Loading…
Loading…
Tender ID
Tender Value
₹16.5 L
EMD Value
₹33,076
Closing Date
13 Feb 2026, 4:00 pmClosed
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Providing and installation of 58 KVA electric Generator set with Servo Stabilizer and allied accessories at Divisional Commissioner Office Kashmir
2026_PWDJK_301728_1
NIT No.269/2025-26 Dt/29/01/2026
Open Tender
Electrical Works
Percentage
10 days
Srinagar
Please refer Tender documents.
4 documents required · 4 mandatory
₹800
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹33,076
29 Jan 2026
29 Jan 2026
14 Feb 2026
29 Jan 2026
13 Feb 2026
29 Jan 2026
Supply, installation, mechanical erection, testing and commissioning of three phase 58.5 + KVA diesel generator set KIRLOSKAR/Cummins/ Mahindra make/ equivalent standard make as desired by engineer incharge. ( sample to be approved before installation),coupled to suitable alternator of 415 V, AC, 3-Phase 0.8 p.f. mounted on a 1) M.S. Fabricated base frame.,2) M.S. fuel tank of required capacity.,3) Residual Silencer with required arrangements for exhaust to the exterior as directed.,4) AMF Control Panel.5) Suitable batteries with lead.,5) First fill of lube oil.,6) Acoustic Enclosure complete with all accessories and 7)Testing equipments as specified and directed by the department conforming to IS comprising the Technical Specification.. as per manufacturer.8) first fuel fill, turbo charged developing required BHP 1500 RPM under NTP with 10 % overloading factor, , with microprocessor based digital display genset engine controller for monitoring, metering, protection, control system etc. conforming to latest Govt. Emission norms CPCB-IV +, Test certificate to be provided by the manufacturer.Refer Annexure-A for technical Specification
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and laying in position reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required (excluding reinforcement).
Carrying out Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete, with Mild steel and medium tensile steel bars
Design,Supplying,Installation,Testing and Commissioning of Cubical Type double door, outdoor LT Panel Board Suitable for 415 V 3 Phase 4 Wire 50 HZ AC Supply System including Incomers,Out Goings,Bus Bars etc. as required as per the Following Description.(IP:42) General Floor Distribution Panel.The successful tenderer shall take prior approval for the panel builder/fabricator alongwith G.A. drawing, wiring diagrams, single line diagram before start of fabrication of LT panel.Circuit breaker shall be capable of carrying the full load current defined for 50 degree Celsius without any derating.The Panel Builder Shall be CPRI /ERDA/ANY NABL ACCREDITED LAB approved. Size of wiring for CTS:- 2.5 sqmm, Size of wiring for voltage sensing Metering :-4.0 Sq.mm, Size of wiring of all push buttons, indicating lamps:-1.5 Sq.mm,Types of wires:-PVC insulated 1100V grade ,Multistrand copper conductor Flexible FR-LSH, Hinged Door Earthing:-Device mounted hinged doors connected to cubicles body by means of 2.5 sqmm.green copper flexible wire, The Complete Panel Shall be Made out of 2.0 mm CRCA sheet including Frame/Partitions/Doors etc, Gland Plates to be 3.0 mm Thick. ( As per approved design,size may vary as per site requirement)
Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
Normal INCOMING:
a)250 Amp TPN MCCB 50 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens/ eq. make to be approved by EIC.
b) 400 amp 4 strip bus 1 No.
d) onload Change over switch 250 Amp for generator.Front operated.
b) 400 amp 4 strip bus 1 No.
OUTGOING:
a)200 Amp TPN MCCB 50 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens / eq. make to be approved by EIC..
a)100 Amp TPN MCCB 36 K including spreader links including spreader links, icu=ics=100% ( Adjustable thermal and Adjustable magnetic release ) Legrand/ Shinider/Semiens / eq. make to be approved by EIC..
c) space for 18 way MCB's
S/L , testing and commissioning of PVC XLPE insulated alluminium armoured cable 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments.Havell/Eq. standard make as directed by engineer incharge and making end termination with brass compression gland and aluminium lugs of required size.
d)95 sq.mm 3.5 core
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor (Havell/Polycab/ Fenolex/ Anchor / eq. make to be approved by EIC..), single core cable in surface/ recessed medium class PVC conduit/duct as required.
( c ) 2 X6 sq. mm + 1 X 6 sq. mm earth wire
( b )2 X 10 sq. mm + 1 X 6 sq. mm earth wire
(f) 2 X 16 sq. mm + 1 X 6 sq. mm earth wire
Engaging of skilled labour/ Electrician for Dismentling of old damaged materials like wires in scraps, fixtures switches-sockets complete as directed by the engineer at site and stacking and handing over to concerned department including carrying out some repairing works etc.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.07 MB
BOQ_978957.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .