Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹97.3 LAdmitted-Finance RAMPUR UTTAR PRADESH | RAMPUR | UTTAR PRADESH | 244701 | +20.05% | ₹97.3 L | L1 | Admitted-Finance |
| 2 | Rejected-Technical | - | - | - | Rejected-Technical due to original stamp not submitted |
Tender Value
₹81.0 L
EMD Value
₹1.6 L
Closing Date
4 Mar 2026, 6:00 pmClosed
SE PHED DISTRICT CIRCLE RIKTIYA BHERU JI CIRCLE JO
SE PHED DISTRICT CIRCLE RIKTIYA BHERU JI CIRCLE JODHPUR
AS PER TD
2026_PHCJO_540005_1
SE/PHED/Distt. Cr./JU/68/2025-26
Open Tender
Civil Works
365 days
WORK
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,500
EE PHED DISTT. DN II JODHPUR
₹1.6 L
Yes
1 Apr 2026
18 Feb 2026
5 Mar 2026
18 Feb 2026
4 Mar 2026
18 Feb 2026
WATER TREATMENT PLANT
Design, construction, commissioning & testing of Non Mechanical Rapid Gravity Filter Plant of capacity as under. This work includes construction of RCC receiving chamber, baffle channel, flocculate, clarifier, collecting channel, filter beds , operation gallery, clear water chamber, channel, chlorination chamber, Back wash tank, pipe system for carrying raw water from Pump House to inlet of RGF, clear water from Plant to CWR, De-sludging system including providing pipe system from clarifier , flocculate & back wash water chamber to existing storage tank, over head back wash tank, back wash pumps (1W+1S) set with piping system, air blowers (1W+1S) as per design, interconnection of raw water, clear water, sludge pipes etc. including allied works such for construction ,commissioning of system as defined in scope of work, technical specifications and provisions of CPHEEO manual at various water supply schemes 45 KLH
ABOVE 45 KLH AND UP TO 60 KLH
Construction of RCC (Dome type) Clear Water Reservoir of following capacity as per Scope of work and Technical specification, consisting of the following main activities: - a) Topographic survey, preparation of site contour plan, conducting SBC test and its approval from department before construction. Submission and approval of concrete mix design and water quality test report for water to be used in construction. . b) Excavation in all types of soil, PCC below foundation & all RCC Work including all labour and material charges including providing and fixing of accessories such as SS ladder, SS manhole frame and covers, water level indicator (float type), SS ventilator with SS screen, float valve, puddle collars, G.I. pipe railing around walk way, Top Dome/Slab, Staircase. c) CWR shall be provided with adequate plinth protection all around the structure in a width starting from edge of structure at GL and extending at least up to 1.0m beyond the vertical wall of CWR. The plinth protection shall consist of 150mm thick PCC in M-15 concrete over 150mm thick compacted soil fill. d) Providing and applying two coats of food grade epoxy paint on the inside surface of the roof slab, and 600 mm height of the vertical wall.
e) Successful hydro test and water tightness test as per I.S. code. f) Providing and applying three coats of anti-carbonation paint on the roof Slab. g) Providing and applying three coats of cement-based paint on the remaining external surface area of the structure. h) Providing and fixing SS-304 ventilator, SS 304 manhole frame and cover and SS 304 ladder from roof slab to bottom Slab, inside container. Providing and fixing water level indicator (Float type). i) Providing and fixing MS ladder from ground to top slab. j) All MS parts to be painted with two coats of the enamelled paint over the primer coat of red oxide. k) Providing and fixing of 150mm wide water bar for the construction joints in the container. l) Providing and fixing CI/DI puddle collars the vertical wall for connecting inlet, outlet, overflow and washout pipes of the reservoir. m) Inlet, outlet, overflow, washout pipes and valves are not included in this work, provision for the same shall be taken separately.
Rates for RCC Partially Underground type clear water reservoir SBC 7 T/sqm, SEISMIC ZONE2,3 & 4
3.4.1.1 CRPF Campus 400 KL capacity
PUMP HOUSE
phed bsr 2023 8.1 Construction of Pump house of brick/ stone masonry of required size suitable for installation of maximum 4 no. Monoblock pump sets as per approved GA drawing, scope of work and technical specification complete work in all respect including electrical works for lighting and fans, rain water drainage. The plinth area of pump house shall be area of measurement. ( 6 x 4 )
phed bsr 2023 8.2 Construction of boundary wall of Brick/ stone masonry as per enclosed GA drawing, scope of work and technical specifications complete work in all respect. Brief details of boundary wall parameter is as below: 1. Depth of foundation- 900 mm. 2. PCC in M-10, width -900 mm and thickness 100 mm, 3. Stone masonry in CM: 1:6 section of foundation above PCC, 600 mm (W )x 450 mm (D) and 450 mm (W) x 450 mm (D) 4. Superstructure work: Stone masonry in CM: 1:6, W-300, height-1650 mm,/ Brick work in CM: 1:6 W-230 mm, height- 1650 mm. 5. Cement mortar pointing on Stone masonry and cement mortar plaster 20 mm thick on brick masonry in CM 1:6. 6. Expansion joint shall be on every 30 mtr. 7. On top of wall there shall be CC Coping 75 mm thick (1:2:4) shall be provided. 8. Pillar for main gate 350x350 mm in size is part of boundary wall. 9. Cement paint of approved colour in 3 coat shall be done.
PUMP MACHINERY
PHED BSR 2023/ 5.1 Providing, installation, testing and commissioning of Centrifugal Monoblock pump set conforming to IS 9079 , 2 pole motor operating at synchronised speed of 3000 RPM with requisite MOC impeller, priming funnel, cock, suitable flanges at suction and delivery side. Pump shall have common shaft for pump and motor. Motor shall be suitable for working on 415 V ± 10%, 3 Ph, 50 Hz A.C. Supply. Motor shall be TEFC type and Pump set shall be suitable for working at various discharge and head requirements as per scope of work. Pump shall be erected on C.C. foundation / cross channels / RSJ frame block with suitable foundation bolts grouted in C.C. foundation block etc. complete in all respect as per specification, scope of work and direction of Engineer in Charge of following power rating, suitable for prescribed duty conditions mentioned in TD.
Centrifugal Monoblock Pump set (Single Stage)
PHED BSR 2023/ 7.2SITC STAR DELTA Starter type LT Panel of following rating: all switchgears are of PHED approved makes, CRCA sheet of Panel enclosure is of TATA/ Essar 1.6mm/ 2.0mm thick duly Electrostatic Powder Coated with angle frame including other ancillaries ( Insulators, Acrylic Sheet , Backlight Sheet, Hardware, Wire, Name Plates, Lugs, Pvc Channel , Mcb Chanel , Lock, Hing , Bidding , Connectors, Neutral Links , Spiral , Saddle & Packing Material ) etc. and 100A/ 125A ,TPN, Aluminium Bus Bar with Colour coated heat shrinkage sleeves complete as per Technical Specifications and as per direction of Engineer-In-Charge.
PHED BSR 2023/ 2.21 Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required.
PHED BSR 2023 6.3.1.4 Providing, lowering, aligning, fixing in position in pipe line, CI double flanged swing type Non Return Valves (NRV) of approved make of following Pressure rating & dia complete, confirming to IS: 5312 (part -1)/ 2004 (amended up to date) and of following specifications: Body, Cover & disc of Grey cast iron of IS:210/ FG200. Face to face dimensions as per IS 5312 (part -1):2004 , Flanges Drilled as per IS:1538. All exposed machined ferrous surfaces shall be painted with one coat of aluminium red oxide primer conforming to IS:5660and two coats of black Japan paints conforming toType B of IS 341or paint conforming to IS9862 or IS2932( Non-Toxic- suitable for drinking water) applied inside and outside. Body seat ring of SS/CS Door face ring - EPDM/ Neoprene (food grade quality) ,Shaft of HTB1/ SS- AISI- 410, Hinge Malleable cast iron / SS AISI 316/410 ,Bonnet Gasket EPDM, Bush- Leaded tin Bronze/ PTET, Gasket EPDM/NBR ,Nut-Bolt as per IS:1363 and IS: 1367 (galvanised steel) ,Insersion rubber of black EPDM 6mm thick. Suitable support structure as per directions of EIC including jointing & jointing material, labour, testing and commissioning along with pipeline as per Technical Specification & as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. 150 MM dia
PHED BSR 2023 /2.20 Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. 16.0 Sq.mm, 4 core
PHED BSR 2023 /6.1.1.4 Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - SS 304 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date), All exposed machined ferrous surfaces shall be painted with one coat of aluminium red oxide primer conforming to IS:5660 and two coats of black Japan paint conforming toType B of IS 341or paint conforming to IS9862 or IS2932( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538.Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel.Insersion rubber of black EPDM 6mm thick . Suitable support structure as per directions of EIC. Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. Manually Operated CI Sluice valve of Class PN-1.0
6.1.1.4 150 MM dia
PHED BSR 2023/ 6.17 Providing, lowering, aligning, fixing in position and jointing CI dismantling joint (Suitable for Sluice valves etc.) as per IS specifications complete of the following sizes including all jointing material, cost of all labour, testing and commissioning and as per technical specifications and direction of Engineer In-Charge. Class PN 1.0/1.6 6.17.4_150 mm
PHED BSR 2023 1.11.1 Providing and fixing of flanged/plain ended MS specials from MS sheet strips of relevant IS specification of approved thickness by welding , lowering, laying and aligning, fixing in position at all level/depths in trenches complete including all taxes, material , labour, inside lining, outside coating , testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-chargeMS pipe special upto 600mm dia (with minimum 5.0 mm thickness sheet)
PHED BSR 11.1.5 SITC of D/F Full bore type Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.5MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Cast Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement of IEC 60529, Accuracy : ± 0.5 % M.V.- velocity 0.3 to 10 m/s, Transmitter/ signal convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 50Hz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, if required, and all materials required for making connection with existing pipeline including cutting the existing pipeline etc. complete in all respect as per technical specification and as per direction of Engineer In-Charge. Note: Rates are exclusive of tail piece / dismantling joints and earth work. 150 MM
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.85 MB
TD68.pdf
Tender Documents • 6.66 MB
BOQ_962746.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid