Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAdmitted-Finance | ₹1.6 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.7 Cr+₹6.5 L (4.00%)Admitted-Finance | ₹1.7 Cr+₹6.5 L (4.00%) | L2 | Admitted-Finance |
| 3 | L3₹1.7 Cr+₹11.5 L (7.06%)Admitted-Finance | ₹1.7 Cr+₹11.5 L (7.06%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | BUHROO MECHANICAL PRIVATE LIMITED L3 | M/S JAY DEE ENTERPRISES L1 | M/S G. H. ENGINEERS L2 |
|---|---|---|---|---|---|---|
| 1.00Electrical Mechanical works (Stage 1st A) | ||||||
| 1.01 | Providing, fitting, installation, testing and commissioning of VT pumping unit of approved make with following specifications: at Stage 1st
Discharge of the Pump = 15000 GPH
Dynamic Head = 48 M
Speed = 1450 RPM
Working Voltage = 380 ± 15 V, 03 phase Rating = Corresponding to the head and discharge not less than 25 HP.
Rest of Specification/Details are as per clause 6 of Annexure "C" of SBD | 2 | job | 7,32,000 ₹14,64,000 | 6,82,500 ₹13,65,000 Lowest | 7,09,800 ₹14,19,600 |
| 1.02 | Providing/supplying and fitting of G.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) for Y junction and washout
Size : 150
Class: C (Heavy)
Rest of Specification as per clause 8 of Annexure "C" of SBD | 30 | Meters | 4,193 ₹1,25,790 | 3,919 ₹1,17,570 Lowest | 4,076 ₹1,22,280 |
| 1.03 | Cutting of hot dip galvanized GI , C-Class pipe acoss the section by dint of pipe cutter/gas cutter. The job includes providing and welding of M.S. Flanges to the two ends of Pipe. The Thickness of flange shall conform to IS 6392 Part 1st Table-17
Dia: 150`
Rest of Specification as per clause 11 of Annexure "C" of SBD | 30 | Job | 2,808 ₹84,240 | 2,624 ₹78,720 Lowest | 2,729 ₹81,870 |
| 1.04 | Fabrication , providing and fiting of Y- Junction having minimum 1m arm length of each arm to be fabricated out of G.I C class pipe with M.S. Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) Fastened with weld joints on three ends.
Dia: 150 mm
Rest of Specification as per clause 8 of Annexure "C" of SBD | 1 | Job | 7,810 ₹7,810 | 7,299 ₹7,299 Lowest | 7,591 ₹7,591 |
| 1.05 | Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units .
Size: DN150
PN:1.6/16 Rest of Specification/Details are as per clause 12 of Annexure "C" of SBD | 3 | No | 35,420 ₹1,06,260 | 33,103 ₹99,309 Lowest | 34,427 ₹1,03,281 |
| 1.06 | Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312.
Size: 150mm
PN: 1.6/16 Rest of Specification/Details are as per clause 13 of Annexure "C" of SBD | 2 | No | 43,911 ₹87,822 | 41,038 ₹82,076 Lowest | 42,680 ₹85,360 |
| 1.07 | Providing and fitting of 150 mm dia flanged flanged bends/elbolw to delivery mainfold and washout, including nuts and bolts and rubber gaskets as per requirement.
Rest of Specification/Details are as per clause 15 of Annexure "C" of SBD | 7 | job | 7,810 ₹54,670 | 7,299 ₹51,093 Lowest | 7,591 ₹53,137 |
| 1.08 | Providing and fitting of flanged Washout Tee 150 mm , including nuts,bolts and gasket as per site requirement.
Rest of Specification/Details are as per clause 09 of Annexure "C" of SBD | 1 | Job | 9,594 ₹9,594 | 8,966 ₹8,966 Lowest | 9,325 ₹9,325 |
| 1.09 | Supply installation , testing and commissioning of level II HT Transfromer
Capacity: 100 KvA
Rest of Specification/Details are as per clause 26 of Annexure "C" of SBD | 2 | Job | 3,42,400 ₹6,84,800 | 3,20,000 ₹6,40,000 Lowest | 3,32,800 ₹6,65,600 |
Tender Value
₹1.2 Cr
EMD Value
₹2.3 L
Closing Date
21 Dec 2022, 6:55 pmClosed
Exen Eng PHE Mech Div North Sopore
Exen Eng PHE Mech Div North Sopore
Electro-Mechanical works
2022_PHE_197223_3
PHE/MDNS/NIT/JJM/E-28 of 2022-23
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
Wadoora
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Yes
Exen Eng PHE Mech Div North Sopore
₹2.3 L
Yes
Exen Eng PHE Mech Div North Sopore
29 Jul 2023
23 Nov 2022
22 Dec 2022
23 Nov 2022
21 Dec 2022
24 Nov 2022
19 Dec 2022
Amount
Electrical Mechanical works (Stage 1st A)
Providing, fitting, installation, testing and commissioning of VT pumping unit of approved make with following specifications: at Stage 1st Discharge of the Pump = 15000 GPH Dynamic Head = 48 M Speed = 1450 RPM Working Voltage = 380 ± 15 V, 03 phase Rating = Corresponding to the head and discharge not less than 25 HP. Rest of Specification/Details are as per clause 6 of Annexure "C" of SBD
Providing/supplying and fitting of G.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) for Y junction and washout Size : 150 Class: C (Heavy) Rest of Specification as per clause 8 of Annexure "C" of SBD
Cutting of hot dip galvanized GI , C-Class pipe acoss the section by dint of pipe cutter/gas cutter. The job includes providing and welding of M.S. Flanges to the two ends of Pipe. The Thickness of flange shall conform to IS 6392 Part 1st Table-17 Dia: 150` Rest of Specification as per clause 11 of Annexure "C" of SBD
Fabrication , providing and fiting of Y- Junction having minimum 1m arm length of each arm to be fabricated out of G.I C class pipe with M.S. Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) Fastened with weld joints on three ends. Dia: 150 mm Rest of Specification as per clause 8 of Annexure "C" of SBD
Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units . Size: DN150 PN:1.6/16 Rest of Specification/Details are as per clause 12 of Annexure "C" of SBD
Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312. Size: 150mm PN: 1.6/16 Rest of Specification/Details are as per clause 13 of Annexure "C" of SBD
Providing and fitting of 150 mm dia flanged flanged bends/elbolw to delivery mainfold and washout, including nuts and bolts and rubber gaskets as per requirement. Rest of Specification/Details are as per clause 15 of Annexure "C" of SBD
Providing and fitting of flanged Washout Tee 150 mm , including nuts,bolts and gasket as per site requirement. Rest of Specification/Details are as per clause 09 of Annexure "C" of SBD
Supply installation , testing and commissioning of level II HT Transfromer Capacity: 100 KvA Rest of Specification/Details are as per clause 26 of Annexure "C" of SBD
9 m Long ST-410 SP33 pole Rest details as per clause 32 of Annexure "C" of SBD
Cement Bottoming 1:2:4 mix as per REC standards 0.5 cum/pole
G.I V cross with top Bracket including clamps Rest details as per clause 32 of Annexure "C" of SBD
11 KvA Polymeric Insulators 12 kV ,5kN , Lighting impulse 75 kV Positive and 80 kV Negative with creepage distance 320mm Rest details as per clause 31 of Annexure "C" of SBD
Galvanized nuts and bolts (1kg/pole) Rest details as per clause 33 of Annexure "C" of SBD
Danger plate with clamps Rest details as per clause 34 of Annexure "C" of SBD
Anti climbing Device with clamps Rest details as per clause 35 of Annexure "C" of SBD
Earthing complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip
Red Oxide coating Rest details as per clause 37 of Annexure "C" of SBD
Alumunium Paint coating Rest details as per clause 38 of Annexure "C" of SBD
Stone pad (300mm x300mm x75mm) Rest details as per clause of Annexure "C" of SBD
PG Clamps fo 50 sqmm ACSR conductor
ACSR conductor 50 sqmm Rest details as per clause 39 of Annexure "C" of SBD
GI Channel/Angle/Flat of sizes including clamps
11 KvA GO , AB Switch 3 Phase, 3 Pole, 200 A, Vertical Type Rest details as per clause 28 of Annexure "C" of SBD
11 kV polymeric composite Disc Insulator 12 kV, Min failing load 45kN, Lighting Impulse 75kV Positive and 80 kV Negative, creepage distance 320mm
Gapless Surge Arrrestor 9KV, 10 KA , LA with Polymer housing, Stn type Rest details as per clause 30 of Annexure "C" of SBD
50 sq mm (2 Ckt) 1.1 kV Grade, PVC Insulated Stranded Conductor FRLS Type
Earthing of substation- Rest details as per clause 48 of Annexure "C" of SBD
LT Distribution Box for 100 kVa DTR with 4 pole MCCB for incomer & SFU's for Outgoing circuits Rest details as per clause 42 of Annexure "C" of SBD
Galvanised stay set with 50x8mm stay clam, guy insulators(2No's), anchor plate (200x200x6mm), nuts and bolts, 2 Nos; turn-buckles, 1.8m long, 16mm dia meter solid GS stay rod & 7/3.15 mm dia GI Stranded wire complete Rest details as per clause 36 of Annexure "C" of SBD
Wedge connectors / PG Clamps Rest details as per clause 36 of Annexure "C" of SBD
Providing, installation, testing and commissioning of outdoor type HT Trivectometer as per IEE Rule. Job includes grouting of legs in cement concrete as per site requirement. All cabling, earthing and allied accessories required to be provided by the firm. Moreover firm responsible for completing all sealing of PDD department and testing on load and noload at site
Sundry items like Alumunium Lugs , Jumprs, binding Tape
35 sq mm AB(HT) Cable (3x35+1x70 sqmm) XLPE (11 kV , 3C+Earth) Rest details as per clause 41 of Annexure "C" of SBD
Heat Shrinkable Outdoor cable termination Kit Rest details as per clause 73 of Annexure "C" of SBD
Providing & Fitting of 35 sq mm Single Core Copper Conductor (Flexible) PVC Insulated Heavy Duty Industrial Cables (Unsheathed), 1100 Volts Conforming to IS: 694- for connecting motors from panel , stabilizers in rubber conduit . Job includes providing & laying of flexible conduit for cu cable with lugs as per requirement Heat Shrinkable Outdoor cable termination Kit Rest details as per clause 73 of Annexure "C" of SBD
Providing, installation ,testing of power service cable for working voltage up to and including 1100 volts; 70 sq mm armored aluminum 3.5 core cable as service line from output terminals of HT/LT transformer to cubical panel. Cost includes laying of cable in trenches in Pvc conduit where ever it is to be laid underground as per site requirement included is termination of ends with suitable Aluminum tube terminals dully crimpled & taped. Rest Specifications as per clause 68 of Annexure "C" of SBD
Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical Equipment. The cable connections terminal shall be fitted with copper thimbles of required size. The main specification of the cable is given below: Size: 16 sq mm Rest specification as per cluase "47" of Annexure "C" of SBD.
Providing , fitting, testing and commission of heavy duty de-silting pumping unit complete unit of capacity 25000 GPH head 25 m and motor including compete cabling, starter- 2nos(one as standby), Sluice valves ,agitator function, delivery pipe minimum 50 m with MS supports with all joints and accessories. Complete job Job includes fabrication , providing , fitting and testing of gantry system for fabricated out of ISCM/ISMB below machine floor of circular shape approx. 7 m dia. The gantry system should be fabricate in such a way that desilting pumping unit should move in all directions. Job includes providing and fitting of 2 MT chain pulley block (chain lift 10 m)and monorail of induff/globe make. the de-silting pumping have. . Job also includes making of hole and covering of the same with 8 mm thick MS sheet & ISA. Job also includes fabrication of Ladder and plate form at middle in ISA,ISMC for handling of the system
Providing, installation, testing and commissioning of 100 KVA Voltage Stabilizer Rest details & specification as per clause 44 of Annexure "C" of SBD
Fabrication Providing and fitting of 3 phase modular control panel. The technical details/ Ratings of various components of Modular Control Panel are given Below b. Main Circuit Breaker = 250 A c. Changeover Switch = 200 A d. Motor Breakup Protection MCCB = 200 A e. FASD starter - 2 units with rating Line contactor _AC3 110 A , Delta Contactor- AC3 110 A Star Contractor- AC3 90A Timer- Star Delta Electronic Thermal overload relay- with relay range 35-75 direct/CT operated suitable-range Aux coil voltage Wide Band fitted with seperate stabilization unit min 1KW Aux wiring f). Auxillary MCCB =63 Amp With S.C. Breaking Capacity of 36kA g). Motor Protection Relay suitable i) M-Power module for mobile starter & Earth fault relay j) Water level controller Rest of Deatils/Technical specification are as per clause 43 of Annexure "C" of SBD
Providing, installation and testing of Heavy Duty manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features Make = Reputed make Capacity = 3 ton (P) No. Of load chain falls = 2 or above Min. Height of lift = 6 M Rest details/ specification as per clause 24 of Annexure "C" of SBD
Illumination of Premises: Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole Rest of Deatils/Technical specification are as per clause 50 of Annexure "C" of SBD
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole , including MCB fiited in box 10A Rest details/ specification as per clause 51 of Annexure "C" of SBD
Providing and installation of Junction Box with DP 32Amp MCB to serve as amin switch for LED lighting including complete wiring min 20-30 m from panel board. Rest details/ specification as per clause 52 of Annexure "C" of SBD
Providing, Installation and testing of 2KVA fully automatic voltage stabilizer , including wiring Rest details/ specification as per clause 53 of Annexure "C" of SBD
Providing & fitting of lighting points for ( machine room , operators room,) as per site requirement in 1.5 mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit pipe by way, switches, socket modules , regulators ,indicators, 08/10 watt LED lamps Surface light Make. .Included is cost on account of modular switch boards with the wooden frames as per site requirements
Providing fitting of heating points in 2.5mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit by way of p / f of 15 Amp switches, 6 pin socket on modular fitting as per site requirements. Heating points are to be connected from main control panel. All accessories required is to be provided by the firm
Providing and fitting of 9” x 9”exhaust fan with complete wiring in 1.5 mm cu wire through conduit and 6 A modular control complete job. Make Providing and fitting of 9” x 9”exhaust fan with complete wiring in 1.5 mm cu wire through conduit and 6 A modular control complete job.
Providing, fitting of Distribution Board of reputed make 4 way S P N single door powder coated sheet steel enclosure for surface mounting fitted with bus bar, DIN channel, neutral link and incoming contact. the above DB is to be provided /fitted with double pole 40 amp MCB for Main. 32 A for heating circuit & rest 3 of 16/6 amps each for premises luminary, auxiliary circuit of reputed make. Further job includes providing / fitting 4 mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit as service line from main panel as per site requirements. Connections should be made in such a way Lighting points is to be connected via automatic transformer by way of p/f switch socket arrangement with allied fixtures & and heating points to main panel. Job includes dismantling of existing damaged conduit , wires, conduit and cleaning the surface properly
Earthing of Panel boad, stabilizer, Motors, heating points, lighting points, D.G sets Rest details as per clause 48 of Annexure "C" of SBD
Painting on steel structure/pipe with synthetic enamel paint of approved brand and maufacturer of required colour to give an even shade on new work( Two or more coats) including a coat of approved steel primer but excluding a coat of mordant solution. (ref 13.61) schedule2021
Providing , installation, testing and commissioning of 415+-10 V (out Put) , 3 phase DG Set of Specification of approved make as per latest guide line Capacity =62.5 KvA Rest details/specifications are as per clause 66 of Annexure "C" of SBD
Providing, installation ,testing of power service cable for working voltage up to and including 1100 volts; 95 sq mm armored aluminum 3.5 core cable as service line from output terminals of HT/LT transformer to cubical panel. Cost includes laying of cable in trenches in Pvc conduit where ever it is to be laid underground as per site requirement included is termination of ends with suitable Aluminum tube terminals dully crimpled & taped. Rest Specifications as per clause 67 of Annexure "C" of SBD
Fabrication, providing, fitting of base frame for pumping units , covering of holes , fabrication of gantry, ladder ,DG set covering, HT/Lt transformer Bed with gantry fabricated out of ISMC/ISMB/ISA/Bars/MS Pipe/MS plain-chequrred Sheets. Including making of holes in concrete, including metal primer 1 coat and two coats of approved shade . The works is to be executed as per site requirement and as per dimentions of Pumping unit and as per directions of site engineer. Rest of Specification/Details are as per clause 21 of Annexure "C" of SBD
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level 1:2:4 with stone aggregrate 20 mm nominal size. For DG Set foundatioin /concrete beds for rising-main as per requirement
Centering and shuttering including strutting, propping etc and removal of form work for foundation, footing , base
Earth work in excavation by manual means in trenches for foundations, drains , pipes , cables etc (Not exceeding 1.5 m in width) and ramming of bottoms lift 1.5 m , including getting out excavated earth and disposal of surplus exacavated earth as directed ( All kinds of soil) (2.81 schedule)
Providing and laying of soling stone
Cement plaster in find sand in 1:3 mix finished with a coat of neat cement and curing complete 18 mm thick. (s-11.8)
Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter with 12V, 180AH Tubular inverter Battery Rest details/ specification as per clause 54 of Annexure "C" of SBD
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen . Rest details/ specification as per clause 55of Annexure "C" of SBD
TOOL KIT For Maintenance: - The Tool Kit for maintenance as per detailed specification in clause 56 of Annexure "C" of SBD
Providing of good quality conveinence and utility items as per details in clause 57 of Annexure "C" of SBD
Fabrication of 6’ x 6’ angle iron bed for operators. Rest details/ specification as per clause 58 of Annexure "C" of SBD
Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet , 2 nos. Rest details/ specification as per clause 59 of Annexure "C" of SBD
Providing of solar/ electrical lantern chargeable on both solar & electrical 220v supply. Rest details/ specification as per clause 60 of Annexure "C" of SBD
Providing of bamboo ladder 18 feet long with 15 feet long link rods and HT gloves pair (01 each) Rest details/ specification as per clause 61 of Annexure "C" of SBD
Providing of 1 KW heat convector for operators for winter season. Rest details/ specification as per clause 62 of Annexure "C" of SBD
Providing and fitting of 01 No. LED (scroll type) sign board fabricated out of stainless steel and metal Rest of Deatils/Technical specification are as per clause 63 of Annexure "C" of SBD
Providing and fitting of 01 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipments installed at site. The legs are to be grouted in cement concrete. Rest of Deatils/Technical specification are as per clause 64 of Annexure "C" of SBD
Providing corrugated G.S Sheet roofing including vertical/ curved surface fixed with polymer coated J or L Hooks , bolts and nuts for DG Set and overhead gantry Rest of Deatils/Technical specification are as per clause 68 of Annexure "C" of SBD
Stage 2nd
Providing, fitting, installation, testing and commissioning of Hz pumping unit of approved make with following specifications: at Stage 2nd Discharge of the Pump = 14000 GPH Dynamic Head = 40 M , with head range 25-50 Speed = 1450 RPM Working Voltage = 380 ± 15 V, 03 phase Rating = Corresponding to the head and discharge not less than 20 HP. Rest of Specification/Details are as per clause 5 of Annexure "C" of SBD
Providing/supplying and fitting of G.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) for Y junction and washout Size : 150 Class: C (Heavy) Rest of Specification as per clause 8 of Annexure "C" of SBD
Cutting of hot dip galvanized GI , C-Class pipe acoss the section by dint of pipe cutter/gas cutter. The job includes providing and welding of M.S. Flanges to the two ends of Pipe. The Thickness of flange shall conform to IS 6392 Part 1st Table-17 Dia: 150` Rest of Specification as per clause 11 of Annexure "C" of SBD
Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units . Size: DN150 PN:1.6/16 Rest of Specification/Details are as per clause 12 of Annexure "C" of SBD
Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312. Size: 150mm PN: 1.6/16 Rest of Specification/Details are as per clause 13 of Annexure "C" of SBD
Providing and fitting of 150 mm dia flanged flanged bends/elbolw to delivery mainfold and washout, including nuts and bolts and rubber gaskets as per requirement. Rest of Specification/Details are as per clause 15 of Annexure "C" of SBD
Providing and fitting of flanged Washout Tee 150 mm , including nuts,bolts and gasket as per site requirement. Rest of Specification/Details are as per clause 09 of Annexure "C" of SBD
Providing/supplying and fitting of G.I flanged Pipe at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) for suction Size : 100 Class: C (Heavy) Rest of Specification as per clause 8 of Annexure "C" of SBD
Cutting of hot dip galvanized GI , C-Class pipe acoss the section by dint of pipe cutter/gas cutter. The job includes providing and welding of M.S. Flanges to the two ends of Pipe. The Thickness of flange shall conform to IS 6392 Part 1st Table-17 Dia: 100` Rest of Specification as per clause 11 of Annexure "C" of SBD
Providing and fitting of 100 mm dia flanged flanged bends/elbolw to suction side/at site, including nuts and bolts and rubber gaskets as per requirement. Rest of Specification/Details are as per clause 15 of Annexure "C" of SBD
Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312. Size: 100mm PN: 1.6/16 Rest of Specification/Details are as per clause 13 of Annexure "C" of SBD
Supply installation , testing and commissioning of level II HT Transfromer Capacity: 100 KvA Rest of Specification/Details are as per clause 26 of Annexure "C" of SBD
9 m Long ST-410 SP33 pole Rest details as per clause 32 of Annexure "C" of SBD
Cement Bottoming 1:2:4 mix as per REC standards 0.5 cum/pole
G.I V cross with top Bracket including clamps Rest details as per clause 32 of Annexure "C" of SBD
11 KvA Polymeric Insulators 12 kV ,5kN , Lighting impulse 75 kV Positive and 80 kV Negative with creepage distance 320mm Rest details as per clause 31 of Annexure "C" of SBD
Galvanized nuts and bolts (1kg/pole) Rest details as per clause 33 of Annexure "C" of SBD
Danger plate with clamps Rest details as per clause 34 of Annexure "C" of SBD
Anti climbing Device with clamps Rest details as per clause 35 of Annexure "C" of SBD
Earthing complete by GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip
Red Oxide coating Rest details as per clause 37 of Annexure "C" of SBD
Alumunium Paint coating Rest details as per clause 38 of Annexure "C" of SBD
Stone pad (300mm x300mm x75mm) Rest details as per clause of Annexure "C" of SBD
PG Clamps fo 50 sqmm ACSR conductor
ACSR conductor 50 sqmm Rest details as per clause 39 of Annexure "C" of SBD
GI Channel/Angle/Flat of sizes including clamps
11 KvA GO , AB Switch 3 Phase, 3 Pole, 200 A, Vertical Type Rest details as per clause 28 of Annexure "C" of SBD
11 kV polymeric composite Disc Insulator 12 kV, Min failing load 45kN, Lighting Impulse 75kV Positive and 80 kV Negative, creepage distance 320mm
Gapless Surge Arrrestor 9KV, 10 KA , LA with Polymer housing, Stn type Rest details as per clause 30 of Annexure "C" of SBD
50 sq mm (2 Ckt) 1.1 kV Grade, PVC Insulated Stranded Conductor FRLS Type
Earthing of substation- Rest details as per clause 48 of Annexure "C" of SBD
LT Distribution Box for 100 kVa DTR with 4 pole MCCB for incomer & SFU's for Outgoing circuits Rest details as per clause 42 of Annexure "C" of SBD
Galvanised stay set with 50x8mm stay clam, guy insulators(2No's), anchor plate (200x200x6mm), nuts and bolts, 2 Nos; turn-buckles, 1.8m long, 16mm dia meter solid GS stay rod & 7/3.15 mm dia GI Stranded wire complete Rest details as per clause 36 of Annexure "C" of SBD
Wedge connectors / PG Clamps Rest details as per clause 36 of Annexure "C" of SBD
Providing, installation, testing and commissioning of outdoor type HT Trivectometer as per IEE Rule. Job includes grouting of legs in cement concrete as per site requirement. All cabling, earthing and allied accessories required to be provided by the firm. Moreover firm responsible for completing all sealing of PDD department and testing on load and noload at site
Sundry items like Alumunium Lugs , Jumprs, binding Tape
35 sq mm AB(HT) Cable (3x35+1x70 sqmm) XLPE (11 kV , 3C+Earth) Rest details as per clause 41 of Annexure "C" of SBD
Heat Shrinkable Outdoor cable termination Kit Rest details as per clause 73 of Annexure "C" of SBD
Providing & Fitting of 35 sq mm Single Core Copper Conductor (Flexible) PVC Insulated Heavy Duty Industrial Cables (Unsheathed), 1100 Volts Conforming to IS: 694- for connecting motors from panel , stabilizers in rubber conduit . Job includes providing & laying of flexible conduit for cu cable with lugs as per requirement Heat Shrinkable Outdoor cable termination Kit Rest details as per clause 73 of Annexure "C" of SBD
Providing, installation ,testing of power service cable for working voltage up to and including 1100 volts; 70 sq mm armored aluminum 3.5 core cable as service line from output terminals of HT/LT transformer to cubical panel. Cost includes laying of cable in trenches in Pvc conduit where ever it is to be laid underground as per site requirement included is termination of ends with suitable Aluminum tube terminals dully crimpled & taped. Rest Specifications as per clause 68 of Annexure "C" of SBD
Providing, installation, testing and commissioning of 75 KVA Voltage Stabilizer Rest details & specification as per clause 44 of Annexure "C" of SBD
Fabrication Providing and fitting of 3 phase modular control panel. The technical details/ Ratings of various components of Modular Control Panel are given Below b. Main Circuit Breaker = 250 A c. Changeover Switch = 200 A d. Motor Breakup Protection MCCB = 160 A e. FASD starter - 2 units with rating Line contactor _AC3 90 A , Delta Contactor- AC3 90 A Star Contractor- AC3 70A Timer- Star Delta Electronic Thermal overload relay- with relay range 20-50 direct/CT operated suitable-range Aux coil voltage Wide Band fitted with seperate stabilization unit min 1KW Aux wiring f). Auxillary MCCB =63 Amp With S.C. Breaking Capacity of 36kA g). Motor Protection Relay suitable i) M-Power module for mobile starter & Earth fault relay j) Water level controller Rest of Deatils/Technical specification are as per clause 43 of Annexure "C" of SBD
Providing, installation and testing of Heavy Duty manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features Make = Reputed make Capacity = 3 ton (P) No. Of load chain falls = 2 or above Min. Height of lift = 6 M Rest details/ specification as per clause 24 of Annexure "C" of SBD
Illumination of Premises: Providing and erection of 9 Mtr long Hot Dip Galvanized octagonal pole Rest of Deatils/Technical specification are as per clause 50 of Annexure "C" of SBD
Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole , including MCB fiited in box 10A Rest details/ specification as per clause 51 of Annexure "C" of SBD
Providing and installation of Junction Box with DP 32Amp MCB to serve as amin switch for LED lighting including complete wiring min 20-30 m from panel board. Rest details/ specification as per clause 52 of Annexure "C" of SBD
Providing, Installation and testing of 2KVA fully automatic voltage stabilizer , including wiring Rest details/ specification as per clause 53 of Annexure "C" of SBD
Providing & fitting of lighting points for ( machine room , operators room,) as per site requirement in 1.5 mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit pipe by way, switches, socket modules , regulators ,indicators, 08/10 watt LED lamps Surface light Make. .Included is cost on account of modular switch boards with the wooden frames as per site requirements
Providing fitting of heating points in 2.5mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit by way of p / f of 15 Amp switches, 6 pin socket on modular fitting as per site requirements. Heating points are to be connected from main control panel. All accessories required is to be provided by the firm
Providing and fitting of 9” x 9”exhaust fan with complete wiring in 1.5 mm cu wire through conduit and 6 A modular control complete job. Make Providing and fitting of 9” x 9”exhaust fan with complete wiring in 1.5 mm cu wire through conduit and 6 A modular control complete job.
Providing, fitting of Distribution Board of reputed make 4 way S P N single door powder coated sheet steel enclosure for surface mounting fitted with bus bar, DIN channel, neutral link and incoming contact. the above DB is to be provided /fitted with double pole 40 amp MCB for Main. 32 A for heating circuit & rest 3 of 16/6 amps each for premises luminary, auxiliary circuit of reputed make. Further job includes providing / fitting 4 mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit as service line from main panel as per site requirements. Connections should be made in such a way Lighting points is to be connected via automatic transformer by way of p/f switch socket arrangement with allied fixtures & and heating points to main panel. Job includes dismantling of existing damaged conduit , wires, conduit and cleaning the surface properly
Earthing of Panel boad, stabilizer, Motors, heating points, lighting points, D.G sets Rest details as per clause 48 of Annexure "C" of SBD
Painting on steel structure/pipe with synthetic enamel paint of approved brand and maufacturer of required colour to give an even shade on new work( Two or more coats) including a coat of approved steel primer but excluding a coat of mordant solution. (ref 13.61) schedule2021
Providing , installation, testing and commissioning of 415+-10 V (out Put) , 3 phase DG Set of Specification of approved make as per latest guide line Capacity =40 KvA Rest details/specifications are as per clause 66 of Annexure "C" of SBD
Providing, installation ,testing of power service cable for working voltage up to and including 1100 volts; 70 sq mm armored aluminum 3.5 core cable as service line from output terminals of HT/LT transformer to cubical panel. Cost includes laying of cable in trenches in Pvc conduit where ever it is to be laid underground as per site requirement included is termination of ends with suitable Aluminum tube terminals dully crimpled & taped. Rest Specifications as per clause 67 of Annexure "C" of SBD
Fabrication, providing, fitting of base frame for pumping units , covering of holes , fabrication of gantry, ladder ,DG set covering, HT/Lt transformer Bed with gantry fabricated out of ISMC/ISMB/ISA/Bars/MS Pipe/MS plain-chequrred Sheets. Including making of holes in concrete, including metal primer 1 coat and two coats of approved shade . The works is to be executed as per site requirement and as per dimentions of Pumping unit and as per directions of site engineer. Rest of Specification/Details are as per clause 21 of Annexure "C" of SBD
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level 1:2:4 with stone aggregrate 20 mm nominal size. For DG Set foundatioin /concrete beds for rising-main as per requirement
Centering and shuttering including strutting, propping etc and removal of form work for foundation, footing , base
Earth work in excavation by manual means in trenches for foundations, drains , pipes , cables etc (Not exceeding 1.5 m in width) and ramming of bottoms lift 1.5 m , including getting out excavated earth and disposal of surplus exacavated earth as directed ( All kinds of soil) (2.81 schedule)
Providing and laying of soling stone
Cement plaster in find sand in 1:3 mix finished with a coat of neat cement and curing complete 18 mm thick. (s-11.8)
Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter with 12V, 180AH Tubular inverter Battery Rest details/ specification as per clause 54 of Annexure "C" of SBD
Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen . Rest details/ specification as per clause 55of Annexure "C" of SBD
TOOL KIT For Maintenance: - The Tool Kit for maintenance as per detailed specification in clause 56 of Annexure "C" of SBD
Providing of good quality conveinence and utility items as per details in clause 57 of Annexure "C" of SBD
Fabrication of 6’ x 6’ angle iron bed for operators. Rest details/ specification as per clause 58 of Annexure "C" of SBD
Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet , 2 nos. Rest details/ specification as per clause 59 of Annexure "C" of SBD
Providing of solar/ electrical lantern chargeable on both solar & electrical 220v supply. Rest details/ specification as per clause 60 of Annexure "C" of SBD
Providing of bamboo ladder 18 feet long with 15 feet long link rods and HT gloves pair (01 each) Rest details/ specification as per clause 61 of Annexure "C" of SBD
Providing of 1 KW heat convector for operators for winter season. Rest details/ specification as per clause 62 of Annexure "C" of SBD
Providing and fitting of 01 No. LED (scroll type) sign board fabricated out of stainless steel and metal Rest of Deatils/Technical specification are as per clause 63 of Annexure "C" of SBD
Providing and fitting of 01 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipments installed at site. The legs are to be grouted in cement concrete. Rest of Deatils/Technical specification are as per clause 64 of Annexure "C" of SBD
Providing corrugated G.S Sheet roofing including vertical/ curved surface fixed with polymer coated J or L Hooks , bolts and nuts for DG Set and overhead gantry Rest of Deatils/Technical specification are as per clause 68 of Annexure "C" of SBD
M/S G. H. ENGINEERS
BUHROO MECHANICAL PRIVATE LIMITED
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.74 MB
BOQ_524213.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .