REPAIR MAINT OF UNSV LT CIRCUIT BREAKERS INCLUDING ACB MCCBs LT UNDERGROUND CABLE NETWORK AND STREET LIGHTS INCLUDING ALLIED WORKS AT SECTOR A AND B UNDER GE UTILITY AMBALA CANTT
2022_MES_554555_1
CA NO GE U AMB T 42 OF 2022-23
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹90,000
15 Nov 2022
27 Sept 2022
28 Oct 2022
27 Sept 2022
26 Oct 2022
12 Oct 2022
27 Sept 2022 - 4 Oct 2022
Amount
Dismantling and taking down security light, street light, hanger light, flood light and high mast lights of any type at any height fittings such as HPSV/HPMV/MH/LED light of 48 Watt, 60 watt 70/72 watt, 90 watt, 120 watt, 150 watt, 200 watt and 300 watt of any make etc. AC 230 volts any wattage from pole/wall roof top/hanger roof including washing/cleaning of perplex cover inspection for location of fault and replacing of defective speare/parts required for smooth functioning, tighting of electric connection complete and assembling and reconnecting all as per site requirment all as specified and directed. Note: Defective spares/parts of relevant light fitting shall be measured and paid separately under relevant item as supply only.
Supply only LED electronic driver/adaptor/SPD for 40-48 watt LED security light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 60 watt LED security light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 70/72 watt LED security light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 90 watt LED security light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 120 watt LED security light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 60-150 watt LED flood light fitting of existing make all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 200-300 watt LED flood light fitting of existing make all as specified and directed.
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locating fault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed.
All as per Item Ser No 9.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre.
Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Material and labour sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and directed.
Supply and lay bricks, common burnt clay, sub class "B', old size, laid in vertical direction to cable as cable protection complete all as specified and directed.
All as per Item Ser No 14.00 here in before but except bricks, all as specified and directed. Note:- Old bricks retrieved from Item Ser No 18 & 19 here in after shall be re-used.
Material and labour PCC 1:4:8 type D-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in pole pit and foundation etc. complete all as specified and directed.
Material and labour cement concrete (1:3:6) type C-1 using 20mm graded crushed stone aggregate as in coping of pole and strut, stay around the pole etc complete all as specified and directed.
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault, rectify the defect and relaying the same cable 1100 volts including connecting and testing for any size complete as directed by Engineer-in-Charge (Excavation/earth work & sand cushioning, bricks and joint shall be measured & paid separately).
Disconnecting & taking out defective underground cable of any size and any type from trenches, pole, pipe, floor, wall etc.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall etc. Note: (i) Earth work, sand, bricks, removal , returning filling, Aluminium thimbles/lugs will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates (iii) All equiments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per item ser No 20 here in before but for 3.5 core 25 Sqmm
All as per item ser No 20 here in before but for 3.5 core 35 Sqmm
All as per item ser No 20 here in before but for 3.5 core 50 Sqmm
All as per item ser No 20 here in before but for 3.5 core 70 Sqmm
All as per item ser No 20 here in before but for 3.5 core 95 Sqmm
All as per item ser No 20 here in before but for 3.5 core120 Sqmm
All as per item ser No 20 here in before but for 3.5 core185 Sqmm
All as per item ser No 20 here in before but for 3.5 core 300 Sqmm
Supplying and fixing in replacement of 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed.
Supply and fixing in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 3 core 2.5 sqmm copper cable including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed. Make - Havells (HSN CODE: 8544, basic code WHMFDSKB32X5) .
Supply and fixing in replacement or passing through PVC conduit pipe of 1100 volts grade heavy duty, PVC insulated round 5 core 2.5 sqmm copper cable including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed. Make - Havells (HSN CODE: 8544, basic code WHMFDSKB52X5).
Supply and fixing in replacement or passing through PVC conduit pipe of single core PVC unsheathed multi stranded copper cable (FRLS) 1.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed.
Supply and fixing in replacement or passing through PVC conduit pipe of single core PVC unsheathed multi stranded copper cable (FRLS) 2.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs,nuts and bolts complete all as specified and directed.
Supply and fixing in replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. Note : PVC pipe will be clamped at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates. complete all as specified and directed.
Supplying and fixing in replacement of light grade galvanised mild steel pipe 80mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitable mild steel clamps , bolts , nuts and washers all as specified and directed. Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule.
All as per Item No 28.00 here-in-before but of size 50 mm bore.
Dismantling and taking down old unsv PCC LT pole and Supply, fix and erection of PCC pole 9.0 mtr long in true vertical position 102x172 mmm at top 102x279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified and as directed by Engr-in-Charge. Note:- (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Dismantling and taking down old unsv Steel tublar LT pole and Supply, fix and erection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31 , 09 meter long, providing synthetic enamel aluminium paint over one coat of red oxide and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr above the coping of pole starting with black strip, incl arrangement of galvanised/Mild steel circular lantern carriage arrangement suitable for 5 luminares symmetrically on steel tubular poles complete all as specified and directed by Engr-in-Charge. Note:- (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply and fixing in replacement of stay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv complete and directed. Note: loop type insulator, stay clamps, excavation and concrete measured and paid separately.
Material and labour in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mm x 140mm, clearance of hole 25.5 mm, Complete all as specified and directed.
Material and labour in replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed by Engineer-in-Charge.
Material and labour in replacement for pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm height and 65 mm dia with GI spindle two washer and one GI nut complete all as specified and directed by Engineer-in-Charge.
Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as per direction of Engr-in-charge.
Material and labour for aluminium conductor steel reinforced (ACSR) conductor of size 6/1 x 2.59 (Weasel) and 6/1 x 2.11 (Squirrel) ISI marked for LT over head lines on poles including stretching, tightening of insulator with winding wire of suitable size all as specified and directed by Engineer-in-Charge.
Dismantling and taking down of old unserviceable cross-arms of M.S. channel or angle sections etc. complete incl cutting, welding complete all as per direction of Engr-in-charge.
Material and labour in replacement of cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primercoat, one under coat and one finishing coat of enamel paint complete all as specified and directed.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-120 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 150-300 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-120 Sqmm complete all as directed by Engr-in-Charge.
Supply and fixing straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 150-300 Sqmm complete all as directed by Engr-in-Charge.
Dismantling and taking down old u/s earthing complete with galvanised earth plate electrode 600mm x 600mm x 6mm thick surrounded by charcoal and salt, buried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 32x6 mm GI strip earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GI protection pipe (light grade), funnel, wire mesh, cast iron cover and frame etc, complete, all as specified or indicated and as directed including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
Dismantling and taking down old u/s earthing complete with galvanized steel plate earth electrode 600mm x 600mm x 6mm thick surrounded by charcoal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part - I including testing complete all as specified and as directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
Material and Labour epoxy brushable insulated compound used as an insulation material in electrical poles, stays and other electrical appliances etc, the inslulation compound to produce void free insulation around the components including removing rusted particles, painting with two coats of epoxy brushable insulated compound over a coat of red oxide primer complete all as specified and directed. Note: The quoted rate shall be included for all types of adhesive which will be used in insulated compound to ready for paint.
Material and Labour insulation cover for overhead conductor of medium voltage wrap around line cover to provide retrofit insulation with overhead conductors to prevent electrical fault caused by trees or wildlife creatures coming in the contact of distribution lines high quality non tracking polyolefin material. Installation shall be easy by using the split insulation tube tool complete all as specified and directed. Note: Accessories of insulation for OH Lines shall be included in quoted rates.
Supply and fixing in replacement MCCB TPN 500 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload and short circuit adjustable type with microprocessor based control incl complete connection with spreader links all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 400 Amps, 415 Volts, 36 KA,4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type microprocessor based control incl complete connection with spreader links all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 250 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload and short circuit adjustable type microprocessor based control incl complete connection with spreader links all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 160 Amps, 415 Volts, 25 KA,4 pole , Ics=100% Icu, overload and short circuit adjustable type microprocessor based control incl complete connection with spreader links all as per direction of Engr-in-Charge.
Supply and fixing in replacement MCCB TPN 100 Amps, 415 Volts, 16/18 KA,4 pole , Ics=100% Icu, overload and short circuit adjustable type microprocessor based control incl complete connection with spreader links all as per direction of Engr-in-Charge.
M&L for Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT/LT (11 KV/430 Volts) serviceable to cable with Straight through joint of size 70-300 Sqmm. Note:- (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges demed to be included in the quoted rate. (b) Charge of cable fault locator and DG set including transportation charge deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will be levied Rs 500/ per hour. (d) Straight through joint , 95 to 185, sqmm, Labour charges, excavation and making joint deemed to be including in quoted rate.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 4 line as per IS complete as per direction of Engr-in-Charge.
Supply and fixing LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 3 line as per IS complete as per direction of Engr-in-Charge.
Re-streching of loose/over sagging over head ACSR conductor of any type/GI wire and repair of the broken conductors and adding new length( if required) in place of old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire all as specified. (Old conductor shall be reused where required for repairing broken length of conductor as directed by Engr-in-charge). Note:- Five lines of conductor together will be measured as one span from pole to pole.
Trimming of Tree branches falls into OH lines of HT/LT & minimum clearance of 3 Mtr from branches ,proper shutdown will be taken and maintained in the register complete all as specified and directed.
Material and labour in replacement of aluminium terminals (thimbles) after cutting the worn out/faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugs including crimping with crimping tools in the existing LT cable 25 Sqmm 4 core upto 50 Sqmm including necessary connection all as specified and directed.
All as per item ser No 67 here in before but size of LT cable 70 Sqmm 3.5 core upto 120 Sqmm 3.5 core.
All as per item ser No 67 here in before but size of LT cable 150 Sqmm 3.5 core upto 300 Sqmm 3.5 core.
Material and labour for shifting heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete all as specified and directed.
Material & Labour for repair of LT panel of any type and any size including replace of old unsv items such as busbar, insulator, CT/PT coils, insulating sleeves, front and rear doors, door hinges, gland, lugs, volt meter, ammeter, indicator, locking arrangement and internal copper wiring after cleaning of surface including removing rusted particles, removing dust, tightening of nut, bolts, welding and painting on complete panel with two coats of synthetic enamel aluminium paint over a coat of red oxide including stand complete all as directed. Note: (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate. (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. (iii) Cost of welding works such as hinges, locking arrangement, door and angles are included in qouted rates.
Material & Labour for surface cleaning of LT steel tubular poles 9 mtrs long including removing rusted particles, painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including stand cross arms, bracing, supports,clamps eye hooks, security light bracket, clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint incl repairing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC
Material & Labour for cement base paint for PCC pole 9 mtr including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer including cross arms, bracing supports, clamps, eye hooks, security light bracket, clamp etc incl repairing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC
Material and labour for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge.
Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 200 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 315 Amps capacity fixed on walls/MS frame/pole/LT panel for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
M&L Chemical spray (DC>2.26 having container 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisam cleanese etc complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacementnof junction box shall be insulated and made out of polycarbonate with glass fiber reinforced. The size in mm should be not less then 225 X 295 X 112 cat. part no KF350B. The polycarbonate Junction box shall be environment friendly, recyclable, UV resistant, halogen & silicon free, anti acid & anti corrosive. The Junction jox shall be rated for degree of Ingress protection IP 66/67 in accordance with IEC 60529. The gasket material shall be polyurethane and the gasket shall be internally embedded. The Junction box shall be complies with requirements of the standards IEC 60998-1, IEC 60998-2-1, IEC 60670 –22 & IEC 60670 – 2-5. The manufacturer of junction box shall submit a copy of IEC certificate. For better safety the polycarbonate enclosure shall be fire retardant & self-extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 Part 3, UL subject 94 for flammability V-2. It should be tested at glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08 including 6 amp MCB and mounting clamp complete all as specified and directed. Make:- Hensel/Siemens/Rittal. Manufacturer should submit routine test certificate for CJB/PJB.
Supply & fixing in replacement of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32 Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Madel :Swadeep-02EC-8kW3P-VMS complete all as specified and directed. Note (i) S S Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years. (iii) The test certificate and warranty certificate must be provided by supplier.(iv) Cost of marking description on the box is incl quoted rate.
Supply & fixing in replacement of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS). Madel : Swadeep-02EC-5kW1P-VMS complete all as specified and directed. Note (i) Nut bolts, clamp for fixing on poles/wall are to be included in quoted rates. (ii) The sensor must have the warranty of min of 2 years . (iii) The test certificate and warranty certificate must be provided by supplier.(iv) Cost of marking description on the box is incl quoted rate.
Supply and fix in replacement of Lithium based Energy Efficient Integrated Solar Street Light of 32 Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 64/66Wp , Lithium Battery 11.1/12.8V, 33.0AH with inbuilt BMS, IP 65, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700K - 6500K, Microcontroller based charge controller cum driver, automatic dimming function (first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10C to (+)55C, weight not more than 16-18kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 6 mtr height with bottom base plate 200x200x12 mm, outdoor dia not less than 65 mm with heavy duty GI Pipe or steel thickness 3 mm and suitable arrangement to mount solar light as directed on pole including foundation and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed Make:- Axxon (AXN-32W) or equivalent of Phillips/Bajaj/wipro/havells
Supply & fixing in replacement of Integral LED Flood light Luminaries 80 Watts consisting of suitable number of LEDs and mounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens, IP 66 protection suitable for mast light mounting, 5700K, LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV , Confirm the tests from auth labs : LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge.
Supply & fixing in replacement of Integral LED Flood light Luminaries 150 Watts consisting of suitable number of LEDs and mounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens, IP 66 protection suitable for mast light mounting, 5700K, LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV , Confirm the tests from auth labs : LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl made proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge.
Supply & fixing in replacement of Integral LED Flood light Luminaries 200 Watts consisting of suitable number of LEDs and mounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens, IP 66 protection suitable for mast light mounting, 5700K, LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV , Confirm the tests from auth labs : LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl made proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge.
Supply & fixing in replacement of LED street light fitting 60 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs : LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole and provide facility of power supply shall be provide as suitable for maint work of light fittings incl made proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to street Light shall be measured and paid separately.
Supply & fixing in replacement of LED street light fitting 70 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs : LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole incl made proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to street Light shall be measured and paid separately.
Supply & fixing in replacement of LED street light fitting 90 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded PC cover/ toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs : LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole incl made proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as directed by Engineer-in-charge. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to street Light shall be measured and paid separately.
Supply and installing, testing & commissioning in replacement of factory fabricated outdoor type feeder pillar board of size 700X600X500 mm , outer shell made out of 3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alloy (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/openable with arrangement of pad lock on door 01 no of pad lock of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coated painting after 7-tank pre treatement control & power wiring with suitable size of copper conductor along with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011 Part-1 and part -2 type test certificate with not less than IP-56 and breaking capacity 65 KA comprising of the following :- (a) MCCB 125 Amps TPN, 25 KA -01 No (b) Copper busbar of capacity 200 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four. (c) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc complete are included in quoted rates
Notes for item Sr No. 89 to 93 (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/GE. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland. (vi) Cost of marking description and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
M&L for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 50-95 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
M&L for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 120-185 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as directed by Engr-in-charge .
Material and labour in replacement of broken earth pit of size 300x300x300 mm made of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars, earthing marked with indication @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result all as specified and directed.
Material and labour in repairs of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire all as specified and directed.
Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) of size 600X600X300mm including form work and applying two coats of white wash all as specified and directed.
Taking down old unserviceable Indicator any type any colour and supply and fixing new Indicator red/yellow/green including making electrical connection with suitable size of copper lugs duly crimped complete all as specified and directed.
M&L for Brick work with subclass 'B' bricks, straight or curved on plan exc 6m mean radiusbuilt in CM 1:6. complete all as specified as directed including taking down old brick work.
M&L for rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:4 finishing the surface fair and even smooth without using extra cement all as specified directed.
M&L for preparation and applying three coats of white wash on new plastered surface of wall complete all as specified as directed.
Material & Labour for in replacement of steel nuts, bolts, washers of any size required at site as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment Fe-290 (Gde E- 165) for existing LT panel doors/gates complete all as specified and directed.
Material & Labour for disconnecting and connecting of LT service wires and XLPE cables of any type and any size from LT panel, MCCBs, DBs, over head conductor, LT poles, street light timer including replacement of old unsv items such as nuts, bolts, thimbles, insulating sleeves and existing misc items etc, and after cleaning and removing of carbon on cables end surface including removing rusted particles, removing dust tightening of nut, bolts complete all as directed. Note: (i) Cost of all tools and ladder required for maintenanne of LT service wires and XLPE cable end connection and disconnection is incl in quoted rate (ii) Cost of misc items like nuts, bolts, thimbles, insulating sleeves etc if required are included in quoted rates.
Supply and fixing in replacement of nature switch operation should be based on natural light lux level, required illuanance level for switching on is <30 Lux and for switching off >10 lux , the sensor should also have part night operation facility of min 4 hrs to max 12 hrs complete all as specified and directed Make:- Swadeep , Model nature switch -02(sensor) or equivalent as approved by GE.
Supply and fixing in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed Make- BCH/L&T or equivalent as approved by GE
Supply and fixing in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed Make- L&T/BCH or equivalent as approved by GE
Supply and fixing in replacement of contactor coil (230V) for MU series 25/40 Amps 2 pole contactors complete all as specified and directed Make- L&T (Cat No CS90793) or equivalent as approved by GE
Supply and fixing in replacement of contactor coil (240V) for freedom series 18 Amps 3 pole contactors complete all as specified and directed Make- BCH, Cat No CE15D1N-K or equivalent as approved by GE
Supply and fix in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled red colour, with letters, figures and conventional skull and bones in signal white colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed.
Supplying and laying in replacement of synthetic rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 10m x 1m complete all as specified and directed.
Supply and fix in replacement of cradles, hexagonal/rectangular, earth continuity wire for GOD/LA fabricated with galvanised steel wire 3.15/4 mm dia complete all as specified and directed.
Supply and fixing in replacement of cable route indicator or cable joint mark for 1100 volts made out of mild steel 100mm dia 6mm thick plate welded to 40 x 40 x 6mm angle iron 60 cm long embeded in PCC 1:3:6 type C-2 (using 20mm graded stone aggregate) block of size of 150mm x 200mm x 200mm including applying two coats of synthetic enamel paint over a coat of redoxide primer on steel surfaces complete all as specified and directed by Engr-in-Charge.
S&F in replacement of bracket made out of GI tubing single piece not welded, bended at proper angle of size 40mm dia, light grade 1.5 mtr long including painting with aluminium paint over one coat of red oxide primer to the bracket including 1.0 sqmm 3.0 core flexible copper cable in PVC conduit with clamp from juction box to connecter of street light fitting all as specified and directed.
S&F in replacement of MS clamp suitable for holding street light bracket on steel/PCC pole made out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia 03 Nos with flat washer 3mm thick 02 Nos for each including painting with aluminium paint over one coat of red oxide primer to the M.S clamps all as specified and directed.
Supply and fixing in replacement of extended spreaders link should be installed both side with existing/new MCCBs 4P/3P of any capacity with existing LT panels complete all as specified and directed by Engineer-in-Charge.
Note:- Amount of credit of Rs. 213140.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender.
BAL SINGH & SONS
Esha Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .