HQ CWE (AF) Ambala Cantt-133001
CWE/AF AMB/AMB-T32/2026-27 REPAIR MAINT REPLACEMENT OF HT CABLES HT OH LINES AND ALLIED WORKS IN DOMESTIC AREA AND OTHER UNITS AT AF STN AMBALA UNDER GE AF AMBALA
2026_MES_793153_1
CWE/AF AMB/AMB-T32/2026-27
Open Tender
Civil Works
Item Rate
180 days
GE (AF) Ambala
For MES enlisted contractor Class D Category b ii and for un-enlisted contractor refer NIT
8 documents required · 8 mandatory
₹500
GE (AF) Ambala
₹80,000
Yes
9 Oct 2026
9 Oct 2026
1 Nov 2026
9 Oct 2026
30 Oct 2026
24 Oct 2026
9 Oct 2026 - 23 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking out / down faulty unserviceable 11KV HT UG cable from trenches/duct/ HT poles, nominal cross sectional area from 95 sqmm to 240 Sqmm, 3 core including disconnecting of cable and taking out PCC covers of any descriptions complete all as specified & directed.
Notes: (i) Earth work shall be measured & paid separately.
(ii) Serviceable cable covers will be kept aside for re-use. | 840 | RM | - | - |
| 2 | Supplying, laying, jointing, testing & commissioning HT 11 KV ( E) XLPE insulated cable aluminium conductor, screened with extruded semi conducting layer, insulation screening with copper tape cover laid up with PVC (ST-2) extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 part-II (1985) with amendment, Size 3 core & cross sectional area 185 Sqmm, laid in trenches/pipes/ducts or fixed along poles/wall/equipment etc. complete all as specified & directed. | 120 | RM | - | - |
| 3 | Supplying, laying, jointing, testing & commissioning HT 11 KV ( E) XLPE insulated cable aluminium conductor, screened with extruded semi conducting layer, insulation screening with copper tape cover laid up with PVC (ST-2) extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 part-II (1985) with amendment, Size 3 core & cross sectional area 120 Sqmm, laid in trenches/pipes/ducts or fixed along poles/wall/equipment etc. complete all as specified & directed. | 320 | RM | - | - |
| 4 | Supplying, laying, jointing, testing & commissioning HT 11 KV ( E) XLPE insulated cable aluminium conductor, screened with extruded semi conducting layer, insulation screening with copper tape cover laid up with PVC (ST-2) extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 part-II (1985) with amendment, Size 3 core & cross sectional area 95 Sqmm, laid in trenches/pipes/ducts or fixed along poles/wall/equipment etc. complete all as specified & directed. | 400 | RM | - | - |
| 5 | Excavation in trenches, not exceeding 1.5mtr wide & not exceeding 1.5mtr in depth; for foundation, laying/taking out pipes/cables etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10sqm on plan & not exceeding 1.5mtr in depth and getting out, in soft/loose type of soil complete all as specified & directed. | 220 | Cum | - | - |
| 6 | Excavation in trenches, not exceeding 1.5mtr wide & exceeding 1.5mtr but not exceeding 3.0mtr in depth; for foundation, laying/taking out pipes/cables etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10sqm on plan & not exceeding 1.5mtr in depth and getting out, in soft/loose type of soil complete all as specified & directed. | 1 | Cum | - | - |
| 7 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm thick each in soft/loose type of soil complete all as specified & directed. | 159 | Cum | - | - |
| 8 | Removal of surplus excavated soil to a distance not exceeding 50 mtr & depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified & directed. | 61 | Cum | - | - |
| 9 | Material and labour sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cm deep after laying the cable (punned down to 18 cm depth after laying and stretching of cable ) complete all as specified & directed. | 48 | Cum | - | - |
| 10 | Supply & laying un-reinforced precast concrete cable cover , Class HVP type-1 with flat, size 300mm x 180mm x 40mm, laid flat for protection of cable, adjacent to each other, perpendicular to central axis of cable complete all as specified & directed. | 2,800 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
TenderT32.pdf
Tender Documents • 0.77 MB
BOQ_889444.xls
BOQ • 8.83 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .