets(d) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set(e) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set(f) Cable glands of required sizes --- LOT(g) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom.(h) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 41,200 | |
| — | 6.00 | — | — | ||
| Providing Distribution Board with incomer MCCB, four-pole, 125 Amp - 2 Nos and outgoing MCB DP, 16/32 Amp - 18 Nos with indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre-fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/ accessories -(a) Incomer - MCCB, four-pole, 125 Amp, with thermal-magnetic release range 100 - 125 Amp, Ics = 100% Icu having 35 KA breaking capacity and conforming to IS/IEC 60947-2 with adjustable overload and short circuit settings and inbuilt instantaneous protection. The MCCB shall be supplied with spreader terminals and rotary handle. The MCCB shall be of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make --- 2 Nos(b) Outgoing -MCB DP, 10 KA breaking capacity, 16/32 Amp of ABB/L&T/HPL/GE/MDS/Siemens/BCH/C&S/ Schneider/CGL/Havells make ---- 18 Nos(c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set(d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set(e) Cable glands of required sizes --- LOT(f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom.(g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 1,28,052 | |
| — | 3.00 | — | — | ||
| Providing Distribution Board with incomer MCCB, four-pole, 160 Amp - 1 No and outgoing MCB TPN, 63 Amp - 6 Nos and MCB DP, 32 Amp - 6 Nos with indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of pre- fabricated Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, outdoor type confirming to relevant IS and complete with MCCBs and MCBs. The Distribution Board shall be suitable for surface/concealed mounting. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the switchgears/accessories as given in the detailed technical specification in Annexure-XXI of tender document. | — | — | — | 71,946 | |
| — | 4.00 | — | — | ||
| Providing Distribution Board, double-door, outdoor type with incomer MCCB, four-pole, 100 Amp - 2 Nos, RCCB, four-pole, 100 Amp - 1 No and outgoing MCB TPN, 32/40 Amp - 6 Nos and MCB DP, 25/32 Amp - 10 Nos, Time Switch, 16 Amp - 2 Nos and Single Phase Contactor, 25 Amp - 2 Nos with indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switchgears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication.The LT panel shall be of rectangular cubicle type, double-door for outdoor installation, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document. | — | — | — | 2,61,812 | |
| — | 2.00 | — | — | ||
| Providing Distribution Board, double-door, outdoor type with incomer MCCB, four-pole, 125 Amp - 1 No and outgoing MCCB, four-pole, 100 Amp - 2 Nos and MCCB, four-pole, 63 Amp- 4 Nos with multifunctional energy meter, indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switchgears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication.The LT panel shall be of rectangular cubicle type, double-door for outdoor installation, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document. | — | — | — | 1,46,920 | |
| — | 1.00 | — | — | ||
| Providing Distribution Board, double-door, outdoor type with incomer MCCB, four-pole, 250 Amp - 2 Nos and outgoing MCCB, four-pole, 125 Amp - 4 Nos and MCCB, four-pole, 63 Amp - 4 Nos with multifunctional energy meter, indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switchgears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication.The LT panel shall be of rectangular cubicle type, double-door for outdoor installation, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document. | — | — | — | 99,636 | |
| — | 2.00 | — | — | ||
| Providing Distribution Panel with incomer MCCB, four-pole, 400 Amp - 1 No and outgoing MCCB, four-pole, 250 Amp - 4 Nos and MCCB, four-pole, 125 Amp - 4 Nos with multifunction energy meter, indication lamps, earthing terminals and all accessories - The price shall cover for design, supply, installation, testing and commissioning L.T. Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switchgears with make and model of the LT panel shall be submitted by the contractor in three copies and got approved from site engineer before fabrication.The LT panel shall be of rectangular cubicle type, double-door for outdoor installation, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender document. | — | — | — | 3,95,052 | |
| — | 485.00 | — | — | ||
| Digging of cable trench 450/600 mm wide and 900 mm deep in all types of soil including hard, rocky etc. - The price shall cover for digging of 450/600 mm wide and 900 mm deep trench in all types of soil including soft, rocky as per cable route plan and filling back the trench after laying of cables. This also includes clearing of roots of trees and bushes and other temporary obstructions on the selected route. | — | — | — | 60,140 | |
| — | 50.00 | — | — | ||
| Digging of cable trench 100 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of cable in HDPE pipe, 50 mm diameter - The price shall cover for digging of cable trench of size 100 x 200 mm deep in concrete/tar road/platform surface and its refilling/plastering after laying of cable in 50 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/Poddar/ Unique/Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 50 mm diameter is included in the scope of work. | — | — | — | 18,200 | |
| — | 100.00 | — | — | ||
| Digging of cable trench 200 mm wide and 200 mm deep in concrete/tar road/platform and refilling to its original position after laying of cable in 110 mm diameter HDPE pipe - The price shall cover for digging of cable trench of size 200 x 200 mm deep in concrete/tar road/platform surface and its refilling/plastering after laying of cable in 110 mm diameter HDPE pipe of Tijaria/Himalyan/Koncept/ Poddar/Unique/Dutron/Reliance/Baba/Shivam make in existing trench. Supply and laying of HDPE pipe, 110 mm diameter is included in the scope of work. | — | — | — | 67,700 | |
| — | 950.00 | — | — | ||
| Supply and laying of DWC pipe, 63 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 63 mm diameter of Tijaria/Himalyan/Koncept/Poddar/Unique/ Dutron/Reliance/Baba/Shivam make. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively.The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 79,800 | |
| — | 400.00 | — | — | ||
| Supply and laying of DWC pipe, 120 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 120 mm diameter of Tijaria/Himalyan/Koncept/Poddar/Unique/ Dutron/Reliance/Baba/Shivam make. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively.The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 63,600 | |
| — | 40.00 | — | — | ||
| Supply and laying of HDPE pipe, 160 mm diameter by pushing method under track/road - The price shall cover for supply of HDPE (High Density Polyethylene) pipe of 160 mm nominal diameter as per IS 4984-1995 of make Tijaria/Himalyan/Koncept/Poddar/Unique/Dutron/Reliance/Baba/Shivam with accessories required for laying such as coupler, bend etc. as per details given in Annexure-XXI of tender document. The price shall also cover for laying the HDPE pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 50,040 | |
| — | 430.00 | — | — | ||
| Providing PVC maxi trunking of size 100 x 50 mm - The price shall cover for supply, fixing, testing and commissioning of ISI marked PVC Maxi Trunking of size 100 x 50 mm with all accessories of make Precision/Gerard/Modi/Prestoplast. The PVC Maxi trunking shall be fixed at site by fabricated clamp of 18 SWG GI sheet or as advised by site-engineer at a distance not more than 1.5 meters by machine screw/GI nut bolts, washers etc. The existing power cables shall be laid in the PVC Maxi trunking properly dressed and secured by means of suitable clamps/fasteners etc. | — | — | — | 1,97,800 | |
| — | 2450.00 | — | — | ||
| Laying of cable in trench - The price shall cover for laying, testing and commissioning of LTUG armoured cable in existing trench/pipe and its connection at both ends. The cable shall be tested with 500 Volt Megger earth tester before laying it in the trench. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to this office as well as site in-charge after laying of cable. Cables shall be supplied by railways at site engineer's stores. | — | — | — | 51,450 | |
| — | 1250.00 | — | — | ||
| Laying of cable on wall/cover shed/existing tray with MS clamp - The price shall cover for laying, testing and commissioning of LTUG armoured cable on wall/cover shed/in existing tray and its connection at both ends. The cable shall be tested with 500 Volt Megger before laying it in the tray. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to site engineer and Divisional Office after laying of cable. | — | — | — | 38,750 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing and commissioning of 5.0 meter height G.I. street light octagonal pole, single arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0 meter height single arm, G.I. street light octagonal pole as per the specifications mentioned in Annexure-XXI of tender document. | — | — | — | 1,22,460 | |
| — | 5.00 | — | — | ||
| Supply, fixing, testing and commissioning of 5.0 meter height G.I. street light octagonal pole, double arm complete with all accessories and foundation - The price shall cover for supply, erection and commissioning of 5.0 meter height double arm, G.I. street light octagonal pole as per the specifications mentioned in Annexure-XXI of tender document. | — | — | — | 67,700 | |
| — | 1.00 | — | — | ||
| — | 400.00 | — | — | ||
| — | 150.00 | — | — | ||
| — | 5.00 | — | — | ||
| — | 25.00 | — | — | ||
| — | 350.00 | — | — | ||
| — | 19.00 | — | — | ||
| Providing maintenance free earthing - The price shall cover for providing maintenance free earthing as per the following specifications - 1.High tensile-low carbon steel rod having diameter not less than 17 mm complying with requirements of BS 4360 Grade 43A or EN10025:2-004 S275JR, molecularly bonded by 99.99% pure high conductivity copper on outer surface with copper coating thickness of 250 micron or more, Length 3000 mm (minimum). Certificates from NABL approved labs shall be submitted with test results.2.Copper earth bus-bar of size 250 mm x 50 mm x 6 mm having electrical conductivity of 101% IACS, minimum 99.9% copper content shall be exothermically welded to rod with 4 holes of 12 mm diameter (two on each side) for connecting earthing conductor.3.Earth Enhancement compound should have characteristics as mentioned in the RDSO specifications. It should have low resistivity preferably below 0.2 Ohm-meter, supplied in sealed bags (minimum 75 kg per pit for 5' x 5' x 10' size pit and minimum 50 kg per pit for 300 mm bore type pit. The bags shall be marked with manufacturer's name or trade name, quality, Batch No. and date of manufacture. Certificates from NABL approved labs shall be submitted with test results, for at least following parameters - i)Composition of Earth Enhancement compoundii)Resistivity - < 2 Ohm-meteriii)pH value - > 7 but < 9iv)Moisture retaining capacity - > 10% at 105 degrees Celsiusv)Water solubility - < 5%4.Backfill material - Good quality soil or excavated soil free from sand, gravel and stones shall be used for backfilling.5.Earth pit of size 5 feet x 5 feet x 10 feet or min 300 mm bore up to 10 feet using earth auger shall be made.6.Inspection chamber - A concrete box of 300 x 300 x 300 mm (inside dimensions) and 50 mm thickness of wall, with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approximately 50 mm thick with pulling hooks shall be provided to cover the earth pit. PVC sleeve shall be provided in concrete wall to take out earthing connections.7.On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background.8.Instead of copper bus-bar and strips mentioned in the drawing, a GI main bus-bar of minimum size 300 mm x 75 mm x 8 mm to be installed on nearby wall etc. It shall be connected to earthing with two GI strips of 50 mm x 6 mm size each, up to a distance of 10 meters from earth bus-bar (minimum 3 meters x 2 Nos GI strips to be supplied).9.Earthing shall generally be carried out in accordance with the requirement of I.E. Rules, 1956, as amended from time to time and shall confirm to IS: 3043 of 1987 with latest amendment. 10.The earth value shall be measured and recorded at the site by painting on earth pit or nearest wall along with date of testing. It shall be less than 2 Ohms and neutral to earth voltage shall be less than 3 Volt.11.Earthing performance after a year of installation shall be jointly checked and measured. It should be less than 2 Ohm.12.General arrangement of the earth system shall be as the drawing given in Annexure-XXI of tender document. | — | — | — | 1,94,085 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TechSpecsofEnergyEfficientLEDBasedLuminaire.pdf
ATTACHMENT
RailwayBoardsletterNo.2018_CE-I_CT_9dated04.06.18.pdf
ATTACHMENT
WesternRailwaysSpecificationsforACBLTPanelsMCCBandMCB.pdf
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf
ATTACHMENT
BankGuaranteeverification.pdf
ATTACHMENT
TenderDocument-BRC-EL-P-19-2552-80-26-27NEWGCC.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].