| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.0 LAccepted-AOC BALTIKURI INDUSTRIAL ESTATE PLOT NO A 01 DASNAGAR HOWRAH 711113 | HOWRAH | HOWRAH | WEST BENGAL | 711113 | L1 | Accepted-AOC L1 | |
| 2 | L2₹21.1 L+₹96,351 (4.77%)Rejected-Finance 103 1A RAJA DINENDRA STREET KOLKATA 700006 | KOLKATA | KOLKATA | WEST BENGAL | 700006 | L2 | Rejected-Finance 2114689.00 | |
| 3 | L3₹22.1 L+₹1.9 L (9.63%)Rejected-Finance | L3 | Rejected-Finance 2212659.00 |
Tender Value
₹16.8 L
EMD Value
₹33,596
Closing Date
1 Jul 2020, 2:00 pmClosed
Executive Engineer PWD BDN ELEC DIVN
Room no 1081st fl purta bhawan salt lake kolkata
Revamping of Electrical Installations works in Different rooms of West Bengal Pollution Control Board Paribesh Bhawan 10A LA Block Sector III Supply and Installation of VRF and Split AC units
2020_WBPWD_285450_1
WBPWD/EE/BED/49/e-IT of 2019_20_4th call
Open Tender
ELECTRICAL WORKS M/R
Item Rate
14 days
paribesh Bhavan
Please refer Tender documents.
5 documents required · 5 mandatory
₹33,596
Yes
22 Oct 2025
15 Jun 2020
3 Jul 2020
18 Jun 2020
1 Jul 2020
18 Jun 2020
Amount
SITC of VRF / VRV Outdoor Unit with connected indoor units including cost of R410 A refrigerent complete VRF system: SITC of Air cooled VRF top discharge type Outdoor Unit each comprising of all variable speed inverter controlled scroll, air cooled condensor with protective coated fins,mounting frame,micro processor panel and other standard accessories as per specification.The unit shall be suitable for operation with R-410A refrigerant and to maintain the room temperature at 24 degree Centigrade and Humidity level as per latest standard of NBC. Minimum COP of the ODUs at 50% load & at 40 degree centigrade ambient condition should be 4.5. and there should be no capacity deration upto 40 degree Centigrade and it should be compatible with exixting 10 HP Hitachi ductable indoor unit. (Make: Hitachi/ Mitsubishi/Blue Star/ Toshiba/ Carrier/LG) i)16 HP- consists of 2/3 Nos SCROLL variable speed INVERTER Compressor.
"Do---------Do------------------Do----------------------Do ii) 8 HP.
VRF/VRV INDOOR UNIT Supply, Installation, Testing & commissioning of Wall mounted Indoor Units complete with cordless remote as per the following Capacity (Make same as ODU). 3 TR Hi-wall Unit
Supply, Installation, Testing & commissioning of Wall mounted Indoor Units complete with cordless remote as per the following Capacity (Make same as ODU). 2 TR Hi-wall Unit
REFRIGERANT PIPE refrigerant piping with(19,13 mm thick) nitrile rubber insulation(with AL cladding outdoor pipes) refrigerant pipes shall be as below i) Dia 28.58mm
ii) Dia 25.4mm
iii) Dia 22.2mm
iv) Dia 19.05mm
v) Dia 15.88mm
vi) Dia 12.7mm
vii) Dia 9.53mm
CONDENSATE DRAIN PIPE Condensate Drain line shall be with following size heavy duty high wall thickness PVC pipes & fittings with 6mm thick nitrile rubber insulation. 32mm. Dia.
Supply, fabrication , delivery and Installation of MS STRUCTURAL WORK as required to make the outdoor units ready and complete for installation and functioning as per direction of EIC and approval of drawing -for 16 HP out door units.
Do--------------do------------do----------------do for - 8 HP out door units.
Supplying & laying of 2C /3C Shielded 'Copper'Control Cable.Control cable between the indoor units and the outdoor units.(make- polycab/havells/ KEI
Y-Joint / Refnet Supply and fixing of Y-Joint / Refnet Joint/Piping Connection Kits.
Supply & installation of Split Type Air Conditioner FittedWith rotary compressor:(cooling capacity not less than 3480 watt, with min ISEER-3.5). Copper Condensor;Without Installation kit, (i.e. Copper pipe, water pipe, installation cable etc.) (make-Daikin/Blue star/Hitachi/Voltas/Carrier)
Supply & installation of Split Type Air Conditioner FittedWith rotary compressor:(cooling capacity not less than 5220 watt, with min ISEER-3.5). Copper Condensor;Without Installation kit, (i.e. Copper pipe, water pipe, installation cable etc.) (make- Ogeneral/Mitshubishi Electric)
Supply & installation of Split Type Air Conditioner FittedWith rotary compressor:(cooling capacity not less than 5220 watt, with min ISEER-3.5). Copper Condensor;Without Installation kit, (i.e. Copper pipe, water pipe, installation cable etc.) (make-Daikin/Blue star/Hitachi/Voltas/Carrier)
Supply & installation of Split Type Air Conditioner FittedWith rotary compressor:(cooling capacity not less than 6960 watt, with min ISEER-3.5). Copper Condensor;Without Installation kit, (i.e. Copper pipe, water pipe, installation cable etc.) (make-Daikin/Blue star/Hitachi/Voltas/Carrier)
Supply & Fixing M.S bracket with proper grouting system & mending good damages & all necessary works as per instruction of E.I.C(Brand approve by EIC)
Supplying & fixing of copper pipe with insulation foam and PVC tape(Brand approve by EIC)(i) 5/8"
Do----do---do----- 1/2"
Do ----do----do---- 3/8"
Do----do---do----- 1/4"
Supplying & fixing of 3 core 4 sq mm FRLSH copper wire for inter-Connection Indoor & Outdoor Unit.(Finolex/Havells/RR cable)
S&F 1/2" best quality PVC drain pipe with necessary accessories as required
Extra charges for supply and fixing 10mm thick ply board for installation of AC units.
Hiring charges for scaffolding arrangement for AC outdoor units installation , pipe, cable & drain pipe laying,wall/glass cutting per storey of building per vertical run.
Withdrawing all Old Existing AC units i.e. indoor and outdoor units, drain pipes, refrigerent pipes and restore it at the given area providerd by the authority . N.B.:- (i) The Agency must procure the materials from the Manufacturer/OEM or from their authorized. Sales channel so that the standard warranty/support of the Manufacture/OEM becomes applicable to the products to be delivered and installed by them. (ii) Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/ support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill. (iii) If any refurbished material is supplied and installed, panal action will be taken as per existing rules.
L.W.C. must be quoted manually @1% on the total quoted value else the total quoted rate shall be treated incl. LWC as per rule. N.B. Rate should be quoted inclusive of GST.
S.R. REFRIGERATION AND APPLIANCES
SOUMYA ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .