Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.2 LAccepted-AOC NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L1 | Accepted-AOC Being lowest. | |
| 2 | L2₹19.9 L+₹1.4 L (7.80%)Rejected-Finance 37 4TH CROSS ASHWATHNAGAR SANJYANAGAR POST BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L2 | Rejected-Finance Other than lowest tenderer |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
27 Aug 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(MAINT)EZHIMALA
GARRISON ENGINEER (MAINT) MILITARY ENGINEER SERVICES INDIAN NAVAL ACADEMY POST KANNUR DIST KERALA 670 310
AS PER BOQ AND TENDER DOCUMENTS
2022_MES_542430_1
GE MAINT EZHIMALA 8499
Open Tender
Civil Works
Item Rate
270 days
EZHIMALA
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MAINT EZHIMALA
₹40,000
Yes
22 Sept 2022
1 Aug 2022
29 Aug 2022
1 Aug 2022
27 Aug 2022
15 Aug 2022
2 Aug 2022 - 9 Aug 2022
Amount
Notes:- 1. Contractor should visit the site before quoting the tender to know the exact working condition of the station. 2. All requisite safety measurers are to be adopted by the contractor on site. 3. The complaint/ breakdown will be attended/rectified within five working days after informing the complaint by the Engg-in-charge or his authorised rep. 4. If the contractor failed to rectify the complaint/breakdown within five day then recovery will be done at Rs. 1500.00 Per day.
Repair in replacement of unserviceable parts of online UPS (with inbuilt Isolation transformer, IGBT, charging Board, mother Board , sine wave synchronizing board with by-pass board and cooling parts etc) of 10 KVA capacity including transportation (Make:- GE or equivalent Make of UTL Model Mars / APC / EMERSON / MICROTEK) and 12 Volts 42 AH SMF batteries, three phase AC input electric supply and out put single phase AC supply with complete connections including the following :- (A) BATTERY (i) SMF Batteries 12 Volts 42 AH Make EXIDE- 40 Nos (ii) Suitable battery rack - 01 No (iii) Connectors & other accessories - as per site requirement. (B) INPUT SUPPLY (i) Voltage range : 400(+/- 20% three phase four wire) (ii) Frequency : 50 Hz (+/- 5%) (iii) Input Power Factor : >0.9
(C) OUTPUT SUPPLY (i) Voltage range : 230(Single phase two wire) (ii) Voltage regulation : +/- 1%) (iii) Frequency : 50 Hz (iv) Frequency regulation : +/-0.05 Hz (v) Power Factor : >0.8 (vi) Transient Response : <8%(10%~90%(Linear Load)) (vii) Voltage Harmonic : <3% (Linear Load) (viii) Crest Factor : 3:1 (ix) Over Load Capacity (%) : 100 to 110% - 5 Minutes 110 to 120% - 2 Minutes 120 to 150% - 30 Second 150 to 200% - 1 Second (D) LED DISPLAY : UPS ON, Battery Low/High,Output Voltage Low/High-RYB, Over Load - RYB, Fault, Chager ON, Input Voltage Low/High-RYB. (E) LCD DISPLAY : Input Voltage & Frequncy -RYB, Output Voltage & Frequncy -RYB,Battery Voltage,Load Level, Working Status,Fault status. Note : Old U/S Batteries will be deposited at MES store yard.
Repair in replacement of unserviceable parts of online UPS (with inbuilt Isolation transformer, IGBT, charging Board, mother board , sine wave synchronizing board with by-pass board and cooling parts etc) of 05 KVA capacity including transportation (Make - GE or equivalent Make of UTL Model Mars / APC / EMERSON / MICROTEK) and 12 Volts 42 AH SMF batteries, three phase AC input electric supply and out put single phase AC supply with complete connections including the following :- (A) BATTERY (i) SMF Batteries 12 Volts 42 AH Make EXIDE- 20 Nos (ii) Suitable Battery Rack -01 No (iii) Connectors & other accessories - as per site requirement. (B) INPUT SUPPLY (i) Voltage range : 400(+/- 20% Three phase four wire) (ii) Frequency : 50 Hz (+/- 5%) (iii) Input Power Factor : >0.9
(C) OUTPUT SUPPLY (i) Voltage range : 230(Single phase two wire) (ii) Voltage regulation : +/- 1%) (iii) Frequency : 50 Hz (iv) Frequency regulation : +/-0.05 Hz (v) Power Factor : >0.8 (vi) Transient Response : <8%(10%~90%(Linear Load)) (vii) Voltage Harmonic : <3% (Linear Load) (viii) Crest Factor : 3:1 (ix) Over Load Capacity (%) : 100 to 110% - 5 Minutes 110 to 120% - 2 Minutes 120 to 150% - 30 Second 150 to 200% - 1 Second (D) LED DISPLAY : UPS ON, Battery Low/High,Output Voltage Low/High-RYB, Over Load - RYB, Fault, Chager ON, Input Voltage Low/High-RYB. (E) LCD DISPLAY : Input Voltage & Frequncy -RYB, Output Voltage & Frequncy -RYB,Battery Voltage,Load Level, Working Status,Fault status. Note : Old U/S batteries will be deposited at MES store yard.
Repair in replacement of unserviceable online UPS battery of 12 Volts 42 AH SMF of Make - Exide including all connection with existing UPS, three phase AC input electric supply and out put single phase AC supply with complete testing all as specified and directed by Engr-in-Charge. Note:- Old U/S batteries will be deposited at MES store yard.
Repair in replacement of unserviceable parts with complete servicing of 10 KVA voltage stabilizer for automatic operation, three phase, naturally oil cooled, indoor type & designed for input variation between 340 V to 480 V with output voltage stabilized at 415 including testing with complete connections including the following :- (a) Input Voltage Range - 340 Volts to 480 Volts (b) Output Voltage - 415 Volts (c) Input Frequency Range - 47 to 53 Hz (d) Digital Display - 3 digit 7 segment display (e) Accuracy of Voltage - 1% +/- 1 digit (f) Under Voltage /Over Voltage - +10% and -10% of output setting (g) Short Circuit Protection - HRC Fuse
Repair/servicing of unserviceable parts of online UPS including minor parts (except inbuilt Isolation transformer, IGBT, Charging Board, Mother Board) of 30/20/10/5 KVA any capacity including transportation complete all as specified and directed by Engr-in-charge. Make:- GE or equivalent make of UTL Model Mars / APC / EMERSON / MICROTEK.
Supply and fix in replacement of 20 KVA UPS mother board suitable for existing UPS complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of 10 KVA UPS charging board suitable for existing UPS complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of 10/20 KVA UPS IGBT suitable for existing UPS complete all as specified and directed by Engr-in-Charge.
M&L for in replacement of sub main wiring complete using 4 runs of 10 sqmm and two runs of 10 sqmm PVC insulated unsheathed FRLSH multistranded copper conductor ISI marked 1100 V grade in surface/concealed PVC conduit fixed in wall/floor,passing through wall/ceiling etc complete all as specified and directed by Engr-in-Charge. Notes:- (i) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate. (ii) Six runs of cable and one run of conduit with necessary accessories will be measured as one unit length. (iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue for phase, black for neutral and green for earth leads.
M&L for in replacement of sub main wiring complete using 2 runs of 10 sqmm and one run of 10 sqmm PVC insulated unsheathed FRLSH multistranded copper conductor ISI marked 1100 V grade in surface/concealed PVC conduit fixed in wall/floor,passing through wall/ceiling etc complete all as specified and directed by Engr-in-Charge. Notes:- (i) Necessary PVC rigid junction boxes for identifying junction as required on site/directed by Engr-in-charge for point wiring work with PVC dummy plates shall deemed to be included in the quoted rate. (ii) Three runs of cable and one run of conduit with necessary accessories will be measured as one unit length. (iii) The wiring shall be done strictly by following proper colour coding using red, yellow and blue for phase, black for neutral and green for earth leads.
Suppy & fix in replacement of fixing sheet metal enclosures DBs 4 way double door with bus bar complete all as specified and directed by Engr-in-charge.
Suppy & fix in replacement of fixing sheet metal enclosures DBs 8 way double door with bus bar complete all as specified and directed by Engr-in-charge.
Suppy & fix in replacement of MCB TPN 63 Amps complete all as specified and directed by Engr-in-charge.
Suppy & fix in replacement of MCB SPN 40 Amps complete all as specified and directed by Engr-in-charge.
Suppy & fix in replacement of MCB SP 63 Amps complete all as specified and directed by Engr-in-charge.
Repair in replacement of unserviceable online UPS battery of 2 Volts 100 AH SMF (UPST 100) of Make - Exide including all connection with existing UPS, output single phase AC supply with complete testing all as specified and directed by Engr-in-Charge. Note:- Old U/S batteries will be deposited at MES store yard.
Supply and fix in replacement of 10 KVA UPS mother board suitable for existing UPS complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of 20 KVA UPS charging board suitable for existing UPS complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of 5 KVA UPS mother board suitable for existing UPS complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of 5 KVA UPS charging board suitable for existing UPS complete all as specified and directed by Engr-in-charge.
M/S J S PRAKASAM
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .