GE NS KOCHI
Military Engineer Services Garrison Engineer (Naval Services) Kataribagh, Naval Base Post Kochi 682004
PROVISION OF LT PANEL AND ALLIED SERVICES AT MT POOL, NAVAL BASE KOCHI
2026_MES_790170_1
8722/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KOCHI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE NS KOCHI
₹16,060
Yes
19 Sept 2026
19 Sept 2026
13 Oct 2026
19 Sept 2026
10 Oct 2026
4 Oct 2026
19 Sept 2026 - 20 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, laying and testing of UG cable XLPE insulated PVC sheathed,armoured,aluminium conductor cable 1100 volts grade 3.5 core 400 sqmm in trench/duct/floor/wall provision of saddle and lugs, joints etc, complete all as specified and as directed by Engr-in-charge | 30 | RM | - | - |
| 2 | Supply,laying and testing of FRLS Insulated Single Core Unsheathed Industrial Flexible Cable conforming to IS 694:2010 with Bright Annealed Copper Conductor for Voltage Grade 1100 Volts of size 185 sqmm in trench/duct/floor/wall provision of saddle and lugs, joints etc, complete all as specified and as directed by Engr-in-charge | 52 | RM | - | - |
| 3 | Supply, laying and testing of FRLS Insulated Single Core Unsheathed Industrial Flexible Cable conforming to IS 694:2010 with Bright Annealed Copper Conductor for Voltage Grade 1100 Volts of size 95 sqmm in trench/duct/floor/wall provision of saddle and lugs, joints etc, complete all as specified and as directed by Engr-in-charge | 25 | RM | - | - |
| 4Supply and Fixing of cable trays perforated of Hot dip galvanised sheet of following sizes on external/internal walls parallel/perpendicular with all accessories including anchor fastener, couplers, threded rod, rungs, horizontal bend, vertical bend inside and outside, tee,Hot dip GI strips, center reducer, right and left hand reducer, cross and necessary brackets,studs, nuts, bolts of hot dip galvanised steel of suitable size and length etc. including painted with anti corosion paint and taking down old cables for fixing on cable tray all as per site requirement:- | |||||
| 4.01 | 250 mm x 100 mm x 1.2 mm (width x height x thick) Tray complete all as specified and as directed. | 30 | RM | - | - |
| 4.02 | 250 mm (width x thick) cover complete all as specified and as directed. | 30 | RM | - | - |
| 5 | Supply and installation of LT panel board outdoor IP65 type platform mounted fabricated through CPRI IEC 61439 approved factory manufacturers, totally enclosed dust and vermin proof openable from both front and rear side made out of self supported 3. mm thick CRCA (Cold Rolled Cold Annealed) MS sheet of suitable length, width and height as per IE rule to accommodate all the items and conforming to IS-8623 and built upon 75 x 40 x 6 mm size Channel and lugs fixed on existing cable trenches having fro t and rear hinged doors with neoprene rubber gasket, danger plate, GI earthing strips at rear side, bottom detachable gland plate complete with suitable size single plated and passivated nuts, bolts, spring washers. The cabinet and all members shall be chemically treated with MSR solution for air corrosive treatment and powder coated (shade RAL - 7032) with 9 tank process and shall be with IP-65 grade protection. The panel shall be suitable for 415 volts, 50 Hz 3 phase 4 wire system and internal connections which shall be provided with aluminium strips of suitable size and comprising of the following accessories. all as specified and as directed BUS BAR CHAMBER : (i) Sheet steel bus bar chamber having front hinged covers with a set of electrolytic grade high conductivity TP&N solid Aluminium bus bars, rated 1000 Amps supported at required intervals sleeved with heat shrinkable PVC sleevings. The bars shall be colour coded at required intervals for identification - 01 No (Set of 04)
INCOMING
MCCB, 4 pole, 630 Amps thermal magnetic, 36 KA - 1 Nos
RYB Indication Lamp 1set, MF Meter 1nos ,Amp Meter 3nos 800/5
15VA CL1 CT 3nos. control MCB 1set
OUTGOING
MCCB, 4 pole, 630 Amps thermal magnetic, 36 KA - 1 Nos. | 1 | Each | - | - |
| 6 | Material and labour for Chemical earthing with copper plate 600x600x5mm buried directly in ground (Earth pit not less than 3.5 meter deep below normal ground level) connected to copper earth strip 32x6 mm (upto 7.5 meter) to earth plate by means of nuts, bolts, thimbles, chuck nuts, washers of GI or charcoal and salt crystals including necessary excavation and earthwork in any type of soil PCC 1:3:6 type C-1 using 20mm graded stone aggregate, chamber with RCC 1:2:4 type B-1, 40mm thick RCC pit cover using 8mm dia light grade GI pipe etc., and testing on completion, complete all as specified and directed by Engr-in-charge | 2 | Each | - | - |
| 7 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, buried directly and preferably vertically in ground, earth pit not less than 2.25 Metre deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with galvanised strip of size 32 x 6 mm by means of nuts, bolts, check nuts and washers including welding of each joints made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded stone aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C both ways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 metre etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed | 2 | Each | - | - |
| 8 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth and getting out in soft / loose soil for laying of cable complete all as specified and directed | 10 | Cum | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.49 MB
COMMONPAGES_8722.pdf
Tender Documents • 0.49 MB
PS_8722.pdf
Tender Documents • 0.55 MB
BOQ_885789.xls
BOQ • 2.19 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .