Ex.Eng (O&M) Valsad Rural Division
Tender for Erection & Maintenance and Labour works for Laying, testing & commissioning of 11/22 KV underground / Overhead XLPE cable (XLPE cable to be supplied by DGVCL), with cable End termination & straight through jointing kits (to be supplied by contractor) for Various feeder under jurisdiction of Bilimora Town subdivision under Valsad Rural Division under COASTAL & Other Various Scheme.
292410
DGVCL/VALSAD-R DO/E-TENDER/2025-26/132
Open
Miscellaneous Works
Works
Valsad
8 documents required · 8 mandatory
₹1,180
DGVCL, Payable @ Valsad
₹20,000
1 Apr 2026
1 Apr 2026
1 Apr 2026
8 Apr 2026
1 Apr 2026
Item Code Details of works Unit FY 2024-25
(A) LINE MAINTENANCE
1 9924000001 Cutting of Tree branches surounding HT/LT line
Replacement of old jumpers & providing new double
2 9924000002 jumpers with 8" binding [D Type] & capsuling with No.
3 9924000005 Support pole for Stay PSC/STP/RSJ No.
4 9924000006 Pin binding of conductor 11/22kv Pin insulator No.
Pin binding of conductor 11/22kv Pin insulator per pole
in costle area with cleaning .
6 9924000008 Pin binding of conductor LT shakel insulator No.
7 9924000009 Replacement of one/both disc.insulator at strain pole No.
8 9924000010 Replacement of LT shackle insulator at cut point No.
9 9924000011 Refixing of V cross Arm No.
Replacement of V cross Arm (With Transportation &
11 9924000013 Refixing of Top fitting in proper position No.
12 9924000014 Replacement of Top fitting No.
13 9924000015 Replacement of LT cross Arm No.
Providing DO fuse on DP with carting &
jumpuring(ONE DO FUSE)
Numburing of pole with paint by preparing back
15 9924000017 ground of one colour and have lettering(height 3" * No.
width 0.5") using stensil
16 9924000018 Fixing of MMB(1PH.) at consumer end No.
17 9924000019 Fixing of MMB(3PH.) at consumer end No.
18 9924000020 Replacement of (1ph.) meter for Urban area No.
19 9924000021 Replacement of (1ph.) meter for Rural area No.
painting consumer no. on MMB (Urban) (with letter
size height 40mm* width 8mm)
painting consumer no. on MMB (Rural) (with letter
size height 40mm* width 8mm)
22 9924000024 Replacement of deteriorated Single phase Service line No.
Fixing of new dist. Box with complete wiring including
clamps,nut bolts etc.
Reparing of guarding involving reshaping of bearer
wire cross lacing binding etc.
Painting of steel fabricated material of RSJ DO DP
structure with paint
Painting of steel fabricated material of RSJ pole
mounted transformer double pole structure with paint
Painting of steel fabricated material of RSJ single pole
painting of steel fabricated material of PSC Single pole
(HT line) with paint
painting of steel fabricated material of PSC DO DP
double pole with paint
painting of steel fabricated material of PSC double
pole at pole mounted transformer with paint
31 9924000033 Providing line seperater single phase No.
32 9924000034 Providing line seperater three phase No.
Replacement / Providing of stay insulator along with
adjustment of tension in stay wire
Replacement of deteriorated /providing LT dist. Box
34 9924000036 with new up to 100KVA capacity & crediting it to No.
Replacement of deteriorated /providing LT dist. Box
35 9924000037 with new above 100KVA capacity & crediting it to No.
36 9924000038 Adjustment of tension in stay wire No.
37 9924000039 Refitting of LA No.
Converting pin point to Shackle point including
38 9924000040 location
dismentaling & restringing etc.
replacement of 11KV Pin insulator with providing new
double pin binding
replacement of 22KV Pin insulator by new 11kv pin
40 9924000042 insulator with spares & providing new double pin No.
Providing 11kv double disc insulators with binding &
Replacement of existing 11kv conductor (all size) with Cond/K
new double pin binding M
43 9924000046 Plumbing of PSC Pole with straightening at pin point No.
Plumbing of PSC Pole with straightening at tension
Plumbing of tilted DP structure (PSC/RSJ/STP) with
refilling of stone Murrum etc.
Providing new 11kv AB /GO switch with fabrication and
insulated colour code jumper, binding, lugs etc
Replacement of old 11kv AB /GO switch with providing
new insulated jumper, binding, lugs etc
Providing cage type loop guard in verticle LT line with per
using PVC reel insulators etc pole
Labour charges for replacement /providing of MMB &
service with all accessories for three phase connection
Labour charges for replacement /providing of MMB &
service with all accessories for single phase connection
Dismentalling of existing Dist.X'mer center(RSJ /STP
51 9924000055 POLE) 25/63/100/200 KVA with all fabrication & No.
creditig the old material to store
52 9924000056 Disconnection from LT pole 1 phase No.
Reconnection from LT pole 1 phase
( payment after receipt of R/C charges)
54 9924000058 Disconnection from LT pole 3 phase No.
Reconnection from LT pole 3 phase
( payment after receipt of R/C charges)
Dismentaling & removing of service line from pole &
crediting to S/dn (1 ph.)
Dismentaling & removing of service line from pole &
crediting to S/dn (3 ph.)
Reconnection of service line complete with PVC cable
Reconnection of service line complete with PVC cable
Providing spiral type earthing by G.I. NO 8(weight 2kg
-5mtr in length) with salt and coal 10kg each,
including pvc rigid pipe 20mm dia( 1.5mtr length) to
pass exposed part of G.I. wire at consumer end with
all materials, earth resistance should be less than
Providing and fixing of signle core 1.5 sq mm single
strand copper insulated cable with cable nail clip for
spiral type earthing at consumer end. The end of G.I.
no 8 is to be connected by connector with copper
61 9924000070 cable of which other end shall be connected to the
earth terminal of meter box. This item shall be used in
location where there is more distance between earth
terminal and earthing terminal of meter. (All materials
supplied by contractor)
9924000065 Stringing of LT ABC of 1*35 SQ MM + 1*25 SQ MM
including fitting of all accessories i.e. special design
suspension / tension clamp, fixing of cross arm, LT
shackle insulator etc. for fixing of messenger wire and
inclusive of dismantling charge of existing bare
62 conductor and crediting in to store & dismantling of KM 8922/-
service line from LT bare conductor and to provide
service connection on Aerial Bunch Cable by insulated
piercing connectors through service connection box
complete as required & directed by Engineer in
9924000066 Stringing of LT ABC of 3*50 SQ MM +1*25 SQ
MM+1*35 SQ MM including fitting of all accessories
i.e. special design suspension / tension clamp, fixing of
cross arm, LT shackle insulator etc. for fixing of
messenger wire and inclusive of dismantling charge of
existing bare conductor and crediting in to store & KM 22303/-
dismantling of service line from LT bare conductor and
to provide service connection on Aerial Bunch Cable by
insulated piercing connectors through service
connection box complete as required & directed by
Engineer in Charge.
9924000067 Stringing of 11KV ABC of 3*95 SQ MM +80 SQ MM
including fitting of all accessories i.e. special design
suspension / tension clamp, fixing of cross arm,
binding to pin insulator, preparing shackle point,
jumpers etc. and inclusive of dismantling charge of
existing bare conductor and crediting in to store
complete as required & directed by Engineer in
9924000068 Stringing of 22 KV ABC OF 3*70 SQ MM +95 SQ MM
including fitting of all accessories i.e. special design
suspension / tension clamp, fixing of cross arm,
65 binding to pin insulator, preparing shackle point, KM 55019/-
jumpers etc. and inclusive of dismantling charge of
existing bare conductor and crediting in to store
complete as required & directed by Engineer in Charge
9924000069 Stringing of LT ABC of 2*50 SQ MM +1*25 SQ MM+
35 SQ MM including fitting of all accessories i.e. special
design suspension / tension clamp, fixing of cross arm,
LT shackle insulator etc. for fixing of messenger wire
and inclusive of dismantling charge of existing bare
66 conductor and crediting in to store & dismantling of KM 15613/-
service line from LT bare conductor and to provide
service connection on Aerial Bunch Cable by insulated
piercing connectors through service connection box
complete as required & directed by Engineer in
-::- SCHEDULE – ‘B 3’: FOR Underground -::-
LABOUR RATE FOR UNDERGROUND CABLE WORK (WITHOUT GST)
Item Code Description Unit FY 2024-25
Labour charge for excavation of cable
trench of 400mm width x 1200mm depth,
in any type of soil for laying of cable of
1 9925000001 size up to 240 mm2 (For additional cable Meter
200 mm additional width shall be
considered i.e. half trench length is to be
Labour charge for excavation of cable
trench of 600mm width x 1200mm depth,
in any type of soil for laying of cable of
2 9925000002 size up to 240 mm2 (For additional cable Meter
200 mm additional width shall be
considered i.e. half trench length is to be
Labour charge for excavation of cable
trench of 400mm width x 1500mm depth,
in any type of soil for laying of cable of
3 9925000003 size up to 240 mm2 (For additional cable Meter
200 mm additional width shall be
considered i.e. half trench length is to be
Labour charge for laying of 11kV / 22 kV
XLPE Cable of size up to 240 mm2 &
preparation of sand layer 100mm thick, in
the cable trench & covering the cable with
150 mm dia (Inner), thickness 25 mm,
1.0 meter long RCC half round muffs and
providing and fixing of 4inch width yellow
colour polyethylene tape with printing
"CAUTION ELECTRIC CABLE BELOW" at
0.75 m depth from ground surface after
laying cable in trench. This will provide
indication that electric cable is passing
underground so as to protect cable from
mechnical injuries, refilling the same, as
per Instruction of Engineer in Charge
Labour charge for horizontal drilling using
Auger machine without damage to surface
road at max 2.0 mtrs depth & putting of
6.11 kg/cm2 , class-4,Green color, 110mm
O.D. , 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984-1987(3rd revision)
and BIS certification and laying of
11KV/22KV XLPE cable of size up to
mm2 in HDPE pipe, as per Site Condition
(excluding cost of pipe). The detail map
obtained from HDD machine and excell
sheet(hard and soft copy) indicating the
respective depth and distance from
adjacent landmark for each segment for
HDD is must required to be submitted.
HDD to be carried out at depth 1.5 mtrs
to 2.0 mtrs as per site conditions and as
per instruction of EIC.
Labour charge for horizontal drilling
manually without damage to surface road
at max 2.0 mtrs depth & putting of
kg/cm2 , class-4,Green color, 110mm
O.D. , 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984-1987(3rd revision)
and BIS certification and laying of
11KV/22KV XLPE cable of size up to
mm2 size, as per Site Condition
(excluding cost of pipe). The detail map
and excell sheet(hard and soft copy)
indicating the respective depth and
distance from adjacent landmark for each
segment of cable to be submitted. Drilling
to be carried out at depth Minimum
mtrs to 2.0 mtrs as per site conditions as
per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5 mm thickness
H.D.P.E. pipe confirms to IS 4984 and BIS
certification for laying of underground
11KV / 22KV XLPE cable up to 240 mm2
Labour work for RCC concreting on
disputed location and repairing of damage
portion of road crossing for the work
carried out for roads crossing as well as
concreting & muffing of ploes including all
materials (1:2:4)
Providing & fixing concrete stone route
marker of 300 mm width x 150 mm thick
x 650 mm height embedded in earth at
least 300 mm below & 350 mm above
ground level respectively at distance
approx 50 meters along the length of
cable. The RCC concreting (1:2:4)(all
necessary maeterials will be in bidder's
scope) of route marker is to be carried out
300 mm width x 150 mm thick x 300 mm
below ground level as per instruction of
EIC. The route marker should be with
name of company with approved yellow
colour-DGVCL. The distance from marker
to cable and cable depth with feeder
name etc., marked with arrow sign is to
be painted on it.The route marker is to be
fixed at location near to any fixed
permanent location (not necessary to fix
exact on top of cable) as per instruction
Erection of D.P. (double pole) structure
using 9 / 11 Mtr. RSJ pole with cable
connection arrangement along with fitting
10 9925000010 of necessary fabrication for 11KV cable No.
including excavation of pit & refilling of
earth as per instruction of EIC. (Exclusive
of concreting & muffing of poles)
Erection of Single pole structure using 9 /
11 Mtr RSJ pole with cable connection
arrangement along with fitting
ofnecessary fabrication for 11KV/22 KV
cable including excavation of pit & refilling
of earth as per instruction of EIC.
(Exclusive of concreting & muffing of
Erection of D.P. (double pole) structure
using 8.0 Mtr. PSC pole with cable
connection arrangement along with fitting
12 9925000012 of necessary fabrication for 11KV cable No.
including excavation of pit & refilling of
earth as per instruction of EIC. (Exclusive
of concreting & muffing of poles)
Erection of Single pole structure using
Mtr PSC pole with cable connection
arrangement along with fitting
ofnecessary fabrication for 11KV/22 KV
cable including excavation of pit & refilling
of earth as per instruction of EIC.
(Exclusive of concreting & muffing of
Labour charge for erecting of 11kV /
kV XLPE cable of size up to 240 mm2 on
DP Structure with fixing of 02 Nos
polymer cleats on top and middle
part.Polymer cleats, nut bolts etc. fixing
material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class-
4,Green color, 110mm O.D. , 8.5mm
thickness H.D.P.E. pipe confirms to IS
4984 and BIS certification on the erected
DP structure for the mechanical protection
of cable by inserting the cable inside
15 9925000015 HDPE pipe. The HDPE pipe shall be Per Job
erected in such a way that 300mm shall
be below the ground level and the rest
2700 mm shall be supported on the
DP Structure with 01 No Polymer cleat.All
materials including polymer cleat and Nut
bolt to be provided by contractor.
Providing and fixing of pipe type earthing
from 80 mm dia class-B GI pipe with pit to
be filled with salt & coke and construction
of chamber as per DGVCL Drg. No. dg
16 9925000016 /100 for DP and cable. The earthing pit No.
should be joined with cable by G.I. strip of
size 1” width & 2 mm thick. All material GI
pipe, Coke, Salt etc will be supplied by
Supply & fixing of heat shrink type end
terminations (outdoor) for upto 11kV 3C x
185 mm2 size XLPE cable as per DGVCL
technical specification
Supply & fixing of heat & shrinkable end
terminations (outdoor) for upto 22 kV 3C
x 185 mm2 size XLPE cable as per DGVCL
technical specification)
Supply & fixing of heat shrink type end
terminations (indoor) for upto 11kV 3C x
185 mm2 size XLPE cable as per DGVCL
technical specification)
Supply & fixing of heat & shrinkable end
terminations (indoor) for upto 22 kV 3C x
185 mm2 size XLPE cable as per DGVCL
technical specification
Supply & fixing of heat shrinkable straight
through joint for upto 11kV 3C x 185 mm2
size XLPE cableas per DGVCL technical
Supply & fixing of heat shrinkable straight
through joint type for upto 22kV 3C x
mm2 size XLPE cable as per DGVCL
technical specification
Labour charge for excavation of 2100mm
long x 1200mm wide x 1200 mm deep
joint pits for installation of 11kV / 22kV
Straight through joints as per instruction
23 9925000023 of engineer-in-charge & covering the No.
cable with 150 mm dia (Outer), thickness
25 mm, 1.0 meter long RCC half round
muffs & refilling same as per instruction
Providing and fixing of insulating bus bar,
made from 11KV/22KV XLPE cable after
removal of semi conducting layer and
applying of PVC heat shrinkable anti-
tracking core insulating tubing (1.1KV), on
both end terminal using Aluminium long
barrel heavy duty up to 240 sq mm lugs,
24 9925000024 Aluminium bus connector. Taping with No.
PG- clamp for bus conductor as per
drawing and as per instruction of EIC. The
Alluminium lugs and PG clamp shall be
covered with 11KV/22KV HT insulating
tapes.(11KV/22KV XLPE cable will be in
scope of DGVCL while all other materials
will be in bidder's scope)
Testing of cable at various points and
commissioning the feeder as per
25 9925000025 instruction of engineer-in-charge.Test No.
result shall be submitted by contractor
Preparation and submission of 6 (six)
copies, of complete layout drawings with
26 9925000026 GIS mapping as per actual cable routing Set
showing road crossing, HDPE pipe
sleeving, jointing locations, markers etc.
Providing and fixing of Sign Board at
junction point Made out of 2 mm
aluminium sheet size 750x300 mm (2.5 x
1ft) rectangle, as per design, pre treated
with phosphate process and acid etching
coated with one coat of epoxy primer and
two coats of best quality paints,
refloctrorised with Hi-Intensity retro –
reflective sheeting as per the latest and
27 9925000027 frame fabricated from suitable size iron No.
angle. The Sign Board is to be fixed on
the base prepared from channel and
bracing angles which is grouted by means
of cement concreting of 1:2:4 for size of
300 mm dia x 800 mm height (500 mm to
be grouted in ground). The details to be
displayed on sign board will be given by
In-charge Engineer.(a) Hi intensity Micro
prismatic Grade
Providing and fixing of Sign Board
(Danger Board) on Distribution
Transformer Centers
Made out of 2mm aluminium sheet size
300x300mm (1x1ft) as per design, pre
treated with phosphate process and acid
etching coated with one coat of epoxy
28 9925000028 primer and two coats of best quality No.
paints, refloctrorised with Hi-Intensity
retro-reflective sheeting as per the latest
and frame fabricated from suitable size
iron angle. The Sign Board (Danger Board
is to be fixed at the location as per
instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size
250 mm (L) x 75 mm (W) from 3 mm
aluminium sheet along with 1.0 mm dia
aluminium binding wire for fixing of
aluminium tag near end termination joint
at DP structure for identifyng the cable.
The details of feeder i.e. 11 / 22 KV with
feeder name shound be punched on the
tag by letter punch of size 16 mm as per
instruction of In-charge Engineer.
Supply & fixing of heat shrink type end
terminations (outdoor) for 11kV 3C x
mm2 size XLPE cable as per DGVCL
technical specification
Supply & fixing of heat & shrinkable end
terminations (outdoor) for 22 kV 3C x
240 mm2 size XLPE cable as per DGVCL
technical specification)
Supply & fixing of heat shrink type end
terminations (indoor) for 11kV 3C x
mm2 size XLPE cable as per DGVCL
technical specification)
Supply & fixing of heat & shrinkable end
terminations (indoor) for 22 kV 3C x
mm2 size XLPE cable as per DGVCL
technical specification
Supply & fixing of heat shrinkable straight
through joint for 11kV 3C x 240 mm2 size
XLPE cableas per DGVCL technical
Supply & fixing of heat shrinkable straight
through joint type for 22kV 3C x 240 mm2
size XLPE cable as per DGVCL technical
Installation, Testing and commissioning
of 11 KV,630 A SCADA Compatible, RRL
type- 3 Way RMU including Two numbers
of earthings as per Drawing (material is in
bidder's scope) and as per DGVCL
Technical specification.
Installation, Testing and commissioning
of 11 KV,630 A SCADA Compatible, RRLL
type- 4 Way RMU including Two numbers
of earthings as per Drawing (material is in
bidder's scope) and as per DGVCL
Technical specification.
Installation, Testing and commissioning
of 22KV,630 A SCADA Compatible, RRL
type-3 Way, RMU including Two numbers
of earthings as per Drawing (material is in
bidder's scope) and as per DGVCL
Technical specification.
Installation, Testing and commissioning
of 22KV,630 A SCADA Compatible, RRLL
type-4 Way, RMU including Two numbers
of earthings as per Drawing (material is in
bidder's scope) and as per DGVCL
Technical specification.
Construction of plinth for 11KV, RRL type-
3 Way (i.e Two numbers of Isolator & One
number of Breaker) Ring Main Unit as per
DGVCL's technical specification mentioned
in drawing no: Drg. 11kv-01. All required
material will be supplied by contractor.
Construction of plinth for 11KV, RRLL
type- 4 Way (i.e Two numbers of Isolator
& Two number of Breaker)Ring Main Unit
41 9925000043 as per DGVCL's technical specification No.
mentioned in drawing no:Drg. 11kv-02.All
required material will be supplied by
Construction of plinth for 22KV, RRL type-
3 Way (i.e Two numbers of Isolator & One
number of Breaker) Ring Main Unit as per
DGVCL's technical specification mentioned
in drawing no: Drg. 22kv-01. All required
material will be supplied by contractor.
Construction of plinth for 22KV, RRLL
type- 4 Way (i.e Two numbers of Isolator
& Two number of Breaker)Ring Main Unit
43 9925000045 as per DGVCL's technical specification No.
mentioned in drawing no:Drg. 22kv-02.All
required material will be supplied by
Modifications e.g.Providing and fixing of
Terminal protectors i.e. Re-use able boot
(HT Side 11/22KV, LT Side 1.1KV)
including 11/22 KV insulating taps and
L.T.(1.1 KV) insulating taps ,Busbar,
Tapping from Bus Bar (11/22 KV XLPE
cable) through P.G. Clamp for H.T.
Jumper to D.O. Fuse to bushings of
Transformer Center, providing & Fixing of
jumper and providing & fixing of Heat
Shrinkable Anti Tracking Core Insulating
Tubing (Insulation Level 11/22 KV) in H.T.
jumper , Clamping arrangement of cable
support frame on both side of existing
Over Head type Distribution Transformer
to utilize in Under Ground cable network
as per drawing & as per instruction of
Engineer incharge. All live parts i.e. PG-
Clamp, connections of D.O.fuses, HT
bushings etc . shall be covered with
fixinng of 11/22 KV HT insulating tapes. (
11/22 KV XLPE cable will be in scope of
DGVCL while all other materials will be in
bidder's scope ) .
Laying of any size of 11/ 22 KV XLPE
45 9925000047 /PILC Cable in redaymade trench or in
Labour charges for Lying of O/H XLPE
cable pole to pole
Supply of 150 mm dia (Inner), thickness
47 9925000064 25 mm, 1.0 meter long RCC half round No.
Total of schedule B1, B2& B3
(+)_______%Above, (-)_______%Below, Rate to
Net Total of Schedule ‘B1, B2 & B3:
Amount in Words: (Twenty-Five Lacs Only)
1. Whatever Steel Material removed after replacement should be credited to Store.
2. The rates are inclusive of PF & Work Contract Tax & excluding of GST.
3. Contractor has to carry out work under Bilimora town Sub-Division under Valsad-
Rural Division.
4. DGVCL will provide 1ph & 3ph LT Ariel Bunch Cable 11/22kv HT ABC with necessary
accessories to the contractor.
5. The rates are inclusive of dismantling charges of existing bare conductor and
crediting in to store & dismantling of service lines from LT bare conductor and to
provide service connections on ABC by insulated pierce connectors through service
connection box.
6. The contractor has to collect all the required materials from DGVCL store as well as
credit the dismantle material to the DGVCL store at their cost.
1. DGVCL will provide key material like M.S. materials, ABC/Bare conductors, PSC/RSJ
Poles, Insulators, Fabricated materials etc. to the contractor.
2. All fabricated items shall be fabricated as per DGVCL approved drawing and by welding
rods confirming to the relevant ISI specification and as directed by Engineer in charge.
3. Necessary electricity connection for fabricated items shall be provided by DGVCL on
payment of required charge for connection & electricity bill of the same shall be paid by the
4. All the rates are inclusive of PF and Exclusive of GST applicable time to time.
5. All steel material are to be painted as below:
(a) Scrubbing of rusted surface properly before applying the paints on to the RSJ poles &
steel fabricated materials of RSJ/PSC poles is must.
(b) Two coats of approved ISI mark red oxide (primer) is to be properly painted for the
RSJ poles & steel fabricated materials of RSJ/PSC poles.
Two coats of approved ISI mark silver paint (i.e. triple mangoes or equivalent quality silver paint)
is to be properly painted on to the RSJ poles & steel fabricated materials of RSJ/PSC poles.
Executive Engineer (O&M)
Valsad Rural Division.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. Schedule A.pdf
2. Bid Document.pdf
4. Detail Technical Specification.pdf
Amend an Arbitration Clause.pdf
GENERAL TERMS and CONDITIONS.pdf
Letter to All DISCOMs for Ratified Common UG Tender Conditions.pdf
TECHNICAL BID.pdf
TECHNICAL SPECIFICATIONS FOR THE WORK.pdf
Notice Inviting Tender.pdf
Schedule-B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .