Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹21.5 LAccepted-AOC | 1 | Accepted-AOC Lowest bidder | |
| 2 | 2₹24.4 L+₹2.0 L (8.89%)Rejected-AOC | 2 | Rejected-AOC Second lowest bidder |
Tender Value
₹21.4 L
EMD Value
₹50,000
Closing Date
3 Oct 2019, 5:00 pmClosed
Managing Director, KTDC Ltd
KTDC -Corporate Office, Mascot Square PMG, Trivandrum
SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF SOLAR AND HEAT PUMP BASED HOT WATER SYSTEM
2019_KTDC_278299_1
KTDC-EW-TVM/750/BPH-Kochi-HWS
Open Tender
Solar Water Heaters
Item Rate
40 days
Ernakulam
As mentioned in NIT (Tender Notice)
8 documents required · 8 mandatory
₹2,950
online
₹50,000
7 Jan 2020
3 Sept 2019
10 Oct 2019
3 Sept 2019
3 Oct 2019
3 Sept 2019
Amount
For Nalukettu rooms including kitchen, restaurant and Palace rooms
Solar Hot water system supported by Heat pump as back up element
Supply, erection, Installation, Testing & Commissioning ( including delivery & lifting charges ) of following type hot water systems on terrace with pneumatic (pressure inlet) feeding complete with below mentioned components and supports, etc. with all accessories required etc. complete.
Storage Tank
2000 Ltr calorifier tank made low carbon steel, double Vitreous enameled single coil hot water storage tank with standard utility ports, magnesium sacrificial anode, duly insulated with 100mm rock wool insulation with 20 guage aluminium cladding, top manifold for inspection and cleaning. Temperature guage, air release valve, temperature and pressure release valve, electrical heating port provision alone without heater coils with necessary mounting supports/legs and lifting hooks etc. complete testing to withstand 6kg/cm2 pressure
Solar flat plate collectors of minimum 100 Litre capacity of (Approximate 2mt x 1mt size) BIS certified Copper tube and fins as collector area, low iron 4mm glass cover and aluminium framed structure and necessary supports etc complete as required at site.
Heat Pumps
Air to water heat pump of minimum capacity of 250 litre per hour and having 10kW or nearest output capacity and 2.5 kW or nearest input power requirement working on 3 Phase electrical power at ambient temperature of 20 deg C, CFC free refrigerant, evaporator coil with coating for corrosion prevention, tube in tube copper / SS heat exchanger, expansion valves, expansion vessels, hot gas bypass arrangements, high efficiency fans, with necessary prewired digital control panel with BMS compatibility for automatic operation based on temperature requirement and all the required motor starter circuits, motor overload & short circuit protection components, metering / controls / indication / sensors and related accessories with provision for cable entry size upto 4C x 6 Sqmm Aluminium conductor housed in a powder coated steel housing pre factory tested and certified.
Timer based operating Automatic hot water recirculation pumps ( 1 HP or nearest ) as per manufacturer / OEM specification & standards. (1W + 1S) -Make- Kirloskar or Equivalent
Circulation pump of required capacity to circulate water between solar panels and calorifier tank with differential temperature controller including all other accessories required for the operation such as RTD etc . (1W+1S ) Make- Kirloskar or Equivalent
25mm copper pipeline between solar collectors and calorifier tank and heat pumps with suitable thickness nitrile rubber sleeve insulation and aluminium tape covering etc complete as required at site including adequate supporting for pipe lines
Centralized Control Panel for the operation of heat pumps, circulation and re circulation pumps and all other electrical accessories in the system in a dust tight, vermin proof Enclosure having provision for cable entry / outgoing as per standards with suitably rated MCB/MCCB as incomer and SP/TP MCBs as outgoing, starters, timers, motor over load protection devices, Multi function meter to read current, Voltage and Active power etc. The control connections shall be wired using PVC insulated 1 Sqmm copper conductor etc. complete using good quality and approved make of materials.(Approved make for al components- L&T, Schnider, Siemens).
Part-B For Marina Block
Hot water system based on Heat pump alone
Storage Tank
2000 Ltr calorifier tank made low carbon steel, double Vitreous enameled single coil hot water storage tank with standard utility ports, magnesium sacrificial anode, duly insulated with 100mm rock wool insulation with 20 guage aluminium cladding, top manifold for inspection and cleaning. Temperature guage, air release valve, temperature and pressure release valve, electrical heating port provision alone without heater coils with necessary mounting supports/legs and lifting hooks etc. complete testing to withstand 6kg/cm2 pressure
Heat Pumps
Air to water heat pump of minimum capacity of 250 litre per hour and having 10kW or nearest output capacity and 2.5 kW or nearest input power requirement working on 3 Phase electrical power at ambient temperature of 20 deg C, CFC free refrigerant, evaporator coil with coating for corrosion prevention, tube in tube copper / SS heat exchanger, expansion valves, expansion vessels, hot gas bypass arrangements, high efficiency fans, with necessary prewired digital control panel with BMS compatibility for automatic operation based on temperature requirement and all the required motor starter circuits, motor overload & short circuit protection components, metering / controls / indication / sensors and related accessories with provision for cable entry size upto 4C x 6 Sqmm Aluminium conductor housed in a powder coated steel housing pre factory tested and certified.
Providing and fixing 1" Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. (SDR 11)
Timer based operating Automatic recirculation pumps (1 Hp or nearest) as per manufacturer / OEM specification and standards.(1W + 1S) Make- Kirloskar or Equivalent
Centralized Control Panel for the operation of heat pumps and re circulation pumps and all other electrical accessories in the system in a dust tight, vermin proof Enclosure having provision for cable entry / outgoing as per standards with suitably rated MCB/MCCB as incomer and SP/TP MCBs as outgoing, starters, motor over load protection devices, Multi function meter to read current, Voltage and Active power etc. The control connections shall be wired using PVC insulated 1 Sqmm copper conductor etc. complete using good quality and approved make of materials.(Approved make for al components- L&T, Schnider, Siemens).
KC COPAR ENERGY SOLUTIONS (P) LTD
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .