Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 LAccepted-AOC | L1 | Accepted-AOC Admitted Found Reasonable for acceptance | |
| 2 | L2₹6.5 L+₹7,840 (1.23%)Rejected-AOC KALIAPPA COMPLEX THRICHY ROAD RANGANATHAPURAM SULUR COIMBATORE 641 402 | COIMBATORE | COIMBATORE | TAMIL NADU | 641402 | L2 | Rejected-AOC Rejected L1 being accepted | |
| 3 | L3₹6.6 L+₹18,015 (2.82%)Rejected-AOC JJ BHAVAN TC 10 1378 2 GN 31 CHENCHERY ROAD NALACHIRA PO TRIVANDRUM 695 015 | TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695015 | L3 | Rejected-AOC Rejected L1 being accepted | |
| 4 | L4₹6.9 L+₹47,865 (7.49%)Rejected-AOC | L4 | Rejected-AOC Rejected L1 being accepted | |
| 5 | L5₹7.7 L+₹1.4 L (21.2%)Rejected-AOC | L5 | Rejected-AOC Rejected L1 being accepted |
Tender Value
₹8 L
EMD Value
₹16,000
Closing Date
11 Aug 2020, 6:00 pmClosed
GE Army Trivandrum
Office of Garrison Engineer Army, Thirumala Post, Trivandrum - 06
As per Tender Documents
2020_MES_360849_1
GE(ARMY) TVM 9320/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Trivandrum
As per NIT
8 documents required · 8 mandatory
₹500
GE Army Trivandrum
₹16,000
20 Oct 2020
14 Jul 2020
13 Aug 2020
15 Jul 2020
11 Aug 2020
27 Jul 2020
15 Jul 2020 - 25 Jul 2020
Amount
Material and labour for distribution board, vertical, made out of sheet metal enclosure (CRCA sheet) dust and vermin proof, double door, VTPN 4 way, 415 volts grade with insulated rated bus bar assembly with isolated neutral bar,door earthing, earth bar IP- 43 protection with poly urithene (PU) gasketing, IK-08 Mechanical impact resistance, door earthing flush to wall, including testing suitable for fixing MCCB, MCB TPN/TP/SPN/SP etc, including taking down existing unserviceable one and removing from site complete all as specified and directed Make: Legrand / L&T/ Havells
All as per ser item No. 1 above but for VTPN 6 way
Supply and fix MCCB triple pole and neutral (four pole) 100 Amps, 415 volts, 50 Hz, having thermal setting range 70% to 100% and adjustable magnetic setting and breaking capacity 25 KA including making incoming and outgoing connections complete all as specified and directed. Make: Legrand/ L&T/ Havells
All as per ser item No. 3 above but for 63 Amps
Material and labour for distribution board made out of sheet metal enclosure (CRCA sheet) dust and vermin proof, double door, TPN 4 way, 415 volts grade with 200 Amps insulated rated bus bar with nickel plated brass, isolated neutral bar and door earthing, earth bar IP- 43 protection with poly urithene (PU) gasketing, IK-08 Mechanical impact resistance, door earthing flush to wall, including testing suitable for fixing MCB SPN, SP etc, including taking down existing unserviceable one and removing from site complete all as specified and directed Make: Legrand / L&T/ Havells
Supply and fix in repair MCB single pole 5 to 32 Amps, 240 volt, 10 KA, C curve, ISI marked as per IS/IEC-60898-1 2002 including sliding bottom clamp, integrated label holder, sliding shutters, biconnect lower terminals with IP-20 protection complete all as specified and directed Make: Legrand / L&T/ Havells
All as per ser item No. 6 above but for MCB single pole and neutral 25 to 32 Amps
All as per ser item No. 6 above but for MCB triple pole 40 to 63 Amps
All as per ser item No. 6 above but for MCB triple pole and neutral 40 to 63 Amps
Supply and fix in repairs of sub main wiring with 4 runs of 6.0 sqmm single core, multi-stranded PVC insulated, FRLS unsheathed cable 1100 Volts grade with copper conductor drawn through and including concealed non metalic PVC FRLS conduit, medium grade, ISI marked, 20/25mm bore with conduit fittings and accessories concealed in wall/ceiling/floor inc 2 runs run of 6.0 Sqmm multistranded PVC insulated FRLS, copper conductor cable as earth continuity conductor and connecting to common earth dolly complete. NOTE: Four runs of 6.0 sqmm copper cable and two run of 6.0 sq mm copper cable alongwith non metallic PVC conduit/conduit accessories will be measured as one unit length Make: V-Guard / RRKabel / Finolex / Havells/
All as per ser item No. 10 above but for sub main wiring with 2 run of 6 sqmm & 1 run of 6 sqmm as earth wire
All as per ser item No. 10 above but for sub main wiring with 2 run of 4 sqmm & 1 run of 4 sqmm as earth wire
Supply and laying or passing through GI pipe, 1100 volts grade heavy duty stranded conductor cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheated 10 sqmm 2 core nominal cross section in service connections including taking down old unsv one from the site complete all as specified and directed Make: V-Guard / RRKabel/ Havells/ / Finolex
Supply & lay GI steel tubing light grade 40mm dia for protection of cable on poles, under road crossing etc, complete all as directed. Make: Jindal /TATA/Zenith/ Surya
Material and labour for Earthing complete in replacement with galvanised iron mild steel earth plate electrode 600 x 600 x 6.3mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below normal ground level, connected to glavanised earthwire 4mm diameter by means of GI Bolts, Nuts, check nuts and washers including earthing pit in PCC (1:3:6) type C-1 RCC pre-cast (1:2:4 type B-1) cover slab 50 mm thick with 8 mm CTD bars reinforcement both ways at 140 mm centre to centre with two handles, 20 mm dia GI pipe medium grade for watering pipe, wire mesh, funnel and providing charcoal or coke and salt in alternative layers of 15 cm and 15 mm dia light grade GI pipe for protection of earth wire from earth plate to MCB DB including necessary earth work in hard/dense soil, returning, refilling and removing of surplus soil to a distance n. exc. 50 mtr and testing on completion complete all as shown in electrical plate No-3 as and directed. NOTE: (a) Earthing shall be provided as per IS:3043-1987. (b) Earthing shall be carried out 7.5 mtr apart from the building. (c) Rate for GI wire upto test point included in the quoted rate. (d) Testing of Earthing will be carried out as per direction of Engr-in-Charge.
Supply and fix in repair earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed with ploes or any other indicated situation for loop earthing etc. as required using galvanised iron or steel wire 4mm dia complete all as specified and directed (for additional length beyond 7.5 mtr)
SUPER COOL
JEETH CONSTRUCTION
R.K. Builders
AKASH CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .